2006-11-16 11:34:34BUILDING REVISION CHECKLIST (REVISION DONE UNDER FBC
 2004 AS SPECIFIED ON PLANS):
 1- SHEET A-1.0:
 A) REVISE TYPE OF CONSTRUCTION. SEE SEC. 602 FBC
 2004. TYPE OF CONSTRUCTION SHOWN ON PLANS APPLIES TO
 TYPE IIIB.
 B) ADD 2004 FLORIDA RESIDENTIAL CODE, WHICH IS THE
 ONE THAT APPLIES TO SINGLE FAMILY RESIDENCES.
 C) AREA CALCULATIONS ON SHEET A-1.0 ARE DIFFERENT
 THAN THOSE SHOWN ON SHEET A-1.1. REVISE AS REQUIRED.
  
 2- TRUSS DRAWINGS WILL BE REQUIRED FOR REVIEW PRIOR TO
 INSTALLATION. SEE SEC. R802.10 FOR REQUIRED
 INFORMATION.
  
 3- NOTICE OF COMMENCEMENT IS EXPIRED AFTER 90 DAYS OF
 BEING RECORDED IF WORK IS NOT STARTED. SEC. 713.13(2)
 FLORIDA STATUTES. NEED RE-RECORDED NOTICE OF
 COMMENCEMENT.
  
 4- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY CHAPTER
 13 FBC 2004.
  
 5- BRING DRAWINGS TO PALM BEACH COUNTY FOR IMPACT FEES
 REVISION. BRING BACK STAMPED DRAWINGS AND PAID RECEIPT
 IF ADDITIONAL FEES ARE DUE.
  
 6- PROVIDE COMPLETE INFORMATION FOR STORM SHUTTERS
 UNDER A SEPARATE PERMIT AS AGREED ON AT TIME OF
 ORIGINAL PERMIT APPLICATION APPROVAL.
  
 7- OWES ADDITIONAL FEES FOR UPDATED BUILDING VALUATION
 AND RADON FEES. FEES WILL BE CALCULATED WHEN ITEM 1(C)
 ABOVE IS CLARIFIED.
  
 8- PROVIDE PRODUCT APPROVAL AS REQUIRED BY RULE 9B-72
 FOR:
 A) INSWING ENTRY DOOR AS SHOWN ON PLANS.
 B) IMPACT SLIDING GLASS DOORS AS SPECIFIED ON
 PLANS.
 C) PRECAST CONCRETE LINTELS AS SPECIFIED ON PLANS.
 D) ALL SIMPSON OR USP CONNECTORS SPECIFIED ON FRAMING
 PLANS AND DETAILS.
 E) GARAGE DOOR. NEED CLEAR AND LEGIBLE DRAWINGS.
 CLARIFY IF USING THE DADE COUNTY NOA OR FLORIDA PRODUCT
 APPROVAL 4861. PROVIDE COMPLETE PACKAGE FOR EITHER ONE,
 BUT DON'T MISMATCH ONE WITH THE OTHER.
 F) ASPHALT SHINGLES. DOWNLOAD DADE COUNTY NOA
 04-0305.03 WHICH IS THE CORRECT NOA THAT WAS SUBMITTED
 TO OBTAIN FLORIDA PRODUCT APPROVAL #FL183-R1. GO TO
 WWW.FLORIDABUILDING.ORG TO DOWNLOAD ALL INFORMATION. G)
 SINGLE HUNG WINDOWS.
  
 9- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITTING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 10-SPECIFY SAFETY GLASS IN WINDOW LOCATED IN MASTER
 BATH TUB. SEC. R308.4 2004 FLORIDA RESIDENTIAL CODE.
  
 11- 2ND FLOOR ATTIC ACCESS SHALL BE IN HALLWAY OR
 ALREADY ACCESSIBLE LOCATION. REVISE AS REQUIRED. SEC.
 R807.1 2004 FLORIDA RESIDENTIAL CODE.
  
 12- ENGINEER TO PROVIDE ALL HIS INFORMATION AND FIRM'S
 CERTIFICATE OF AUTHORIZATION AS REQUIRED BY SEC.
 61G15-23.002 OF FLORIDA ADMINISTRATIVE CODE.
  
 13- ARCHITECT TO PROVIDE ALL HIS INFORMATION AND FIRM'S
 INFORMATION AS REQUIRED BY SEC. 61G1-16.004 OF FLORIDA
 ADMINISTRATIVE CODE.
  
 14- SURVEY TO HAVE ORIGINAL SIGNATURE AS REQUIRED BY
 CHAPTER 472 FLORIDA STATUTES.
  
 15- SHEET A-2.1:
 A) FLOOR PLAN CALLS FOR ONE 16'X7' GARAGE DOOR.
 ELEVATION SHOWS 2 SMALL GARAGE DOORS. CLARIFY/REVISE AS
 REQUIRED TO MATCH.
 B) REVISE ELEVATIONS ORIENTATION. SEE SURVEY FOR
 CORRECT ORIENTATION.
  
 16- SHEET A-3.1:
 A) PORCH SECTION AND TYP. WALL SECTION CALL FOR
 "ASPHALT TILE ROOF". CLARIFY WHAT IS IT?. REVISE AS
 REQUIRED.
 B) CHANGES DONE BY HAND ARE NOT ACCEPTABLE. EG:
 STUCCO THICKNESS. REVISE ORIGINAL DRAWINGS AS
 REQUIRED.
  
 17- SHEET A-4.1:
 A) DETAIL #1 IS FOR WINDOW AND DOOR BUCK DETAIL.
 CLARIFY TITLE SAYS WINDOW, WHILE DETAIL SAYS DOOR
 FRAME.
 B) THERE ARE TWO DIFFERENT SPECS FOR BUCK FASTENING.
 SEE DETAIL 1 AND WINDOW/DOOR BUCK NOTES ON SHEET S-2
 AND REVISE AS REQUIRED.
 C) HURRICANE PANEL DETAIL: EDGE DISTANCE IS
 INCORRECT. STUCCO THICKNESS CAN'T BE CONSIDERED FOR
 EDGE DISTANCE. REVISE AS REQUIRED. SEE ACTUAL STORM
 PANELS PRODUCT APPROVAL.
 ***NOTE: THIS DETAIL IS NOT REQUIRED. IT'S EASIER AND
 WILL AVOID DISCREPANCIES IF ONLY THE PRODUCT APPROVAL
 FOR STORM SHUTTERS IS SUPLLIED WHEN APPROVED BY THE
 DESIGNER OF RECORD.
 D) SECTION AT REAR PORCH: SPECIFY LEDGERS FOR ROOF
 SHEATHING SUPPORT AT MASONRY WALL. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
 C) SPECIFY FIREBLOCKING. SEC. R602.8 2004 FLORIDA
 RESIDENTIAL CODE.
  
 18- SHEET S-2:
 A) REVISE WINDOW NOTES. NEED WINDOWS FOR 140 MPH
 INSTALLATION, NOT 120. REVISE ORIGINAL DRAWING. HAND
 CHANGES ARE NOT ACCEPTABLE.
 B) BEARING WALL CONNECTION TO CBS DETAIL AND DETAIL
 1/S-2: CLARIFYIF USING SIMPSON OR USP CONNECTORS. C)
 DETAIL 1/S-2 CALLS FOR (3)2X4 STUDS, WHILE 2ND FLOOR
 FRAMING PLAN CALLS FOR (4)2X4 STUDS. CLARIFY/REVISE AS
 REQUIRED TO MATCH.
 D) SPECIFY ROOF TRUSS CONNECTORS FOR REAR PORCH
 ROOF.
  
 19- SHEET S-3:
 A) REVISE PLYWOOD SHEATHING NAILING SCHEDULE FOR
 ROOF SHEATHING. SEE TABLE 2304.9.1 FBC 2004 AND REVISE
 AS REQUIRED.
 B) SPECIFICATION GIVENON PLYWOOD SHEATHING NAILING
 SCHEDULE AND OVERHANG DETAIL DON'T MATCH. REVISE AS
 REQUIRED.
 C) CONNECTOR SCHEDULE: REVISE UPLIFT AND FASTENERS
 SPECIFIED FOR SIMPSON HETAL 16 AND SP4. SEE CURRENT
 CATALOGUE AND UPDATE AS REQUIRED. OTHERWISE, PROVIDE
 COMPLETE ENGINEERING ANALYSIS FOR VALUES AND NUMBERS
 THAT ARE DIFFERENT FROM THOSE TESTED AND PUBLISHED BY
 MANUFACTURER. SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004.
 D) MAXIMUM DESIGN PRESSURES SHOWN ARE LOW COMPARED
 TO TABLE 1609.6B OR TABLES IN ASCE 7-02.PROVIDE
 ACTUAL CALCULATIONS SHOWING HOW THE MAXIMUM POSITIVE
 AND NEGATIVE LOADS ARE DETERMINED. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712