Plan Review Notes For Permit 05090825 |
Permit Number |
05090825 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-08-21 00:00:00 | *** DENIED *** | | 1) JOB ADDRESS MUST APPEAR ON ALL PAGES | | OF PLANS. | | | | 2) MECHANICAL PLANS EQUIPMENT LIST SHOWS | | AHU IS A 10 SEER AND CONDENSER UNIT IS A | | 12 SEER, PLEASE SHOW THE SEER OF THE | | SYSTEM ONLY. AND SHOW THE TOTAL BTU'S. | | AND SENSIBLE BTU'S. OF THE A/C SYSTEM. | | | | 3) PLEASE SHOW ON MECH. PLANS THE SIZE | | OF THE RETURN AIR GRILL TO THE AIR | | HANDLER. | | | | 4) RETURN AIR TRANSFER DUCTS TO | | BEDROOMS, THE GRILLS ARE TO SMALL FOR | | THE DUCTS. | | | | 5) SUPPLY AIR DUCT TO SECOND FLOOR | | CLOSET #2 NEEDS TO BE SIZED. | | | | 6) PLEASE EXPLAIN WHY A 7" SUPPLY AIR | | DUCT IS GOING TO THE SMALL CLOSET IN THE | | HALL. | | | | 7) PLEASE SUBMIT MANUAL D CALCULATIONS | | FOR RESIDENTIAL DUCT DESIGN, PER 2004 | | FBC/R M1601.1 AND FBC 13-610.1.ABC.1 . | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|