Plan Review Notes For Permit 05090802 |
Permit Number |
05090802 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-09-21 00:00:00 | ** UNSAT ** | | | | 1)NOTE: PLEASE SEE 250.66 FOR MIN | | GROUNDING ELECTRODE CONDUCTOR. 2/0 MIN, | | A #2 IS SHOWN ON PART OF THE RISER AND | | 2/0 ON OTHER PART. | | | | 2)NOTE: PLEASE INDICATE THE GROUNDING | | ATTACHMENT FOR TRANSFORMERS PER | | 250.30,AND GROUNDING ELECTRODE SIZE FOR | | SEPARATELY DERIVED SYSTEMS. | | 250.66 | | | | 3)NOTE: PLEASE SEE THE "EQUIPMENT | | GROUNDING CONDUCTORS" ARE ONLY INSTALLED | | AFTER THE FIRST MEANS OF DISCONNECT. | | PLEASE REMOVE ALL "EQUIPMENT GRNDS" UP | | TO THE FIRST MEANS OF DISCONNECT. | | | | 4)NOTE: PLEASE SEE LOADS INDICATED ON | | PANELS "A" ARE THE SAME LOADS SHOWN ON | | "H-1". PLEASE SEE LOADS ON 277/480V | | PANEL FOR THESE 120/208V PANELS WOULD | | NOT BE THE SAME. | | PLEASE VERIFY LOADS AND ADJUST. | | | | 5)NOTE: PLEASE NOTE: ANY COLD | | WATER/PIPING/SPRINKLER STAND PIPE | | SYSTEMS IN BLDG SHALL BE BONDED TO THE | | GROUNDING ELECTRODE SYSTEM. | | PLEASE SEE WATER PIPE SYSTEM TO SITE | | SHALL BE PART OF THE GROUNDING ELECTRODE | | SYSTEM. | | 250.50,250.104 | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|