2005-10-14 00:00:00 | 1)713.13 F.S.A NOTICE OF COMMENCEMENT |
| SHALL BE RECORDED AT PALM BEACH COUNTY |
| COURTHOUSE AND A COPY SUBMITTED TO THIS |
| OFFICE BEFORE A PERMIT CAN BE ISSUED. |
| BLANK FORMS ARE AVAILABLE FROM THIS |
| OFFICE. |
| NOTE: THE NOTICE OF COMMENCEMENT MUST BE |
| RE-RECORDED IF THE DESCRIBED IMPROVEMENT |
| OR CONSTRUCTION IS NOT COMMENCED WITHIN |
| 90 DAYS OF RECORDING. |
| |
| 2) 713.13(2) F.S.THE NOTICE OF |
| COMMENCEMENT MUST BE RE-RECORDED BECAUSE |
| HE DESCRIBED IMPROVEMENT OR |
| CONSTRUCTION DID NOT COMMENCE WITHIN 90 |
| DAYS OF RECORDING. |
| |
| 3) THE SHEET WHICH SHOWS THE APPROVAL |
| STATUS OF THE STORM PANELS IS MISSING |
| FORM THE REPORT. |
| |
| 4) INDICATE THE TYPE OF SYSTEM WHICH |
| WILL BE USED TO INSTALL THE PANELS. |
| PLEASE DO SO BY HI-LIGHTING OR CIRCLING |
| EACH DETAIL TO BE USED. |
| |
| 5) THE ANCHOR SCHEDULE NEEDS TO SPECIFY |
| WHICH TYPE OF FASTENER WILL BE USED. |
| ALSO, THE MAXIMUM DESIGN PRESSURE RATING |
| AND CORRESPONDING MAXIMUM ANCHOR SPACING |
| SCHEDULE SHALL BE INDICATED ON THE |
| CHARTS. |
| |
| 6)THE SHEET WHICH REFERS TO ASCE-7-98 IS |
| NOT LEGIBLE.ALL INFORMATION FILED FOR |
| RECORD SHALL BE OF SUFFICIENT |
| CLARITY.FBC.104.2.1 |
| |
| MYRON JACOBS |
| BUILDING PLAN REVIEWER |