Plan Review Notes For Permit 05090750 |
Permit Number |
05090750 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-11-14 00:00:00 | PLAN DENIED | | 1) PLEASE SHOW DISTRIBUTION BOXES ON | | MAIN TRUNKLINE ON MECHANICAL PLANS | | 2) PLEASE REFER TO SECTION 601.4 | | BALANCED RETURN AIR 2001 FBC(M). | | 3) PLEASE REFER TO 606.2.1 SUPPLY AIR | | SYSTEMS SMOKE DETECTORS,AND 606.4.1 | | SUPERVISION. | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|