2005-11-03 00:00:00 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBC FLORIDA BUILDING CODE 2001 |
| FBC* CITY OF WEST PALM BEACH AMENDMENTS |
| TO THE FBC2001 |
| |
| 1.)A NOTICE OF COMMENCEMENT MUST BE |
| FILED WITH THE CLERK OF COURTS BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2.)SHOW ACCESSIBLE PARKING DIMENSIONS |
| FOR THE SPACE AND THE ACCESS AISLE, |
| FBC11-4.6.THIS IS SHOWN ON L-1. |
| |
| 3.)PROVIDE FINISHED FLOOR ELEVATIONS |
| OR SLOPE FOR THE ACCESSIBLE ROUTE |
| (SIDEWALK TO ENTRANCE) AND A RAMP |
| DETAIL, FBC11-4.8.SHEET ID-0.2. |
| |
| 4.) PLEASE DECLARE OCCUPANCY FOR THE |
| ADJACENT TENANT SPACE. |
| |
| 5.) THE BLOCK WALL APPEARS TO BE A |
| TENANT SEPARATION; PLEASE INDICATE AS |
| SUCH. SHOW FIRE RATING OF THE EXISTING |
| TENANT SEPARATION SHOWN; S4-ID4.0 REFERS |
| TO U419 BUT SHOULD ALSO INDICATE RATING. |
| INDICATE FIRE RATING OF THE BLOCK WALL. |
| SHEET ID-2.0 REFERS TO A 1 HOUR |
| OCCUPANCY SEPARATION OF AN HOUR IN THE |
| FORM OF A NOTE, AND DOOR B IS SHOWN AS |
| AN EXISTING FIRE RATED DOOR.SHOW THE |
| FIRE RATING FOR THE DOOR.NO OCCUPANCY |
| SEPARATION SHOWN ON THE PLAN. |
| |
| 6.)PROVIDE A ROOM DESIGNATION FOR THE |
| ROOM WHICH HAS ACCESS TO THE EXTERIOR |
| BUT NOT ACCESS FROM THE OTHER SPACE |
| (ADJACENT TO THE MODEL KITCHEN). |
| DECLARE AN OCCUPANCY FOR THIS AREA.IF |
| IT IS ACCESSORY STORAGE, PROVIDE |
| INFORMATION AS TO WHAT WILL BE STORED. |
| SHOW ANY REQUIRED TENANT OR OCCUPANCY |
| SEPARATIONS. |
| |
| 7.)THE MAXIMUM TRAVEL DISTANCE WHEN |
| SCALED IS 73.5' RATHER THAN 70' AS |
| INDICATED ON THE PLAN.THE PATH OF |
| TRAVEL IS SHOWN GOING THROUGH FURNITURE, |
| SEE ID2.1.ALSO THE PATH OF TRAVEL IN |
| SOME PLACES IS AGAINST (OR VERY CLOSE |
| TO) THE WALL; PLEASE SHOW A NATURAL PATH |
| OF TRAVEL.IF THE TRAVEL DISTANCE |
| EXCEEDS 75' A SECOND EGRESS DOOR IS |
| REQUIRED, FBC1020.1(4). |
| |
| 8.)IS THIS BUILDING SPRINKLED? PROVIDE |
| FIRE SPRINKLER PLANS, FBC104.3.1.1. |
| |
| 9.)SPECIFY MINIMUM INTERIOR FINISH |
| CLASSIFICATION, FBC803.2. |
| |
| 10.)SHOW EXIT SIGNS, FBC1016.3. |
| |