Plan Review Notes
Plan Review Notes For Permit 05090679
Permit Number 05090679
Review Stop E
Sequence Number 2
Notes
Date Text
2005-11-22 00:00:00 
 THE COMMENTS FOR THIS REVIEW ARE THE
 SAME AS THE LAST REVIEW.
  
 THE ENGINEER OF RECORD NEEDS TO INDICATE
 IF THE "PANEL" SHOWN ON SHEET 2 OF 3
 ELECTRICAL SCHEMATIC IS NEW OR EXISTING.
 IF IT IS NEW PLEASE SUBMIT DETAILS FOR
 THE PANEL SHOWN ON THE SCHEMATIC, FEEDER
 AND CONDUIT SIZE AND TYPE, PANEL RATING
 AND OCP, PANEL SCHEDULE AND COMPUTED
 LOAD.
  
 MR KOVNER NEEDS TO CALL ME REGARDING
 THIS MATTER IF THERE ARE ANY QUESTIONS.
  
 ALSO THE ELECTRICAL CONTRACTOR
 SUBMITTING THE PANEL SCHEDULE HAS AN
 INCORRECT ADDRESS. THE PANEL SCHEDULE
 ALONE DOES NOT RESPOND TO ALL OF THE
 COMMENT. FEEDER CONDUIT AND CONDUCTOR
 SIZES ARE NOT ADDRESSED, AND MAY NOT
 NEED TO BE IF THE PANEL ON THE SCHEMATIC
 IS EXISTING, ONE OF THE ISSUES THE
 ENGINEER OF RECORD HAS NOT CORRECTED.
  
 DO NOT RESUBMIT WITHOUT A CORRECTED
 WIRING SCHEMATIC. SEE FLORIDA STATUTE
 553.80, ATTACHED.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  
  