Plan Review Notes
Plan Review Notes For Permit 05090679
Permit Number 05090679
Review Stop E
Sequence Number 1
Notes
Date Text
2005-09-23 00:00:00 
 THE ENGINEER OF RECORD NEEDS TO INDICATE
 IF THE "PANEL" SHOWN ON SHEET 2 OF 3
 ELECTRICAL SCHEMATIC IS NEW OR EXISTING.
 IF IT IS NEW PLEASE SUBMIT DETAILS FOR
 THE PANEL SHOWN ON THE SCHEMATIC, FEEDER
 AND CONDUIT SIZE AND TYPE, PANEL RATING
 AND OCP, PANEL SCHEDULE AND COMPUTED
 LOAD.
  
 MR KOVNER NEEDS TO CALL ME REGARDING
 THIS MATTER IF THERE ARE ANY QUESTIONS.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved