Plan Review Notes
Plan Review Notes For Permit 05090634
Permit Number 05090634
Review Stop B
Sequence Number 2
Notes
Date Text
2005-09-30 00:00:00*******DENIED*******
 MYRON JACOBS(561) 805 6726
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 1) FBC 1606.2.5THE SYSTEM SELECTED
 FROM THE SUBMITTED FLAT ROOF PRODUCT
 APPROVAL NOA HAS A MAXIMUM DESIGN
 PRESSURE OF LESS THAN -89 PSF AND CITES
 GENERAL LIMITATION #9 (SEE PAGE 39 OF
 45).GENERAL LIMITATION #9 PROHIBITS
 RATIONAL ANALYSIS OR EXTRAPOLATION TO
 ENHANCE THE UPLIFT PRESSURE AT PERIMETER
 AND CORNER AREAS BY REDUCING THE
 FASTENER SPACING IN THESE AREAS.EITHER
 SELECT AN ALTERNATIVE SYSTEM (OR PRODUCT
 APPROVAL) THAT DOES NOT CITE GENERAL
 LIMITATION #9.ALTERNATIVELY IF THE
 SELECTED SYSTEM DOES CITE GENERAL
 LIMITATION #9, IT MUST HAVE A MAXIMUM
 DESIGN PRESSURE THAT EXCEEDS THE
 PRESSURE IN ROOF ZONE 3 (TYPICALLY -89
 PSF FOR MEAN ROOF HEIGHT OF 30 FEET OR
 LESS).
  
 2) FL#560-R1 IS NOT APPROVED ON THE
 STATE WEB-SITE. CHOOSE AN APPROVED
 PRODUCT AND SUBMIT IT FOR PLAN REVIEW.
 THE REPORT ON THE WEB-SITE IS A SBCCI
 REPORT.
  
 3) SEE PREVIOUS NOTES FROM ROB MCDOUGAL
  
 BUILDING PLAN REVIEW
 MYRON JACOBS.
 TEL: (561)805-6726
 FAX: (561)659-8026
 [email protected].
  
  
  