Plan Review Notes For Permit 05090602 |
Permit Number |
05090602 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-09-23 00:00:00 | ******DENIED****** | | | | 1) PLANS ONLY SHOW ONE PIV. TAMPER | | SWITCHES ARE REQUIRED FOR EACH BUILDING. | | | | 2) ELECTRONIC SWITCHES WITH CHAIN AND | | LOCK WILL BE REQUIRED FOR DOUBLE CHECK | | DETECTOR ASSEMBLY. | | | | 3) FIRE ALARM PANELS THAT MONITOR | | SPRINKLER SYSTEMS SHALL BE UL CERTIFIED | | FOR CENTRAL STATION SERVICE. | | | | 4) FIRE ALARM TO BE CLASS A, STYLE D OR | | FULLY ADDRESSABLE. | | | | 5) PLEASE PROVIDE A COPY OF THE CONTRACT | | TO VERIFY VALUE FOR ENTIRE PROJECT. | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | FIRE PLAN REVIEW (561) 805-6722 |
|