Plan Review Notes
Plan Review Notes For Permit 05090568
Permit Number 05090568
Review Stop P
Sequence Number 2
Notes
Date Text
2006-05-17 00:00:00DENIED
 REFERENCE: FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHTS P2.1.1, P2.2.4, P3.1.1, P3.2, &
 P3.2.4 SEAL DOES NOT IMPART INFORMATION
 REQUIRED FOR THE IMPRESSION TYPE SEAL.
 SIGNATURE REQUIRED ON THE SEAL, INITIALS
 DO NOT MATCH SIGNATURE ON OTHER PLUMBING
 SHEETS. 61G15-23.002(1) & FS R71.025.
 ALSO SEE 61G15-23.001, AND ATTACHED
 SHEET CONCERNING SEAL MANDATE FROM THE
 FLORIDA BOARD OF PROFESSIONAL ENGINEERS.
  
 2. SHTS P2.1.1, P3.1.1 THE SANITARY
 BUILDING DRAIN SHALL BE A MINIMUM OF 4
 FT. OFF THE FOOTER PER SECTION 307.4.
  
 3. SHTS P2.2.4, & P3.2.4 FLOOR PLAN AND
 RISER DIAGRAM SHOW THE KITCHEN SINK ARMS
 RUNNING ABOVE THE FLOOR AND IN FRON OF
 THE RANGE. PLEASE CLARIFY. SECTION
 104.2.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]