Date |
Text |
2006-05-14 00:00:00 | ************** UNSAT 2ND REVIEW ******** |
| |
| **PLEASE SEE SOME NOTES FROM PREVIOUS |
| REVIEW STILL NEED TO BE ADDRESSED. |
| PLEASE ALSO SEE SOME NEW NOTES DUE TO |
| CHANGES IN PLANS. |
| |
| |
| SUB 1)NOTE: OK |
| |
| |
| |
| 1)NOTE: NOTE #1 OK, HOWEVER SEE NEW |
| NOTES DUE TO NEW SERVICE FOR BLDG BEING |
| SHOWN. SEE NEW NOTES LISTED SEPARATELY |
| BELOW. |
| |
| |
| 2)NOTE: NOTE #2 NO: |
| ** PLEASE SUBMIT AIC RATINGS FOR |
| ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| RATED FOR THE AVAILABLE FAULT CURRENT. |
| PER 110.9/215.5 |
| AIC RATINGS ARE SHOWN FOR EACH PANEL, |
| BUT WILL ALSO BE REQUIRED FOR MAINS.(NEW |
| SERVICE). |
| PLEASE SEE CALCUALTIONS SUBMITTED ARE |
| BASED ON UNIT MAINS, WHICH ARE OK, |
| HOWEVER PLEASE SEE THE MAIN IS ALSO |
| REQUIRED. THE SEC'S ARE NOT 2/0'S. |
| |
| |
| 3)NOTE: NOTE #3 OK, |
| |
| 4))NOTE: NOTE #4 OK |
| |
| 5)NOTE: NOTE #5 OK. |
| |
| 6)NOTE: NOTE #6 OK. |
| |
| 7)NOTE: NOTE #7 NO, ??PLEASE SEE THIS |
| COULD NOT BE LOCATED ON LOAD CALCS. |
| PLEASE SEE 220.3B4.PANEL SCHEDULE |
| MENTIONS RECESSED LTS, HOW MANY, AND |
| WATTAGE PER FIXTURE NOT SHOWN. |
| PLEASE SHOW ALL RECESSED LTS BASED ON |
| MAX WATTAGE FOR FIXTURE(S). THIS NEEDS |
| TO BE SHOWN ABOVE THE GEN. KT/RECEPT |
| LOADS. THIS SHOULD BE ABOVE THE FIGURED |
| 3W/PER SQ FT. |
| PLEASE PROVIDE FIXTURE INFORMATION ON |
| LEGEND. |
| |
| 8)NOTE: NOTE #8 NO, PLEASE SEE AN EFFORT |
| WAS MADE TO LIST THESE, HOWEVER PLEASE |
| SEE LISTING INDICATES "GFI" WHEREAS |
| "AFCI" PROTECTION IS REQUIRED. |
| |
| ** PLEASE LIST ALL THE REQUIRD ARC |
| FAULT PROECTED CIRCUITS AS REQUIRED PER |
| 2002 210.12 |
| PLEASE KNOW, SD'S ARE BEING SHOWN |
| CIRCUITED TO KITCHEN LIGHTING CIRCUIT, |
| THIS IS OK, HOWEVER PLEASE KNOW, THIS |
| WOULD ALSO REQUIRE ARC FAULT PROTECTION |
| FOR THIS ADDITIONAL CIRCUIT. |
| THIS IS ONLY A NOTE: |
| |
| 9)NOTE: NOTE #9 OK, NOTE WAS ADDED TO |
| PLANS, HOWEVER PLEASE SEE SD'S ARE STILL |
| BEING SHOWN WITHIN 20' OF COOKING |
| APPLIANCES. THIS IS PERMITTED, HOWEVER |
| PLEASE SPECIFY THE SD TO BE INSTALLED IN |
| ORDER TO MEET EXCEPTION AS LISTED. |
| |
| *PLEASE SEE SOME NEW SHEETS WERE ADDED |
| WITH COMPLETE NOTE REVISED, HOWEVER NOT |
| ALL SHEETS?? |
| |
| **PLEEASE SEE NFPA-72 (2002) |
| EDITION,11.8.3.5. |
| PLEASE PLACE NOTE ON PLANS WHICH STATES |
| LOCATIONS OF SD'S TO BE A MIN OF 3' FROM |
| BATH(S) AND KITCHEN DOORS AND 20' FROM |
| KITCHEN COOKING APPLIANCES. |
| ** PLEASE SEE EXCEPTION TO 20' FROM |
| COOKING WITH TYPE OF SD USED.** |
| PLEASE SEE PLANS SHOWS A SD IN KITCHEN |
| AREA AT THIS TIME. |
| |
| 10)NOTE: NOTE #10 OK. |
| |
| 11)NOTE: NOTE #11 NO. |
| THIS IS REQUIRED ON ALL SHEETS. |
| |
| **PLEASE SEE ARCHITECTS TITLE |
| BLOCK SHALL ALSO CONTAIN THE PRINTED |
| LICENSE NUMBER FOR ARCHITECT OF RECORD. |
| FAC 61G1-16.004. |
| PLEASE SEE THIS WAS NOT DONE FOR OLD |
| SHEETS, ONLY NEW. |
| PLEASE SEE THIS COMMENT IS FOR ALL |
| TRADES AND FOR ALL SHEETS WHETHER OR NOT |
| COMMENT IS MADE BY OTHER REVIEWER(S). |
| PLEASE KNOW THIS COMMENT DOES NOT APPLY |
| TO KAMM CONSULTING'S TITLE BLOCK. |
| |
| ********** NEW NOTES ************* |
| |
| 1)NOTE: PLEASE SEE 250.66 FOR MIN |
| GROUNDING ELECTRODE CONDUCTOR REQUIRED. |
| #4 AWG SHOWN, MIN 3/0 AWG REQUIRED |
| |
| 2)NOTE: PLEASE SEE NO SEC'S ARE SHOWN |
| FOR SERVICE.??PLEASE SEE 240.4, 310.16 |
| |
| 3)NOTE: PLEASE INDICATE THE OCP AT THE |
| METER CENTER FOR ALL UNIT BRKRS.215.5 |
| |
| 4)NOTE: PLEASE SHOW SERVICE ON PLANS. |
| PLEASE SEE ELECTRICAL PLANS DO NOT |
| INDICATE THE LOCATION OF SERVICE ON |
| EITHER END OF BLDG. PLEASE ALSO NEEDS TO |
| BE SHOWN ON THE A-SHEETS, FLR PLANS, |
| ELEVATION. |
| |
| 5)NOTE: PLEASE SEE PLANS SHALL CONTAIN |
| THE SIGNATURE OF THE ENGINEER OF RECORD. |
| PLEASE SEE NEW SHEETS CONTAIN "INITIALS" |
| ONLY AND DO NOT CORRELATE WITH THE |
| ORIGINAL PLANS. |
| FS 471.025, FAC 61G15-23.002 |
| PLEASE SEE THIS IS REQUIRED FOR ALL |
| SHEETS AND FOR ALL TRADES. PLEASE SEE |
| PLUMB SHEETS WHICH ARE ALSO INITIALED. |
| PLEASE SEE "RAISED SEAL" SHALL BE CLEAR |
| AND VISABLE WITH ALL INFORMATION ON |
| SAID SEAL. PLEASE SEESHEETS, |
| INFORMATION ON SEAL IS NOT VISABLE EVEN |
| WHEN "SHADOWED WITH PENCIL". |
| |
| 6) NOTE: PLEASE SEE MISSING EQUIPMENT |
| GROUNDING CONDUCTOR FROM MAINS TO PANELS |
| IN UNITS. 250.110,250.24,250.122 |
| |
| PLEASE SEE ANY OTHER POSSIBLE COMMENTS |
| FROM OTHER TRADES WHICH MAY AFFECT |
| ELECTRICAL PLANS. |
| |
| PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| ONLY INSERT NEW REVISED SHEETS INTO |
| COMPLETE SETS FOR REVIEW AND STAMPING. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE IN CONTACTING |
| THIS OFFICE. |
| |