Date |
Text |
2005-11-22 00:00:00 | DENIED: |
| 1.PLAN SHEET 1-0.0.0 PROJECT |
| INFORMATION INDICATES TYPE VI, |
| UNPROTECTETED SPRINKLERED.PLEASE |
| INDICATE FULL SPRINKLERED, 13R OR 13D |
| TYPE SYSTEM.PLEASE NOTE, ADDTIONAL |
| COMMENTS MAY BE GENERATED BY THE |
| RESPONSES GIVEN. |
| |
| 2.PLEASE CLARIFY DUCT PENETRATION |
| THROUGH THE SEPARATION WALL BETWEEN THE |
| GARAGE AND THE FIRST FLOOR OF THE |
| RESIDENCE.PLAN SHEET A-4.0.2 & |
| A-10.0.0, INDICATES THIS SEPARATION AS 1 |
| HR. PLAN M1 ONLY INDICATES A FIRE DAMPER |
| AT THE CEILING PENETRATION.DUCTS LESS |
| THAN 100 SQ INCHES SHALL COMPLY WITH |
| 2001 FMC 607.1.3 #3 ITEMS 1 THROUGH 4. |
| |
| 3.PLAN SHEET M2 DRYER EXHAUST EXCEEDS |
| 25 FT REQUIREMNET WITH REDUCTIONS FOR |
| 90'S PER 2001 FMC 504.6.PLAN SHEET |
| E2.2.4 INDICATES "BF" (BOOSTER FANS?). |
| PLEASE NOTE INSTALLATION OF BOOSTER FANS |
| WILL BE REVIEWED BY THE BUILDING OFFICAL |
| UNDER "ALTERNATE MATERIALS & METHODS" |
| 2001 FMC 103.7.1.PLEASE PROVIDE THE |
| FOLLOWING INFORMATION FOR REVIEW: 1) A |
| LETTER FROM AN ENGINEER EMPLOYED BY THE |
| DRYER MANUFACTURER STATING THE |
| INSTALLATION OF THE DRYER BOOSTER FAN IS |
| ACCEPTABLE AND WILL NOT VOID THE |
| WARRANTY OF THE DRYER. 2) MEANS OF |
| NOTIFYING THE OWNER SHOULD THE BOOSTER |
| FAN FAIL. 3) MANUFACTURER'S SUBMITTAL & |
| INSTALLATION DATA FOR THE BOOSTER FANS. |
| 4) PROVIDE ALL PERTINENT INFORMATION FOR |
| ALL TRADES MECHANICAL, ELECTRICAL, FIRE, |
| ETC. FOR THE INSTALLATION OF BOOSTER |
| FANS. |
| |
| 4.PLAN SHEET M2 THE O.A. INTAKE IS |
| WITHIN 10 FT OF THE TOILET & DRYER |
| EXHAUST TERMINATIONS.EXHAUST |
| CONTAMINANTES SHALL NOT BE RECIRCULATED |
| PER 2001 FMC 501.3. |
| |
| 5.PLEASE PROVIDE OUTSIDE AIR |
| CALCULATIONS IN ACCORDANCE WITH TABLE |
| 403.3. |
| |
| 6.PLEASE NOTE R/A TRANSFER GRILLES |
| LOCATED ON THE 3RD FLOOR ARE NOT SIZED |
| PROPERLY, SEE 2001 FMC 601.4 EXCEPTION 2 |
| & 3.TRANSFER SHALL BE A MINIMUM OF 50 |
| SQ INCHES PER 100 CFM OF SUPPLY AIR INTO |
| THAT AREA. |
| |
| 7.PLEASE PROVIDE DETAIL FOR THE AHU |
| LOCATED IN THE CLOSET.PLEASE NOTE, |
| MECHANICAL CLOSET SHALL BE CONSTRUCTED |
| PER 2001 FMC 603.9 & 610.1.ABC.3.7 OF |
| CHAPTER 13 OF THE 2001 FBC. |
| |
| 8.NO COMBUSTIBLES ALLOWED IN THE |
| MECHANICAL CLOSET PER 2001 FMC 602.2.1. |
| |
| 9.CONDENSATE DRAIN SHALL TERMINATE A |
| MINIMUM OF 12" FROM THE BUILDING |
| STUCTURE PER 2001 FBC 1503.4.4. |
| |
| 10. AUXILIARY DRAIN PAN WITH OVERFLOW |
| PROTECTION REQUIRED PER 2001 FMC |
| 307.2.3. |
| |