Plan Review Notes
Plan Review Notes For Permit 05090568
Permit Number 05090568
Review Stop M
Sequence Number 1
Notes
Date Text
2005-11-22 00:00:00DENIED:
 1.PLAN SHEET 1-0.0.0 PROJECT
 INFORMATION INDICATES TYPE VI,
 UNPROTECTETED SPRINKLERED.PLEASE
 INDICATE FULL SPRINKLERED, 13R OR 13D
 TYPE SYSTEM.PLEASE NOTE, ADDTIONAL
 COMMENTS MAY BE GENERATED BY THE
 RESPONSES GIVEN.
  
 2.PLEASE CLARIFY DUCT PENETRATION
 THROUGH THE SEPARATION WALL BETWEEN THE
 GARAGE AND THE FIRST FLOOR OF THE
 RESIDENCE.PLAN SHEET A-4.0.2 &
 A-10.0.0, INDICATES THIS SEPARATION AS 1
 HR. PLAN M1 ONLY INDICATES A FIRE DAMPER
 AT THE CEILING PENETRATION.DUCTS LESS
 THAN 100 SQ INCHES SHALL COMPLY WITH
 2001 FMC 607.1.3 #3 ITEMS 1 THROUGH 4.
  
 3.PLAN SHEET M2 DRYER EXHAUST EXCEEDS
 25 FT REQUIREMNET WITH REDUCTIONS FOR
 90'S PER 2001 FMC 504.6.PLAN SHEET
 E2.2.4 INDICATES "BF" (BOOSTER FANS?).
 PLEASE NOTE INSTALLATION OF BOOSTER FANS
 WILL BE REVIEWED BY THE BUILDING OFFICAL
 UNDER "ALTERNATE MATERIALS & METHODS"
 2001 FMC 103.7.1.PLEASE PROVIDE THE
 FOLLOWING INFORMATION FOR REVIEW: 1) A
 LETTER FROM AN ENGINEER EMPLOYED BY THE
 DRYER MANUFACTURER STATING THE
 INSTALLATION OF THE DRYER BOOSTER FAN IS
 ACCEPTABLE AND WILL NOT VOID THE
 WARRANTY OF THE DRYER. 2) MEANS OF
 NOTIFYING THE OWNER SHOULD THE BOOSTER
 FAN FAIL. 3) MANUFACTURER'S SUBMITTAL &
 INSTALLATION DATA FOR THE BOOSTER FANS.
 4) PROVIDE ALL PERTINENT INFORMATION FOR
 ALL TRADES MECHANICAL, ELECTRICAL, FIRE,
 ETC. FOR THE INSTALLATION OF BOOSTER
 FANS.
  
 4.PLAN SHEET M2 THE O.A. INTAKE IS
 WITHIN 10 FT OF THE TOILET & DRYER
 EXHAUST TERMINATIONS.EXHAUST
 CONTAMINANTES SHALL NOT BE RECIRCULATED
 PER 2001 FMC 501.3.
  
 5.PLEASE PROVIDE OUTSIDE AIR
 CALCULATIONS IN ACCORDANCE WITH TABLE
 403.3.
  
 6.PLEASE NOTE R/A TRANSFER GRILLES
 LOCATED ON THE 3RD FLOOR ARE NOT SIZED
 PROPERLY, SEE 2001 FMC 601.4 EXCEPTION 2
 & 3.TRANSFER SHALL BE A MINIMUM OF 50
 SQ INCHES PER 100 CFM OF SUPPLY AIR INTO
 THAT AREA.
  
 7.PLEASE PROVIDE DETAIL FOR THE AHU
 LOCATED IN THE CLOSET.PLEASE NOTE,
 MECHANICAL CLOSET SHALL BE CONSTRUCTED
 PER 2001 FMC 603.9 & 610.1.ABC.3.7 OF
 CHAPTER 13 OF THE 2001 FBC.
  
 8.NO COMBUSTIBLES ALLOWED IN THE
 MECHANICAL CLOSET PER 2001 FMC 602.2.1.
  
 9.CONDENSATE DRAIN SHALL TERMINATE A
 MINIMUM OF 12" FROM THE BUILDING
 STUCTURE PER 2001 FBC 1503.4.4.
  
 10. AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001 FMC
 307.2.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.