2006-04-09 00:00:00 | BUILDING PLAN REVIEW |
| *******DENIED******* |
| ROBERT BROWN(561) 805 6652 |
| E-MAIL: [email protected] |
| |
| REVISION TO REDUCE HEIGHT OF ENTRY |
| DOORS, AND SUBMITTAL FOR ALTERNATIVE |
| STORM PANEL SHUTTERS TO ADDRESS PROVISO. |
| |
| 1) ONLY ONE COPY OF REVISED SHEETS A-3.0 |
| AND A-4.1 WAS SUBMITTED.TWO SIGNED AND |
| SEALED COPIES OF EACH REVISED SHEET |
| SHOULD HAVE BEEN SUBMITTED, ONE COPY FOR |
| PERMIT FILE AND ONE FOR THE JOB SITE. |
| |
| 2) THE SUBMITTED SHEETS A-3.0 AND A-4.1 |
| ARE REVISIONS OF THE SHEETS REVIEWED FOR |
| PERMIT ISSUANCE.THEY WERE BROUGHT IN |
| AS SUBMITTALS, WHEN THEY ARE IN FACT |
| REVISIONS.A REVISION FEE OF $70 IS |
| DUE.THE FEE IS DERIVED FROM THE |
| STANDARD REVISION FEE OF $50 PLUS $10 |
| PER REVISED SHEET (IN THIS CASE, TWO |
| SHEETS).PLEASE PAY THE REQUIRED FEE |
| WHEN RESUBMITTING. |
| |
| 3) AS NOTED IN COMMENTS 1 AND 2, ABOVE, |
| THE PLANS HAVE BEEN REVISED TO REDUCE |
| THE STOREFRONT DOOR HEIGHT TO MATCH THE |
| SCOPE OF THE STOREFRONT DOOR PRODUCT |
| APPROVALS THAT WERE PREVIOUSLY |
| SUBMITTED.PRIOR TO THE PLAN REVISION, |
| THE STOREFRONT DOOR PRODUCT APPROVALS |
| COULD NOT BE STAMPED AS SUITABLE FOR THE |
| PROJECT, SO ALL COPIES WERE RETURNED TO |
| YOU, UNSTAMPED.NOW THAT THE PLANS HAVE |
| BEEN REVISED, TWO COPIES OF THE |
| STOREFRONT DOOR PRODUCT APPROVALS MUST |
| BE SUBMITTED FOR REVIEW.THE PRODUCT |
| APPROVALS THAT WERE PREVIOUSLY SUBMITTED |
| ARE ARCH ALUMINUM STOREFRONT DOOR |
| PRODUCT APPROVALSNOA# 01-0226.05 AND |
| 02-0904.02. |
| |
| 4) ONLY ONE COPY OF THE POMA CORPORATION |
| ALUMINUM STORM PANEL SHUTTER PRODUCT |
| APPROVAL NOA# 02-0417.06 WAS SUBMITTED. |
| TWO COPIES ARE REQUIRED.ALSO, THE |
| STATEWIDE PRODUCT APPROVAL COVER SHEET |
| WAS NOT SUBMITTED.I HAVE PRINTED THE |
| RELEVANT COVER SHEET AND ATTACHED IT TO |
| THE SUBMITTED PRODUCT APPROVAL SO THAT |
| TWO COMPLETE COPIES CAN BE RESUBMITTED, |
| ASSUMING COMMENT 5, BELOW, CAN BE |
| ADDRESSED WITHOUT HAVING TO SELECT A |
| DIFFERENT SHUTTER SUPPLIER. |
| |
| 5) ARCHITECTURAL PLAN SHEET A-4.1 AND |
| MODULAR BUILDING PLAN SHEET 7 OF 7, SHOW |
| DOOR AND WINDOW BUCKS OF 1"X 4" P.T. |
| WOOD, SCREWED TO THE METAL FRAME |
| STRUCTURE.SHEET A-4.1 SHOULD BE |
| REVISED TO SHOW HOW THE SHUTTERS WILL BE |
| ANCHORED, IN ACCORDANCE WITH THE PRODUCT |
| APPROVAL, TO THE STEEL FRAME STRUCTURE. |
| ALSO, THE SAME COMMENT ALSO APPLIES TO |
| ANCHORING OF THE STOREFRONT PER THE |
| SUBMITTED ARCH ALUMINUM PRODUCT |
| APPROVAL.PROVIDE THE REQUIRED |
| ADDITIONAL DETAILS. |
| |
| **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| |
| END OF REVIEW COMMENTS |