2006-02-23 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 805 6652
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 --PROVISO--
 FBC 1606.1SUBMIT ALTERNATIVE
 STOREFRONT DOOR PRODUCT APPROVALS OR
 REVISE THE PLANS.THE SUBMITTED ARCH
 ALUMINUM STOREFRONT DOOR PRODUCT
 APPROVALS REFERENCE MIAMI-DADE NOA#
 01-0226.05 AND 02-0904.02.BOTH
 DOCUMENTS SHOW A MAXIMUM DOOR FRAME
 HEIGHT OF 97" WHICH IS LESS THAN THE
 PROPOSED 120" (9'-2") DOOR FRAME SHOWN
 ON SHEET A-4.1 OF THE PLANS.THE 120"
 DOOR IS OUTSIDE OF THE SCOPE OF THE
 SUBMITTED PRODUCT APPROVALS.
  
 --PROVISO--
 FBC 1606.1.4SUBMIT AN ALTERNATIVE
 STORM PANEL SHUTTER PRODUCT APPROVAL.
 THE SUBMITTED EASTERN METAL SUPPLY
 SHUTTER PRODUCT APPROVAL REFERENCES
 MIAMI-DADE NOA# 03-0716.02 WHICH STATES
 THAT THE MAXIMUM ALLOWABLE STORM PANEL
 LENGTH IS 9'-0".THE PLANS SHOW
 STOREFRONT WINDOWS THAT EXCEED 9'-0",
 BOTH HORIZONTALLY AND VERTICALLY.THESE
 WINDOW SIZES ARE OUTSIDE THE SCOPE OF
 THE SUBMITTED PRODUCT APPROVAL
  
  