2006-02-23 00:00:00 | BUILDING PLAN REVIEW |
| ******PROVISO******* |
| ROBERT BROWN(561) 805 6652 |
| E-MAIL: [email protected] |
| |
| FBC = FLORIDA BUILDING CODE 2001 |
| FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| F.S.= FLORIDA (STATE) STATUTE |
| |
| --PROVISO-- |
| FBC 1606.1SUBMIT ALTERNATIVE |
| STOREFRONT DOOR PRODUCT APPROVALS OR |
| REVISE THE PLANS.THE SUBMITTED ARCH |
| ALUMINUM STOREFRONT DOOR PRODUCT |
| APPROVALS REFERENCE MIAMI-DADE NOA# |
| 01-0226.05 AND 02-0904.02.BOTH |
| DOCUMENTS SHOW A MAXIMUM DOOR FRAME |
| HEIGHT OF 97" WHICH IS LESS THAN THE |
| PROPOSED 120" (9'-2") DOOR FRAME SHOWN |
| ON SHEET A-4.1 OF THE PLANS.THE 120" |
| DOOR IS OUTSIDE OF THE SCOPE OF THE |
| SUBMITTED PRODUCT APPROVALS. |
| |
| --PROVISO-- |
| FBC 1606.1.4SUBMIT AN ALTERNATIVE |
| STORM PANEL SHUTTER PRODUCT APPROVAL. |
| THE SUBMITTED EASTERN METAL SUPPLY |
| SHUTTER PRODUCT APPROVAL REFERENCES |
| MIAMI-DADE NOA# 03-0716.02 WHICH STATES |
| THAT THE MAXIMUM ALLOWABLE STORM PANEL |
| LENGTH IS 9'-0".THE PLANS SHOW |
| STOREFRONT WINDOWS THAT EXCEED 9'-0", |
| BOTH HORIZONTALLY AND VERTICALLY.THESE |
| WINDOW SIZES ARE OUTSIDE THE SCOPE OF |
| THE SUBMITTED PRODUCT APPROVAL |
| |
| |