2006-02-01 00:00:00 | BUILDING PLAN REVIEW |
| *******DENIED******* |
| ROBERT BROWN(561) 805 6716 |
| E-MAIL: [email protected] |
| |
| FLORIDA BUILDING CODE 2001 |
| |
| FBC = FLORIDA BUILDING CODE 2001 |
| FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| F.S.= FLORIDA (STATE) STATUTE |
| |
| FOR CONSISTENCY, THE FOLLOWING COMMENTS |
| ARE NUMBERED AS PER THE BUILDING PLAN |
| REVIEW OF 12/19/05: |
| |
| 2) THIS COMMENT HAS NOT BEEN PROPERLY |
| ADDRESSED.THE COMMENT RESPONSE LETTER |
| STATES THAT NO REFERENCE TO 2004 FLORIDA |
| BUILDING CODE COULD BE FOUND.THAT IS |
| NOT CORRECT.PLEASE SEE THE BOTTOM LINE |
| OF TEXT ON FRED S. CARDWELL, P.E., P.L.S |
| FOUNDATION PLAN SHEET A-1 WHICH STATES |
| DESIGN IN ACCORDANCE WITH 2004 FLORIDA |
| BUILDING CODE.THAT NOTE DOES NOT |
| CORRELATE WITH STRUCTURAL SHEET S-0, |
| GENERAL NOTES, WHICH STATES DESIGN IN |
| ACCORDANCE WITH FLORIDA BUILDING CODE |
| 2001.THE PERMIT APPLICATION WAS |
| SUBMITTED DURING THE CODE OVERLAP PERIOD |
| 7/1/05 THROUGH 10/1/05 SO EITHER EDITION |
| COULD BE USED. HOWEVER BECAUSE THE |
| SUBMITTED DCA APPROVED MODULAR BUILDING |
| PLANS CITE 2001 FLORIDA BUILDING CODE, |
| IT HAS BEEN ASSUMED THAT IS THE DESIRED |
| CODE EDITION.THE PLANS MUST BE |
| CONSISTENT.AMEND THE FOUNDATION PLAN. |
| |
| 7) THIS COMMENT HAS NOT BEEN PROPERLY |
| ADDRESSED.THE 1/11/06 REVISION TO THE |
| COMMENT RESPONSE LETTER INCLUDES AN ARCH |
| ALUMINUM PRODUCT APPROVAL |
| NOA# 00-1220.05 BUT STILL STATES "DOORS |
| AND WINDOWS WILL BE SUBMITTED VIA |
| SEPARATE PERMIT...".ONLY ONE COPY OF |
| THE NOA WAS SUBMITTED.TO EXPEDITE |
| REVIEW, TWO COPIES OF THE REQUIRED |
| STATEWIDE PRODUCT APPROVAL COVER SHEET |
| (SEE BELOW) HAVE BEEN PROVIDED BY THIS |
| OFFICE.NO PRODUCT APPROVAL WAS |
| SUBMITTED FOR THE DOORS OR STORM |
| SHUTTERS.AS PART OF THIS PERMIT |
| APPLICATION, TWO COPIES OF PRODUCT |
| APPROVALS FOR THE STORM SHUTTERS AND |
| DOORS AND STOREFRONT MUST BE SUBMITTED. |
| NOTE: FL. ADMIN CODE RULE 9B-72 (IN |
| EFFECT SINCE OCTOBER 1, 2003) REQUIRES |
| THAT PRODUCTS HAVE STATEWIDE, LOCAL OR |
| SITE-SPECIFIC PRODUCT APPROVAL.THE |
| SUBMITTAL SHOULD INCLUDE THE STATEWIDE |
| PRODUCT APPROVAL NUMBER (FL###), |
| AVAILABLE FROM THE DEPT OF COMMUNITY |
| AFFAIRS PRODUCT APPROVAL WEBSITE |
| WWW.FLORIDABUILDING.ORG/PR/PR_SRCH.ASP |
| (IF YOU FIND THAT THE QUOTED WEB PAGE IS |
| NO LONGER AVAILABLE, PLEASE INFORM THE |
| PLAN REVIEWER) |
| |
| 14) 472.025(1) F.S.BOUNDARY SURVEY |
| SHEET S-1 IS NOT SIGNED AND SEALED BY |
| JON V. NOLTING. |
| |
| |
| **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| |
| END OF REVIEW COMMENTS |
| THE CODE REFERENCES GIVE ADDITIONAL INFO |
| TELEPHONE: (561) 805 6716ROBERT BROWN |
| E-MAIL: [email protected] |