Plan Review Notes
Plan Review Notes For Permit 05090560
Permit Number 05090560
Review Stop M
Sequence Number 1
Notes
Date Text
2005-11-10 00:00:00DENIED:2001 FBC
 1.PLEASE PROVIDE OUTSIDE AIR
 CALUCALTIONS IN ACCORDANCE WITH 2001
 FBC(M) TABLE 403.3.
  
 2.PLAN SHEET 4 OF 7 INDICATES ROOF
 CURB TO BE INSTALLED BY OTHERS, SUBJECT
 TO LOCAL CODES.PER 2001 FBC 1511.7
 ROOF CURBS SHALL BE A MINIMUM OF 8"
 ABOVE THE ROOF SURFACE.PLEASE PROVIDE
 ENGINEERED DETAIL FOR CURB ATTACHMENT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.