Plan Review Notes For Permit 05090560 |
Permit Number |
05090560 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-11-10 00:00:00 | DENIED:2001 FBC | | 1.PLEASE PROVIDE OUTSIDE AIR | | CALUCALTIONS IN ACCORDANCE WITH 2001 | | FBC(M) TABLE 403.3. | | | | 2.PLAN SHEET 4 OF 7 INDICATES ROOF | | CURB TO BE INSTALLED BY OTHERS, SUBJECT | | TO LOCAL CODES.PER 2001 FBC 1511.7 | | ROOF CURBS SHALL BE A MINIMUM OF 8" | | ABOVE THE ROOF SURFACE.PLEASE PROVIDE | | ENGINEERED DETAIL FOR CURB ATTACHMENT. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|