Plan Review Notes For Permit 05090560 |
Permit Number |
05090560 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-11-09 00:00:00 | ******DENIED****** | | | | 1) AN ADDRESS NUMBER IS REQUIRED ON THE | | BUILDING, AND SHALL BE A MINIMUM OF 6" | | IN HEIGHT AND CONTRASTING TO THE | | BACKGROUND. | | | | 2) PLEASE PROVIDE FLAME SPREAD/RETARDANT | | INFORMATION FOR THE CANVAS CANOPY. | | | | 3) IN ADDITION TO FAN SHUT DOWN, DUCT | | SMOKE DETECTORS ARE REQUIRED TO HAVE | | AUDIBLE/VISUAL DEVICES IN THE AREA OF | | THE DETECTOR. | | | | 4) 2A-10B,C, RATED FIRE EXTINGUISHERS | | ARE REQUIRED AND SHALL BE MOUNTED TO | | SATISFY THE 75' TRAVEL DISTANCE | | REQUIREMENT. | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | FIRE PLAN REVIEW (561) 805-6722 |
|