Plan Review Notes
Plan Review Notes For Permit 05090560
Permit Number 05090560
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2005-11-09 00:00:00******DENIED******
  
 1) AN ADDRESS NUMBER IS REQUIRED ON THE
 BUILDING, AND SHALL BE A MINIMUM OF 6"
 IN HEIGHT AND CONTRASTING TO THE
 BACKGROUND.
  
 2) PLEASE PROVIDE FLAME SPREAD/RETARDANT
 INFORMATION FOR THE CANVAS CANOPY.
  
 3) IN ADDITION TO FAN SHUT DOWN, DUCT
 SMOKE DETECTORS ARE REQUIRED TO HAVE
 AUDIBLE/VISUAL DEVICES IN THE AREA OF
 THE DETECTOR.
  
 4) 2A-10B,C, RATED FIRE EXTINGUISHERS
 ARE REQUIRED AND SHALL BE MOUNTED TO
 SATISFY THE 75' TRAVEL DISTANCE
 REQUIREMENT.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722