2005-09-29 00:00:00********** UNSAT ********
  
 1)NOTE: PLEASE SEE TITLE BLOCK ON STATE
 APPROVED TRIALERS IS MISSING REQUIRED
 CERTIFICATE OF AUTHORIZATION NUMBER AS
 REQUIRED UNDER FS 471.023, FAC
 61G15-23.002.
  
  
 2)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS
 AT 125% (3 OR MORE HRS).
 THIS IS SHOWN ON STATE PLANS.
 PLEASE ALSO CORRELATE LOADS AND LOAD
 CALCULATIONS SHOWN ON STATE PLANS AND
 PLANS SUBMITTED BY FES.
 215.3,230.42, 220 ETC.
  
 3)NOTE: PLEASE SUBMIT DETAIL FOR NEW
 FOUNTAIN, PUMP, LTS ETC. THIS SHOULD
 SHOW ALL GROUNDING, GFI PROTECTION FOR
 LTS, ANY SUBMERSIBLE PUMPS ETC.680.51
  
 4)NOTE: PLEASE SEE GROUNDING ELECTRODE
 SYSTEM RISER TO SHOW CWP AND NEW FOOTER
 STEEL.
 PLEASE ALSO SHOW GROUNDING DETAIL FOR
 TRAILERS.
 250.50
  
 5)NOTE: PLEASE PROVIDE COMPLETE SIGNED,
 SEALED, DATED WIND LOADING CALCULATIONS
 AT THIS TIME FOR LT POLES AND LTS
 FIXTURES ATTACHED.
 ALL TO MEET FBC 140 MPH FASTEST MILE.
 PLEASE SEE BLDG REVIEW COMMENTS FOR
 THIS.
  
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 ** PLEASE REMOVE ALL OLD/VOIDED SHEETS
 AND ONNLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 PLEASE SUBMIT ONE SET OF ALL OLD/VOIDED
 SHEETS WHEN RE-SUBMITTING PLANS WHICH
 WILL BE USED FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATIONFOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  