2005-09-29 00:00:00 | ********** UNSAT ******** |
| |
| 1)NOTE: PLEASE SEE TITLE BLOCK ON STATE |
| APPROVED TRIALERS IS MISSING REQUIRED |
| CERTIFICATE OF AUTHORIZATION NUMBER AS |
| REQUIRED UNDER FS 471.023, FAC |
| 61G15-23.002. |
| |
| |
| 2)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS |
| AT 125% (3 OR MORE HRS). |
| THIS IS SHOWN ON STATE PLANS. |
| PLEASE ALSO CORRELATE LOADS AND LOAD |
| CALCULATIONS SHOWN ON STATE PLANS AND |
| PLANS SUBMITTED BY FES. |
| 215.3,230.42, 220 ETC. |
| |
| 3)NOTE: PLEASE SUBMIT DETAIL FOR NEW |
| FOUNTAIN, PUMP, LTS ETC. THIS SHOULD |
| SHOW ALL GROUNDING, GFI PROTECTION FOR |
| LTS, ANY SUBMERSIBLE PUMPS ETC.680.51 |
| |
| 4)NOTE: PLEASE SEE GROUNDING ELECTRODE |
| SYSTEM RISER TO SHOW CWP AND NEW FOOTER |
| STEEL. |
| PLEASE ALSO SHOW GROUNDING DETAIL FOR |
| TRAILERS. |
| 250.50 |
| |
| 5)NOTE: PLEASE PROVIDE COMPLETE SIGNED, |
| SEALED, DATED WIND LOADING CALCULATIONS |
| AT THIS TIME FOR LT POLES AND LTS |
| FIXTURES ATTACHED. |
| ALL TO MEET FBC 140 MPH FASTEST MILE. |
| PLEASE SEE BLDG REVIEW COMMENTS FOR |
| THIS. |
| |
| |
| ** PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| OTHER TRADES WHICH MAY AFFECT ELECTRICAL |
| PLANS. |
| |
| ** PLEASE REMOVE ALL OLD/VOIDED SHEETS |
| AND ONNLY INSERT NEW REVISED SHEETS INTO |
| COMPLETE SETS FOR REVIEW AND STAMPING. |
| PLEASE SUBMIT ONE SET OF ALL OLD/VOIDED |
| SHEETS WHEN RE-SUBMITTING PLANS WHICH |
| WILL BE USED FOR REFERENCE. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATIONFOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE IN CONTACTING |
| THIS OFFICE. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-805-6717 |
| [email protected] |