Plan Review Notes
Plan Review Notes For Permit 05090560
Permit Number 05090560
Review Stop B
Sequence Number 1
Notes
Date Text
2005-12-16 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FLORIDA BUILDING CODE 2001
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 1) 61G15-23.002(2)FL. ADMIN. CODE.
 ONLY ONE SET OF THE STRUCTURAL PLANS ARE
 SIGNED AND SEALED.ALSO, THE PRINTED
 NAME AND LICENSE NUMBER OF DAOUD
 ISKANDAR, P.E. MUST BE ADDED TO EACH
 SHEET (MAY BE ADDED BY HAND).
 PLANS SIGNED & SEALED BY A PROFESSIONAL
 ENGINEER SHALL INCLUDE EITHER THE NAME,
 ADDRESS AND LICENSE NUMBER OF THE
 ENGINEER OR, THE NAME AND LICENSE NUMBER
 OF THE ENGINEER AND THE NAME, ADDRESS
 AND CERTIFICATE OF AUTHORIZATION NUMBER
 OF THE ENGINEERING BUSINESS THROUGH
 WHICH THE ENGINEER IS PRACTICING
 (471.025 F.S. AND 471.023 F.S.).
  
 2) THE SUBMITTED FOUNDATION PLAN SHEET
 A-1 STATES DESIGN IN ACCORDANCE WITH
 2004 FLORIDA BUILDING CODE WHILE
 STRUCTURAL SHEET S-0, GENERAL NOTES,
 STATES DESIGN IN ACCORDANCE WITH FLORIDA
 BUILDING CODE 2001.THE PERMIT
 APPLICATION WAS SUBMITTED DURING THE
 CODE OVERLAP PERIOD 7/1/05 THROUGH
 10/1/05 SO EITHER EDITION COULD BE USED.
 HOWEVER BECAUSE THE SUBMITTED DCA
 APPROVED MODULAR BUILDING PLANS CITE
 FLORIDA BUILDING CODE, IT HAS BEEN
 ASSUMED THAT IS THE DESIRED CODE
 EDITION.THE PLANS MUST BE CONSISTENT.
 AMEND THE FOUNDATION PLAN.
  
 3) FBC 11-4.1.3(8)(A)(II)THE NUMBER OF
 ACCESSIBLE ENTRANCES MUST BE AT LEAST
 EQUAL TO THE NUMBER OF REQUIRED EXITS.
 TWO EXITS ARE REQUIRED, SO AT LEAST TWO
 ACCESSIBLE ENTRANCES ARE REQUIRED.
 PROVIDE A RAMP OR SLOPED (LESS THAN 1 IN
 20) PATH FROM THE FOUNTAIN AREA TO THE
 WEST PATIO TO MAKE THE WEST ENTRANCE
 ACCESSIBLE.
  
 4) FBC 1-4.8.1SHEET C-5 SHOWS A PATH
 FROM EACH ACCESSIBLE PARKING SPACE THAT
 SLOPES UP FROM 20.90' TO 21.90' IN A
 DISTANCE THAT IS TOO SHORT TO ACHIEVE
 THE STATED MAX. 1 IN 20 SLOPE.AMEND
 THE LEVELS OR PROVIDE DETAILS FOR A RAMP
 INCLUDING HANDRAILS AND EDGE PROTECTION.
  
 5) FBC 1007.5.7SHEET A-3.0EAST AND
 WEST ENTRANCE.THE STAIR HANDRAILS DO
 NOT ALIGN WITH THE DOORS.HANDRAILS
 SHALL BE LOCATED ALONG THE NATURAL PATH
 OF EGRESS TRAVEL.AMEND THE PLANS SO
 THAT THE HANDRALS ARE CENTERED ON THE
 EXIT DOOR LOCATION.
  
 6) FBC* 104.2.1.2SHEET A-3.0THE
 PLANS DO NOT SHOW, OR MAKE REFERENCE TO,
 A SOUTH ELEVATION.
  
 7) SUBMIT PRODUCT APPROVALS FOR THE
 DOORS AND STOREFRONT.
 NOTE: FL. ADMIN CODE RULE 9B-72 (IN
 EFFECT SINCE OCTOBER 1, 2003) REQUIRES
 THAT PRODUCTS HAVE STATEWIDE, LOCAL OR
 SITE-SPECIFIC PRODUCT APPROVAL.THE
 SUBMITTAL SHOULD INCLUDE THE STATEWIDE
 PRODUCT APPROVAL NUMBER (FL###),
 AVAILABLE FROM THE DEPT OF COMMUNITY
 AFFAIRS PRODUCT APPROVAL WEBSITE
 WWW.FLORIDABUILDING.ORG/PR/PR_SRCH.ASP
 (IF YOU FIND THAT THE QUOTED WEB PAGE IS
 NO LONGER AVAILABLE, PLEASE INFORM THE
 PLAN REVIEWER)
  
 8) FBC 1606.1CANOPIES.A SEPARATE
 PERMIT APPLICATION IS REQUIRED FOR THE
 CANVAS CANOPIES.THEY ARE TO BE
 DESIGNED FOR A WIND SPEED OF 140 MPH, 3
 SECOND GUST IN EXPOSURE CATEGORY B.
  
 9) FBC 1606.1.7SHEET E-1 SHOWS LIGHT
 POLES.SUBMIT WIND LOAD AND FOUNDATION
 CALCULATIONS/DETALS FOR THE LIGHT POLES.
  
 10) FBC 104.2.1.2SHEET S-0 AND S-3
 SHOW A "WORK AREA E".WHAT STRUCTURE IS
 THIS.
  
 11) FBC 11-4.1.3(10)(A)DRINKING
 FOUNTAIN.A DRINKING FOUNTAIN IS
 REQUIRED.IT SHALL MEET THE CLEARANCE
 REQUIREMENTS OF FBC 11-4.14 AND FIG. 27
  
 12) FBC 11-4.24BREAK ROOM SINK.THE
 BREAK ROOM SINK SHALL HAVE THE REQUIRED
 CLEARANCES (FIG. 32)
  
 13) FBC 1511.7MECHANICAL EQUIPMENT.
 THE ROOF MOUNTED MECHANICAL EQUIPMENT
 SHALL BE MOUNTED ON CURBS RAISED A
 MINIMUM OF 8 INCHES ABOVE THE ROOF
 SURFACE.WHERE THE ROOFING MATERIALS
 EXTEND BENEATH THE MECHANICAL EQUIPMENT
 THE SUPPORTS SHALL PROVIDE THE MINIMUM
 CLEARANCE GIVEN IN TABLE 1511.7.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]
  