Plan Review Notes
Plan Review Notes For Permit 05090553
Permit Number 05090553
Review Stop B
Sequence Number 1
Notes
Date Text
2005-10-17 00:00:00BUILDING REVIEW CHECKLIST:
 1- CONTRACTOR'S LICENSE IS FOR ALUMINUM
 SPECIALTIES. WINDOW INSTALLTION IS OUT
 OF THE SCOPE OF WORK FOR THIS LICENSE.
 NEED CONTRACTOR WITH GLASS AND GLAZING
 LICENSE TO APPLY FOR THIS PERMIT.
  
 2- BEDROOM WINDOWS NEED TO COMPLY WITH
 MIN. SIZE AS REQUIRED BYSEC. 1005.4.4
 FBC 2001. MIN. SIZE IS 24" CLEAR OPENING
 HEIGHT, 20" CLEAR OPENING WIDTH AND
 5.7S.F. MIN. CLEAR OPENING. CLEARLY
 IDENTIFY ON KEY PLAN BEDROOM WINDOWS AND
 REVISE WINDOW SIZE AS REQUIRED TO COMPLY
 WITH CITED SEC. ABOVE.
  
 3- DADE COUNTY NOA SUBMITTED IS NOT THE
 SAME THAT WAS SUBMITTED FOR FLORIDA
 PRODUCT APPROVAL. NEED NOA #03-0514.01
 AND MAKE SURE THAT COPIES ARE LEGIBLE.
  
 4- PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR:
 A) WINDOW MULLIONS.
 B) IMPACT WINDOWS WITH FROSTED GLASS AS
 SPECIFIED FOR BATHROOMS.
  
 5- DESIGN PRESSURES CHART IS NOT
 LEGIBLE. NEED A CLEAR ONE.
  
 6- NEED RECORDED NOTICE OF COMMENCEMENT.
  
 7- THERE ARE 2 BUILDINGS IN THIS
 PROPERTY. SPECIFY WHICH BUILDING IS THE
 ONE HAVING THE WINDOWS REPLACED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712.