Plan Review Notes
Plan Review Notes For Permit 05090538
Permit Number 05090538
Review Stop B
Sequence Number 1
Notes
Date Text
2005-10-12 00:00:001) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE CITY OF WPB DOES NOT USE THE
 SOUTH FLORIDA BUILDING CODE BOOK. THE
 CODE BOOK WE USE IS THE FLORIDA BUILDING
 CODE 2001. HOWEVER, AS OF OCTOBER 1ST WE
 WILL BE USING THE 2004 FLORIDA BUILDING
 CODE BOOK.
  
 3) IF THIS STRUCTURE IS DESIGN UNDER THE
 2001 CODE, IT WILL HAVE TO BE DESIGNED
 TO WITH-STAND 140MPH WITH THE CANVAS
 AWNING IN PLACE.SEE FBC 2001 SEC.
 1606.1.6 AND 1606.1.7 FOR BASIC WIND
 SPEEDS.
  
 4) IF THIS STRUCTURE IS DESIGNED FOR THE
 CANVAS TO BE REMOVED AT 75MPH WIND
 SPEED. IT WILL HAVE TO BE DESIGN USING
 THE 2004 CODE.SEC 3105. ALSO A NOTORIZE
 LETTER FROM THE OWNER STATING THAT THE
 CANVAS WILL BE REMOVED AT WIND SPEEDS OF
 75MPH SHALL BE SUBMITTED FOR REVIEW.
  
 5) WHAT IS THE HEIGHT OF THE STRUCTURE?
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]