2005-09-15 00:00:00 | BUILDING PLAN REVIEW | | PERMIT:05090376 | | ADD:3701 S. FLAGLER #B204 | | CONT:NICK RAICH BLDG. CORP. | | TEL: (561)659-9347 | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | * WEST PALM BEACH AMENDMENTS | | | | REVIEW | | ACTION: BUILDING PROVISO | | | | 803.4 FOAM PLASTICS. FOAM PLASTICS SHALL | | NOT BE USED AS INTERIOR FINISH. | | | | EXCEPTION: FOAM PLASTIC TRIM, DEFINED | | AS PICTURE MOLDS, CHAIR RAILS, | | BASEBOARDS, HANDRAILS, CEILING BEAMS, | | DOOR TRIM AND WINDOW TRIM SHALL BE | | PERMITTED TO BE USED PROVIDED: | | | | 1. THE MINIMUM DENSITY IS 20 LB/CU FT | | (320 KG/M^3). | | | | 2. THE MAXIMUM THICKNESS OF THE TRIM | | IS 1/2 INCH (12.7 MM) AND THE | | MAXIMUM WIDTH IS 4 INCHES (102 MM). | | | | 3. THE TRIM CONSTITUTES NO MORE THAN | | 10 PERCENT OF THE AREA OF ANY WALL | | OR CEILING. | | | | 4. THE FLAMESPREAD RATING DOES NOT | | EXCEED 75 WHEN TESTED PER ASTM E 84. | | THE SMOKE DEVELOPED RATING IS NOT | | LIMITED. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | |
|