2005-10-07 00:00:00 | BUILDING REVIEW CHECKLIST: |
| 1- RECORDED NOTICE OF COMMENCEMENT IS |
| MISSING REQUIRED INFORMATION: |
| LEGAL DESCRIPTION OF PROPERTY, STREET |
| ADDRESS AND THE TAX FOLIO NUMBER. NEED |
| TO COMPLETE INFORMATION AND RE-RECORD |
| NOTICE OF COMMENCEMENT. |
| |
| 2- PROVIDE ENGINEERED DESIGN PRESSURES |
| FOR WINDOWS AND DOORS OPENINGS AS REQ'D |
| BY SEC. 1606.1 FBC 2001 AND SEC. |
| 104.2.1.2 OF CITY AMENDMENTS TO FBC |
| 2001. ALSO, CLEARLY INDICATE IF |
| WINDOW/DOOR IS LOCATED AT THE END OR |
| INTERIOR ZONE. PROVIDE KEY PLAN. SEC. |
| 1606.1 FBC 2001. |
| |
| 3- TO VERIFY THAT DOORS AND WINDOWS |
| COMPLY WITH THE DESIGN PRESSURES |
| CALCULATED BY THE ENGINEER NEED TO |
| PROVIDE: |
| A) DOORS AND WINDOWS SIZES. |
| B) MARK ON DRAWINGS SPECIFIC WINDOWS AND |
| DOORS TO BE USED. INCLUDING GLAZING TYPE |
| TO BE USED AND REINFORCING IF REQUIRED. |
| SEC. 104.2.1.2 CITY AMENDMENTS FBC 2001. |
| |
| 4- IF USING 2X STRUCTURAL BUCKS FOR |
| DOORS AND WINDOWS, THEN THEY NEED TO BE |
| DESIGN TO RESIST THE LOADS. PROVIDE |
| DETAIL/SPECS FOR STRUCTURALBUCK SIZE |
| AND ANCHORING FOR DOORS AND WINDOWS.SEC. |
| 1707.4.4.2 FBC 2001, SEC. 104.2.1.2 CITY |
| AMENDMENTS TO FBC 2001 AND AS REQUIRED |
| ON PRODUCT APPROVALS. |
| SEE NOTE: "BUCKS BY OTHERS" ON PRODUCT |
| APPROVALS. |
| |