2005-10-07 00:00:00BUILDING REVIEW CHECKLIST:
 1- RECORDED NOTICE OF COMMENCEMENT IS
 MISSING REQUIRED INFORMATION:
 LEGAL DESCRIPTION OF PROPERTY, STREET
 ADDRESS AND THE TAX FOLIO NUMBER. NEED
 TO COMPLETE INFORMATION AND RE-RECORD
 NOTICE OF COMMENCEMENT.
  
 2- PROVIDE ENGINEERED DESIGN PRESSURES
 FOR WINDOWS AND DOORS OPENINGS AS REQ'D
 BY SEC. 1606.1 FBC 2001 AND SEC.
 104.2.1.2 OF CITY AMENDMENTS TO FBC
 2001. ALSO, CLEARLY INDICATE IF
 WINDOW/DOOR IS LOCATED AT THE END OR
 INTERIOR ZONE. PROVIDE KEY PLAN. SEC.
 1606.1 FBC 2001.
  
 3- TO VERIFY THAT DOORS AND WINDOWS
 COMPLY WITH THE DESIGN PRESSURES
 CALCULATED BY THE ENGINEER NEED TO
 PROVIDE:
 A) DOORS AND WINDOWS SIZES.
 B) MARK ON DRAWINGS SPECIFIC WINDOWS AND
 DOORS TO BE USED. INCLUDING GLAZING TYPE
 TO BE USED AND REINFORCING IF REQUIRED.
 SEC. 104.2.1.2 CITY AMENDMENTS FBC 2001.
  
 4- IF USING 2X STRUCTURAL BUCKS FOR
 DOORS AND WINDOWS, THEN THEY NEED TO BE
 DESIGN TO RESIST THE LOADS. PROVIDE
 DETAIL/SPECS FOR STRUCTURALBUCK SIZE
 AND ANCHORING FOR DOORS AND WINDOWS.SEC.
 1707.4.4.2 FBC 2001, SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001 AND AS REQUIRED
 ON PRODUCT APPROVALS.
 SEE NOTE: "BUCKS BY OTHERS" ON PRODUCT
 APPROVALS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712