Notes
Date Text
2006-07-20 00:00:00PAUL SCHMITZ
 [email protected]
 FBC2001 FUEL GAS CODEPLAN REVIEW
 FBC 2001 PLUMBING CODEPLAN REVIEW FBC
 2001 FL ACESSIBILITY CODE PLANREVIEW
 DENIED "THIRD TIME"
  
 PREVIOUS NOTE #2 NOT ADDRESSED.
  
 104.2 DRAWINGS AND SPECIFICATIONS.
 104.2.1 REQUIREMENTS. AS REQUIRED BY
 104.3.1.1 OF THE CODE, TWO OR MORE
 COPIES OF
 SPECIFICATIONS, AND OF DRAWINGS DRAWN TO
 SCALE WITH SUFFICIENT CLARITY AND DETAIL
 TO INDICATE THE
 NATURE AND CHARACTER OF THE WORK, SHALL
 ACCOMPANY THE APPLICATION FOR A PERMIT.
 SUCH
 DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF
 NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY
 IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES.
 SUCH INFORMATION SHALL BE SPECIFIC, AND
 THE TECHNICAL CODES SHALL NOT BE CITED
 AS A WHOLE OR IN
 PART, NOR SHALL THE TERM ?LEGAL? OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR
 SPECIFIC INFORMATION.
 ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR
 THE DESIGN.
  
 2)SHT A-1 BREAK ROOM SINKS:
 11-4.24 SINKS.
 ?11-4.24.1 GENERAL. SINKS REQUIRED TO
 BE ACCESSIBLE BY ?11-4.1 SHALL
 COMPLY WITH ?11-4.24.
 ?11-4.24.2 HEIGHT. SINKS SHALL BE
 MOUNTED WITH THE COUNTER OR RIM NO
 HIGHER THAN 34 IN. (865 MM) ABOVE THE
 FINISH FLOOR.
 ?11-4.24.3 KNEE CLEARANCE. KNEE
 CLEARANCE THAT IS AT LEAST 27 IN. (685
 MM) HIGH, 30 IN. (760 MM) WIDE, AND 19
 IN (485 MM) DEEP SHALL BE
 PROVIDED UNDERNEATH SINKS.
 ?11-4.24.4 DEPTH. EACH SINK SHALL BE A
 MAXIMUM OF 6-1/2 IN (165 MM) DEEP.
 ?11-4.24.5 CLEAR FLOOR SPACE. A CLEAR
 FLOOR SPACE AT LEAST 30 IN. BY 48
 IN. (760 MM BY 1220 MM) COMPLYING WITH
 11-4.2.4 SHALL BE PROVIDED IN
 FRONT OF A SINK TO ALLOW FORWARD
 APPROACH.THE CLEAR FLOOR SPACE SHALL
 BE ON AN ACCESSIBLE ROUTE AND SHALL
 EXTEND A MAXIMUM OF 19 IN. (485 MM)
 UNDERNEATH THE SINK (SEE FIGURE 11-32)
 ?11-4.24.6 EXPOSED PIPES AND SURFACES.
 HOT WATER AND DRAIN PIPES EXPOSED
 UNDER SINKS SHALL BE INSULATED OR
 OTHERWISE CONFIGURED SO AS TO PROTECT
 AGAINST CONTACT.THERE SHALL BE NO
 SHARP OR ABRASIVE SURFACES UNDER SINKS.
 ?11-4.24.7 FAUCETS. FAUCETS SHALL
 COMPLY WITH ?11-4.27.4.LEVER-
 OPERATED, PUSH-TYPE, TOUCH-TYPE, OR
 ELECTRONICALLY CONTROLLED MECHANISMS
 ARE ACCEPTABLE DESIGNS.
  
 END OF COMMENTS, QUESTIONS 561-805-6692