Plan Review Notes
Plan Review Notes For Permit 05090351
Permit Number 05090351
Review Stop M
Sequence Number 1
Notes
Date Text
2005-10-18 00:00:00DENIED:
 1.PLAN SHEET M-1, OUTSIDE AIR SCHEDULE
 INDICATES 2 AHU-2 ON AHU-3 IS NOT LISTED
 PLEASE CLARIFY & CORRECT.
  
 2.PLAN SHEET P-1 INDICATES THE
 AUXILIARY DRAIN LINE FROM THE PAN
 TERMINATING OVER THE ENTRANCE DOOR.
 PLEASE NOTE, PER 2001 FBC 307.2.1,
 CONDENSATE SHALL NOT DISCHARGE INTO A
 STREET ALLEY OR OTHER AREAS SO AS NOT TO
 CREATE A NUISANCE.THIS MAY CAUSE A
 SLIP AND FALL TERMINATING INTO THE
 ENTRANCE WAY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.