Plan Review Notes For Permit 05090351 |
Permit Number |
05090351 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-09-29 00:00:00 | ******DENIED****** | | | | 1) PLEASE SEE STAIR DETAIL ON SHT S-2. | | IS TREAD DEPTH IN COMPLIANCE WITH NFPA | | 101, SECTION 7.2.2.2.1 (A)? | | | | 2) IN ACCORDANCE WITH LOCAL | | REQUIREMENTS, DUCT SMOKE DETECTORS WHERE | | PROVIDED SHALL BE WIRED TO THE FIRE | | ALARM PANEL TO CAUSE A GENERAL FIRE | | ALARM CONDITION WHEN ACTIVATED. | | | | 3) PLEASE SHOW LOCATIONS OF NEW OR | | EXISTING 2A-10B,C RATED FIRE | | EXTINGUISHERS. | | | | 4) SEPARATE SHOP DRAWINGS AND PERMITS | | ARE REQUIRED FOR FIRE SPRINKLER AND FIRE | | ALARM REMODEL. | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | FIRE PLAN REVIEW (561) 805-6722 |
|