2005-11-05 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION.561-233-5025
  
 3.)ADDITIONAL FEES WILL BE DUE
 (RADON).
  
 4.)PROVIDE AREA CALCULATIONS FOR THE
 PROPOSED MEZZANINE.
  
 5.)DECLARE AN OCCUPANT LOAD FOR THE
 MEZZANINE.
  
 6.)SHOW TRAVEL DISTANCE TO THE EXIT
 FROM THE MEZZANINE.NO DIMENSIONS SHOWN
 ON THE PLAN.FBC1005.7, 1004.1.5.
  
 7.)PROVIDE FIRE SPRINKLER PLAN,
 FBC104.3.1.1.
  
 8.)SEE FBC1005.7.3.THERE IS ENCLOSED
 SPACE UNDER THE MEZZANINE.PLEASE
 ADDRESS.
  
 9.)THE STAIRS ARE TO COMPLY WITH
 FBC1007.1.4.
  
 10.) STAIR TREADS TO COMPLY WITH
 FBC1007.3, MINIMUM OF 11 INCHES.
  
 11.)PROVIDE A STRUCTURAL DETAIL FOR
 THE STAIRS, INCLUDING FIREBLOCKING.
  
 12.)SHOW THE DISTANCE BETWEEN THE TWO
 DOORS, FROM THE FRONT ENTRY TO DOOR 2.
 SEE FBC 11 FIGURE 25.
  
 13.)THE STAIR HANDRAIL IS TO COMPLY
 WITH FBC11-4.9.4.SEE ALSO FIGURE 19.
  
 14.)FIREBLOCKING REQUIRED, 8-A2,
 FBC705.3.1.1.
  