2006-03-01 00:00:00BUILDING REVIEW SECOND CHECKLIST:
 1- AS OF JANUARY 1ST 2006 ENGINEER NEEDS
 TO USE NEW SEAL AS REQUIRED BY RULE
 61G15-23.001 OF F.A.C.
 SEE ATTACHED COPY.
  
 2- PROVIDE A COMPLETE INSTALLATION
 SCHEDULE THAT PROVIDES ALL INFORMATION
 REQUIRED TO REVIEW COMPLIANCE WITH THE
 CALCULATED DESIGN PRESSURES AND WITH THE
 LIMITATIONS OF THE FLORIDA PRODUCT
 APPROVAL SUBMITTED.
 MIN. INFORMATION REQUIRED: OPENING SIZE,
 PROPOSED INSTALLATION OF ARMOR SCREEN
 (EG: STRAIGHT, STORM BAR, ANGLE, ETC),
 SPAN, DEFLECTION, ANCHOR TYPE AND
 SPACING, ETC.
 SECTION 104.2.1.2OF CITY AMENDMENTS TO
 FBC 2001.
  
 3- ADDITIONAL DRAWING SUBMITTED FOR
 TYPICAL FLUSH MOUNT APPLICATION IS NOT
 PART OF THE DADE COUNTY NOA SUBMITTED,
 THEREFORE, IT CAN'T BE USED. SEE
 MOUNTING CONDITIONS ON DADE COUNTY NOA
 DRAWINGS.
  
 4- NEED EMERGENCY EGRESS AS REQUIRED BY
 SEC. 1005.4.5 FBC 2001. SPECIFY HOW IS
 THIS ACCOMPLISHED. NEED AT LEAST ONE
 MEANS OF ESCAPE. HAND WRITTEN NOTE ON
 KEY PLAN SAYING THAT SCREEN TO BE CUT OR
 REMOVED IS NOT ACCEPTABLE TO COMPLY WITH
 SEC. 1005.4.5 FBC 2001.
  
 5- NOTICE OF COMMENCEMENT IS EXPIRED
 AFTER 90 DAYS OF RECORDING IT IF WORK IS
 NOT STARTED. NEED RE-RECORDED NOC.
  