2006-03-01 00:00:00 | BUILDING REVIEW SECOND CHECKLIST: |
| 1- AS OF JANUARY 1ST 2006 ENGINEER NEEDS |
| TO USE NEW SEAL AS REQUIRED BY RULE |
| 61G15-23.001 OF F.A.C. |
| SEE ATTACHED COPY. |
| |
| 2- PROVIDE A COMPLETE INSTALLATION |
| SCHEDULE THAT PROVIDES ALL INFORMATION |
| REQUIRED TO REVIEW COMPLIANCE WITH THE |
| CALCULATED DESIGN PRESSURES AND WITH THE |
| LIMITATIONS OF THE FLORIDA PRODUCT |
| APPROVAL SUBMITTED. |
| MIN. INFORMATION REQUIRED: OPENING SIZE, |
| PROPOSED INSTALLATION OF ARMOR SCREEN |
| (EG: STRAIGHT, STORM BAR, ANGLE, ETC), |
| SPAN, DEFLECTION, ANCHOR TYPE AND |
| SPACING, ETC. |
| SECTION 104.2.1.2OF CITY AMENDMENTS TO |
| FBC 2001. |
| |
| 3- ADDITIONAL DRAWING SUBMITTED FOR |
| TYPICAL FLUSH MOUNT APPLICATION IS NOT |
| PART OF THE DADE COUNTY NOA SUBMITTED, |
| THEREFORE, IT CAN'T BE USED. SEE |
| MOUNTING CONDITIONS ON DADE COUNTY NOA |
| DRAWINGS. |
| |
| 4- NEED EMERGENCY EGRESS AS REQUIRED BY |
| SEC. 1005.4.5 FBC 2001. SPECIFY HOW IS |
| THIS ACCOMPLISHED. NEED AT LEAST ONE |
| MEANS OF ESCAPE. HAND WRITTEN NOTE ON |
| KEY PLAN SAYING THAT SCREEN TO BE CUT OR |
| REMOVED IS NOT ACCEPTABLE TO COMPLY WITH |
| SEC. 1005.4.5 FBC 2001. |
| |
| 5- NOTICE OF COMMENCEMENT IS EXPIRED |
| AFTER 90 DAYS OF RECORDING IT IF WORK IS |
| NOT STARTED. NEED RE-RECORDED NOC. |
| |
| JULIO GOMEZ |
| BUILDING PLANS EXAMINER |
| (561)805-6712 |