Plan Review Notes
Plan Review Notes For Permit 05090323
Permit Number 05090323
Review Stop B
Sequence Number 1
Notes
Date Text
2005-10-07 00:00:00BUILDING REVIEW CHECKLIST:
 1- DESIGN PRESSURES CHART:PROVIDE
 ENGINEERED CALCULATIONS SIGNED AND
 SEALED BY THE ENGINEER WHO CALCULATED
 THE DESIGN PRESSURES USING ASCE 7-98.
 CLEARLY SPECIFY THE DESIGN PRESSURES FOR
 EACH OPENING. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
  
 2- PROVIDE A COMPLETE INSTALLATION
 SCHEDULE THAT PROVIDE ALL INFORMATION
 REQUIRED TO REVIEW COMPLIANCE WITH THE
 DESIGN PRESSURES CALCULATED IN ABOVE
 ITEM. SEE ATTACHED COPY OF INSTALLATION
 SCHEDULE SAMPLE. FILL INFORMATION THAT
 APPLIES TO THIS PRODUCT AND EXPAND CHART
 TO INCLUDE INFORMATION REQUIRED TO
 DESCRIBE THIS PRODUCT. SPECIFY ALL
 FASTENERS TO BE USED. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
  
 3- PROVIDE FLORIDA PRODUCT APPROVAL OR
 APPLY FOR LOCAL PRODUCT APPROVAL FOR
 THIS PRODUCT AS REQUIRED BY RULE 9B-72
 OF DCA. SEE WWW.FLORIDABUILDING.ORG.
 DADE COUNTY NOA ALONE IS NOT
 AUTOMATICALLY AN STATE WIDE FLORIDA
 PRODUCT APPROVAL. MANUFACTURER, MAY
 APPLY FOR LOCAL PRODUCT APPROVAL USING
 THE DADE COUNTY NOA AND COMPLETING THE
 LOCAL PRODUCT APPROVAL FORM DOWNLOADED
 FROM WWW.FLORIDABUILDING.ORG.
  
 4- CLEARLY MARK ON DRAWINGS SPECIFIC
 SCREEN MOUNTING CONDITIONS AND ANCHORS
 TO BE USED INCLUDING CHART ON PAGE 2 OF
 8 TO VERIFY COMPLIANCE. SEC. 104.2.1.2.
  
 5- NEED EMERGENCY EGRESS AS REQUIRED BY
 SEC. 1005.4.5 FBC 2001. SPECIFY HOW IS
 THIS EMERGENCY EGRESS ACCOMPLISHED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved