2005-10-07 00:00:00BUILDING REVIEW CHECKLIST:
 1- DESIGN PRESSURES CHART: PROVIDE
 ENGINEERED CALCULATIONS SIGNED AND
 SEALED BY THE ENGINEER WHO CALCULATED
 THE DESIGN PRESSURES USING ASCE 7-98.
 CLEARLY SPECIFY THE DESIGN PRESSURES FOR
 EACH OPENING. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
  
 2- PROVIDE A COMPLETE INSTALLATION
 SCHEDULE THAT PROVIDES ALL INFORMATION
 REQUIRED TO REVIEW COMPLIANCE WITH THE
 DESIGN PRESSURES. SEE ATTACHED SAMPLE
 COPY AND FILL IN INFORMATION THAT
 APPLIES TO THIS PRODUCT. EXPAND CHART TO
 INCLUDE INFORMATION REQUIRED TO DESCRIBE
 APPLICATION OF THIS PRODUCT. SPECIFY ALL
 FASTENERS TO BE USED. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
  
 3- PROVIDE FLORIDA PRODUCT APPROVAL OR
 APPLY FOR LOCAL PRODUCT APPROVAL FOR
 THIS PRODUCT AS REQUIRED BY RULE 9B-72
 OF DCA. SEE WWW.FLORIDABUILDING.ORG.
 DADE COUNTY NOA ALONE IS NOT
 AUTOMATICALLY AN STATE WIDE FLORIDA
 APPROVAL. MANUFACTURER, MAY APPLY FOR
 LOCAL PRODUCT APPROVAL USING THE DADE
 COUNTY NOA AND COMPLETING THE LOCAL
 PRODUCT APPROVAL FORM DOWNLOADED FROM
 WWW.FLORIDABUILDING.ORG.
  
 4- CLEARLY MARK ON DRAWINGS SPECIFIC
 SCREEN MOUNTING CONDITIONS AND ANCHORS
 TO BE USED INCLUDING THOSE IN SHEET 2 OF
 8 TO VERIFY COMPLIANCE. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
  
 5- NEED EMERGENCY EGRESS AS REQUIRED BY
 SEC. 1005.4.5 FBC 2001. SPECIFY HOW IS
 THIS EMERGENCY EGRESS ACCOMPLISHED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712