Plan Review Notes
Plan Review Notes For Permit 05090251
Permit Number 05090251
Review Stop P
Sequence Number 1
Notes
Date Text
2005-09-28 00:00:00DENIED;
 1.WATER HEATER DETAIL ON PAGE P-1 DOES
 NOT COMPLY, PLEASE DELETE OR CHANGE. NOT
 24 80 GAL HEATER TO BE INSTALLED. PLAN
 SHOWS HEATER IN MECHANICAL ROOM.
 2.THERMAL EXPANSION CONTROL REQUIRED SEE
 SEC. 607.3.
 3.RISER DIAGRAM NOT TO CODE. BAR SINK
 AND FLOOR DRAIN MUST DISCHARGE DOWN
 STREAM OF BATHROOM GROUP, SEE SEC.
 909.1. NOTE TRAP TO BE DEEP SEAL TYPE.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695