Plan Review Notes
Plan Review Notes For Permit 05090231
Permit Number 05090231
Review Stop B
Sequence Number 1
Notes
Date Text
2005-10-06 00:00:00BUILDING REVIEW CHECKLIST:
 1- NEED RECORDED NOTICE OF COMMENCEMENT.
  
 2- ROLLAFLEX SHADE:
 A) EVEN THOUGH THIS PRODUCT IS NOT USED
 FOR HURRICANE MISSILE IMPACT PROTECTION,
 STILL IT NEEDS TO MEET THE DESIGN
 CRITERIA OF SEC. 1606 FBC 2001. PRODUCT
 WAS DESIGNED FOR 90MPH. NEED TO COMPLY
 WITH THE 140MPH WIND LOAD DESIGN
 PRESSURES.
  
 B) WIND LOAD TABLE 3.44 IS NOT PREPARED
 BY THE SAME ENGINEER WHO DESIGNED THE
 ROLLAFLEX SHADE. NEED TO BE SIGNED AND
 SEALED BY THE CONSULTING ENGINEER SHOWN
 ON THE TITLE BLOCK AT BOTTOM OF PAGE AS
 REQUIRED BY CHAPTER 471 FLORIDA
 STATUTES.
  
 C) WIND LOAD TABLE 3.44: CLARIFY WHY
 USING TRIBUTARY AREA OF 100S.F.SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
  
 D) PROVIDE DETAILS AND SPECIFICATION FOR
 ANCHORING OF UPPER BOX SUPPORTING THE
 ROLLAFLEX SHADE WHEN IT'S IN OPEN
 POSITION. MUST RESIST WIND LOADS OF
 CHAPTER 16 FBC 2001.
  
 E) NUMBER OF SPANS ARE TWOACCORDING TO
 90MPH WIND LOAD. REVISE NUMBER OF SPAN
 REQUIRED ACCORDING TO THE REVISED
 ENGINEER CALCULATIONS FOR 140MPH. SEE
 SHEET 2 OF 2.SECTION 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
  
 F) ENGINEER TO PROVIDE ALL HIS
 INFORMATION ON SIGNED AND SEALED
 DRAWINGS AS REQUIRED BY CHAPTER 471 FL.
 STATUTES & FLORIDA ADMINISTRATIVE CODE
 61G15-23.002.
  
 G) PROVIDE SPECS/DETAILS OF HOW IS THE
 SHADE OPENED/CLOSED. IS IT DONE MANUALLY
 OR POWERED?. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001. (ELECTRIC PERMIT
 REQUIRED FOR POWERED OPERATION)
  
 H) PROVIDE 2 ORIGINAL SIGNED AND SEALED
 DRAWINGS. NOT COPIES. CHAPTER 471
 FLORIDA STATUTES.
  
 3- IF THE INTENTION IS TO PROTECT ALL
 DWELLING OPENINGS, THEN CLARIFY WHY
 OPENING #1 IS NOT GOING TO BE PROTECTED.
 LEAVING OPENINGS WITHOUT PROTECTION
 (SPECIALLY A LARGE OPENING) DECEIVES THE
 PURPOSE OF PROTECTING THE DWELLING.
 DWELLING WILL BE PARTIALLY OPEN AND IF
 GLASS BRAKES IN OPENING #1, THEN THE
 OTHER SHUTTERS WILL PROVIDE NOT
 PROTECTION BECAUSE THEY MAY BE BLOWN
 AWAY BY THE THE INTERNAL PRESSURES.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712.