2006-05-04 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 BUILDING |
| FBC-2001 CHAPTER 11 |
| FHA-98 DESIGN MANUAL |
| |
| FROM PREVIOUS REVIEW. THE COMMENT NUMBER |
| SHALL REMAIN THE SAME AS FIRST REVIEW: |
| |
| 1. SHT A2.0.5 SUBMIT CALCULATIONS FOR |
| PRIMARY AND SECONDARY ROOF DRAINS. SHOW |
| SQUARE FEET FOR EACH AREA, PLUS 1/2 AREA |
| OF ALL VERTICAL WALLS, INCLUDING |
| PARAPETS, AS WELL AS THE AREA OF ALL |
| ROOFS THAT DRAIN ONTO EACH AREA FROM |
| ABOVE ADDED IN CALCULATIONS. SECTIONS |
| 1106 & 1107 AND ALL SUBSECTIONS. |
| ***RESPONSE NOTED, BUT CALCULATION ARE |
| HARD TO READ. PLEASE SUBMIT THIS |
| INFORMATION IN 1/8" MINIMUM SCALE AS |
| REQUIRED IN SECTION 104.2.1.3. |
| |
| 3. SHTS A4.0.2, A4.0.2A, A4.0.3, |
| A4.0.3A, A4.0.4, & A4.0.4A, NO SHOWER |
| BATH ELEVATIONS FOR W/C SHOWN. W/C TO BE |
| 18" OFF WALL TO CENTER OF FIXTURE. LAV |
| TO BE 34" TO FLOOD RIM LEVEL. PAGES 7.43 |
| AND 7.52 FHA DESIGN MANUAL. SHTS A4.0.7, |
| & A4.0.7A W/C TO BE 18" OFF WALL TO |
| CENTER OF FIXTURE. (DETAIL E). |
| ***RESPONSE NOTED, BUT SHT A4.0.4A W/C |
| TO BE 1'6" OFF THE SAME WALL AS THE |
| DISPENSER. |
| |
| 4. SHT A4.0.8 SUBMIT CALCULATIONS FOR |
| MINIMUM FACILITIES PER TABLES 1003.1 |
| BLDG. AND 403.1 PLMG. SHOW SF OF EACH |
| COMMON AREA & INDICATE THE OCCUPANCY AND |
| OCCUPANCY LOAD OF EACH AREA. ALSO |
| INDICATE ROOM DESIGNATION ON PLANS. |
| SECTION 104.2.1. |
| ***RESPONSE NOTED, BUT 1 MORE W/C |
| REQUIRED IN THE WOMEN'S TOILET ROOM AS |
| REQUIRED FOR POTTY PARITY PER SECTION |
| 403.1.1 EXCEPTION. IN ASSEMBLY |
| OCCUPANCIES, THE ESTABLISHMENT SHALL |
| HAVE AT LEAST THE SAME NUMBER OF WATER |
| CLOSETS FOR WOMEN AS THE COMBINED TOTAL |
| OF WATER CLOSETS AND URINALS FOR MEN. |
| ALSO PER TABLE 403.1 A SERVICE SINK IS |
| REQUIRED. |
| |
| 5. SHT A4.0.8 KITCHEN SINK SHALL COMPLY |
| WITH SECTION 11-4.24 AND ALL |
| SUBSECTIONS. SUBMIT A DETAIL. FORWARD |
| APPROACH CLEAR FLOOR SPACE REQUIRED. |
| ***RESPONSE NOTED, BUT SUCH INFORMATION |
| SHALL BE SPECIFIC, AND THE TECHNICAL |
| CODES SHALL NOT BE CITED AS A WHOLE OR |
| IN PART, BE USED AS A SUBSTITUTE FOR |
| SPECIFIC INFORMATION. SECTION 104.2.1. |
| SHOW THE FOLLOWING: |
| A. 11-4.24.2 HEIGHT |
| B. 11-4.24.3 KNEE CLEARANCE |
| C. 11-4.24.4 SINK DEPTH |
| D. 11-4.24.5 CLEAR FLOOR SPACE - |
| FORWARD APPROACH IS REQUIRED AND SHALL |
| EXTEND A MAXIMUM 19" UNDERNEATH THE |
| SINK. CABINET DOORS ARE NOT APPROVED IN |
| THE CLEAR FLOOR SPACE OF THE SINK. |
| PLEASE DELETE FROM DETAIL. |
| E. 11-4.24.6 EXPOSED PIPES AND SURFACES |
| F. 11-4.24.7 FAUCETS |
| |
| 6. SHT A4.0.10 DETAIL #5, BACKFLOW |
| PROTECTION IS REQUIRED FOR THE TRASH |
| CHUTE WASHDOWN. SECTION 608. INDICATE |
| METHOD OF PROTECTION. |
| ***RESPONSE NOTED, BUT THIS SHALL BE |
| SHOWN ON THE WATER ISOMETRIC RISER |
| DIAGRAM TO REFLECT THE FLOOR TIME. |
| |
| 19. SHTS P5.3 & P5.4 SANT. ISOMETRIC |
| SHOW DFU'S AS THEY ACCUMULATE IN THE |
| SYSTEM. SECTION 104.2.1 & TABLE |
| 710.1(1). |
| ***RESP0NSE NOTED, BUT THE DFU'S ARE NOT |
| SHOWN AS THE ACCUMULATE IN THE BLDG. |
| SANT. (SEE RED LINE CORRECTIONS ON |
| SHEET) |
| |
| 22. SUBMIT A STORM RISER DIAGRAM |
| ISOMETRIC FOR THE BLDG. STORM DRAIN |
| SYSTEM. SHOW ALL PIPE SIZES, RISER |
| CONNECTION LOCATION, AND SF AS THEY |
| ACCUMULATE IN THE SYSTEM. SECTIONS |
| 104.2.1 AND 104.3.1.1. |
| ***RESPONSE NOTED, BUT SQUARE FOOTAGE IS |
| NOT SHOWN AS IT ACCUMULATES IN THE |
| SYSTEM. SQUARE FOOTAGE FROM ROOF DRAINS |
| IS NOT REFLECTED ON THE BUILDING STORM |
| DRAIN ISOMETRIC RISER DIAGRAM. PLEASE |
| CLARIFY. SECTION 104.2.1. |
| |
| 23. SUBMIT STORM RISER DIAGRAMS FOR EACH |
| RWL. SHOW ALL PIPE SIZES AND SF FOR EACH |
| RISER. SECTIONS 104.2.1 & 104.3.1.1. |
| ***RESPONSE NOTED, BUT THIS IS ANOTHER |
| BUILDING STORM DRAIN ISOMETRIC AND NOT |
| STORM RISER DIAGRAMS, (FOR RWL'S) SUBMIT |
| VERTICAL RISER DIAGRAMS FOR EACH RWL. |
| INDICATE RWL NUMBER FOR EACH. (EXAMPLE |
| RWL-1, RWL-2 ETC). |
| |
| **************NEW COMMENTS************** |
| 1B. CLEANOUTS ARE REQUIRED IN THE STORM |
| SYSTEM AS REQUIRED IN THE SANITARY |
| SYSTEM. SECTION 1101.8. SHOW CLEANOUTS |
| ON THE FLOOR PLAN, AS WELL AS ON THE |
| BUILDING STORM DRAIN ISOMETIC. |
| 2B. SHT P5.2 RISER S/E4 IS 32 FU'S NOT |
| 24 FU'S AS SHOWN. TABLE 709.1. |
| 3B. SHT P5.3 RISER S/D3 IS NOT SHOWN ON |
| THE BUILDING DRAIN SANT. ISOMETRIC. |
| 4B. SHT P5.3 CAN NOT SEE PART OF THE |
| BLDG DRAIN ISOMETRIC, (RISER S/D2), |
| BECAUSE OF THE WAY IT IS STAPLED |
| TOGETHER. PLEASE SHOW THAT PART OF THE |
| ISOMETRIC AS INDICATED IN RED OR ADJUST |
| THE WAY THE PLAN IS STAPLED TOGETHER. |
| SECTION 104.2.1.3. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |