Plan Review Notes
Plan Review Notes For Permit 05090156
Permit Number 05090156
Review Stop M
Sequence Number 2
Notes
Date Text
2006-05-16 00:00:00DENIED:2001 FLORIDA BUILDING CODE
 COMMENT #1 FROM REVIEW DATED 10/18/05:
 RESPONSE INDICATES NO EXHAUST DUCT
 EXTENDS OR PASS THROUGH RETURN AIR
 PLENUM.RESPONSE REFERS TO NOTE #8.
 NOTE #8 REFERS TO THE CITY OF BOYNTON
 BEACH.SEE ALSO NEW COMMENT # BELOW.
  
 COMMENT #2:OK
 COMMENT #3:RESPONSE TO COMMENT
 INDICATES RELIEF LOUVERS HAVE BEEN
 RELOCATED.SEE REV 1 ON PLAN SHEETS
 M4.4 & M4.5.PLANS STILL SHOW INTAKES
 AND EXHAUST TERMINATING AT AN EXIT
 ACCESS CORRIDOR WHICH IS PROHIBITED PER
 2001 FBC 1005.3.2.
  
 COMMENT #4:OK
 COMMENT #5:OK
 COMMENT #6:OK
  
 ****************************************
 NEW COMMENTS:
 7.PLAN SHEET M5.1 DETAIL FOR THE DRYER
 SHAFT.PLEASE ADDRESS THE FOLLOWING
 WITH REGARDS TO THE SHAFT ENCLOSURE.
 A) PER 2001 FBC 705.2.3.3, SHAFT SHALL
 CONTINUE THROUGH TO THE FIRST FLOOR. SEE
 ALSO EXCEPTION 1 TO THE AFOREMENTIONED
 CODE.
  
 8.FIRE DAMPER SHALL NOT BE INSTALLED
 ON THE DRYER EXHAUST.PLEASE PROVIDE
 MANUFACTURER'S SPECIFICATION AND
 INSTALLATION INSTRUCTIONS.
  
 9.AIR MAKE-UP IS NOT REQUIRED FOR THE
 THE SUB-DUCT SHAFT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  