2006-05-23 00:00:00 | ***DENIED*** |
| |
| PLEASE ADDRESS SOME PREVIOUS COMMENTS IN |
| ADDITION TO NEW COMMENTS: |
| |
| 1) PREVIOUS COMMENT #1- PLEASE INDICATE |
| THE INTERIOR FINISH CLASSIFICATION THAT |
| IS SPECIFIC TO THIS PROJECT. YOUR |
| RESPONSE GENERALLY CITES THE TECHNICAL |
| CODE REQUIREMENT. |
| |
| 2) KEY TURN ACTIVATION KNOX BOX ENTRY |
| SYSTEM IS REQUIRED ON NEW PROPERTY ENTRY |
| INSTALLATIONS. |
| |
| 3) PLEASE ILLUSTRATE ARRANGEMENT OF |
| MEANS OF EGRESS, (TRAVEL DISTANCE TO |
| EXITS, COMMON PATH OF TRAVEL, ETC) BASED |
| ON TYPE OF OCCUPANCY ON LIFE SAFETY |
| DRAWINGS. |
| |
| 4) TEMPORARY STANDPIPES ARE REQUIRED |
| WHEN THE BUILDING REACHES (3) STORIES OR |
| (30) FEET IN HEIGHT. |
| |
| 5) KNOX BOXES ARE REQUIRED ON THE |
| BUILDINGS. |
| |
| 6) DUCT SMOKE DETECTORS SHALL INITIATE A |
| GENERAL FIRE ALARM WHEN ACTIVATED IN |
| ACCORDANCE WITH LOCAL REQUIREMENTS. |
| |
| 7) NO SMOKE DETECTORS ARE SHOWN IN |
| CORRIDORS. PLEASE SEE NFPA 101, SECTIONS |
| 9.6.2.8 AND 9.6.2.9 REGARDING |
| REQUIREMENTS FOR ALL OCCUPIABLE AREAS, |
| COMMON AREAS, CORRIDORS ETC. |
| |
| 8) FDV'S TO BE 2 1/2" TO 1 1/2" REDUCER |
| WITH CHAINS. |
| |
| 9) DOUBLE CHECK DETECTOR ASSEMBLY SHALL |
| IN ADDITION TO ELECTRONIC SUPERVISION, |
| BE SECURED WITH CHAIN AND LOCK. |
| |
| 10) PLEASE PROVIDE PRESCRIPTIVE SRENGTH |
| REQUIREMENT FOR HANDRAILS AND GUARDS. |
| |
| |
| MIKE WENNERGREN, CAPTAIN/WPBFR |
| FIRE PLAN REVIEW (561) 805-6722 |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |