Plan Review Notes
Plan Review Notes For Permit 05090156
Permit Number 05090156
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2006-05-23 00:00:00***DENIED***
  
 PLEASE ADDRESS SOME PREVIOUS COMMENTS IN
 ADDITION TO NEW COMMENTS:
  
 1) PREVIOUS COMMENT #1- PLEASE INDICATE
 THE INTERIOR FINISH CLASSIFICATION THAT
 IS SPECIFIC TO THIS PROJECT. YOUR
 RESPONSE GENERALLY CITES THE TECHNICAL
 CODE REQUIREMENT.
  
 2) KEY TURN ACTIVATION KNOX BOX ENTRY
 SYSTEM IS REQUIRED ON NEW PROPERTY ENTRY
 INSTALLATIONS.
  
 3) PLEASE ILLUSTRATE ARRANGEMENT OF
 MEANS OF EGRESS, (TRAVEL DISTANCE TO
 EXITS, COMMON PATH OF TRAVEL, ETC) BASED
 ON TYPE OF OCCUPANCY ON LIFE SAFETY
 DRAWINGS.
  
 4) TEMPORARY STANDPIPES ARE REQUIRED
 WHEN THE BUILDING REACHES (3) STORIES OR
 (30) FEET IN HEIGHT.
  
 5) KNOX BOXES ARE REQUIRED ON THE
 BUILDINGS.
  
 6) DUCT SMOKE DETECTORS SHALL INITIATE A
 GENERAL FIRE ALARM WHEN ACTIVATED IN
 ACCORDANCE WITH LOCAL REQUIREMENTS.
  
 7) NO SMOKE DETECTORS ARE SHOWN IN
 CORRIDORS. PLEASE SEE NFPA 101, SECTIONS
 9.6.2.8 AND 9.6.2.9 REGARDING
 REQUIREMENTS FOR ALL OCCUPIABLE AREAS,
 COMMON AREAS, CORRIDORS ETC.
  
 8) FDV'S TO BE 2 1/2" TO 1 1/2" REDUCER
 WITH CHAINS.
  
 9) DOUBLE CHECK DETECTOR ASSEMBLY SHALL
 IN ADDITION TO ELECTRONIC SUPERVISION,
 BE SECURED WITH CHAIN AND LOCK.
  
 10) PLEASE PROVIDE PRESCRIPTIVE SRENGTH
 REQUIREMENT FOR HANDRAILS AND GUARDS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  