Plan Review Notes
Plan Review Notes For Permit 05090156
Permit Number 05090156
Review Stop E
Sequence Number 2
Notes
Date Text
2006-04-17 00:00:00**** UNSAT 2ND REVIEW ****
  
 ** PLEASE SEE SOME COMMENTS FROM
 PREVIOUS REVIEW WHICH STILL NEED TO BE
 ADDRESSED AND SOME NEW COMMENTS DUE TO
 INFORMATION/OR CHANGES TO PLANS.
  
  
 ** PLEASE SEE NOTES BELOW ARE TAKEN
 DIRECTLY FROM PREVIOUS REVIEW ABD NOTED.
 PLEASE SEE NEW NOTES WERE ADDED TO THE
 BOTTOM OF NOTES AND ARE NOTED AS NEW.
  
 MARVILLA
  
 4-STORY CONDO BLDGS W/ PARKING GARAGES.
  
  
 1)NOTE: OK.
  
 2)NOTE: NO/YES, PLEASE SEE A DETAIL WAS
 SUBMITTED, HOWEVER PLEASE KNOW THE
 CURBING SHALL GO COMPLETELY AROUND BUS
 PENTRATING THE FLR. CAN NOT BE THREE
 SIDED UP ON WALL.
  
 ** PREVIOUS NOTE **
 PLEASE PROVIDE A DETAIL FOR CURBING
 REQUIRED AROUND BUS-DUCT ON FLOOR
 PENETRATIONS WHERE A VERTICAL RISER
 PENETRATES TWO OR MORE DRY FLOORS,
 A MINIMUM 100 MM (4 IN.) HIGH CURB SHALL
 BE INSTALLED AROUND ALL FLOOR OPENINGS
 FOR RISER BUSWAYS TO PREVENT LIQUIDS
 FROM ENTERING THE OPENING. PER 368.6
  
 3)NOTE: OK, HOWEVER SEE NOTE #7 FOR
 OTHER AREAS WHICH REQUIRE A BATTERY FIX.
  
  
 4)NOTE:NO, PLEASE SEE STAIR AREA WERE
 NOT SHOWN AND PHOTO METRICS WERE DONE
 FOR MOST FLRS AND AREAS BUT NOT ALL.
 PLEASE SEE IF FIRST FLR IS "TYPICAL"
 THEN PLEASE NOTE AS:
 PLEASE SEE WHAT APPEARS TO BE FT CANDLES
 SHOWN ON OTHER SHEETS WHICH ARE NOT
 VISABLE.
  
 ** PREVIOUS NOTE**
 PLEASE PROVIDE PHOTOMETRICS FOR
 STAIR/CORRIDOR AREAS FOR EGRESS TO THE
 PUBLIC RIGHT OF WAY. PLEASE SEE 2003
 101, 7.8 AND 7.9, WHICH REQUIRES 10FT
 CANDLES FOR STAIR AREAS AND 1FT FOR
 CORRIDOR.
 7.8.1.3,7.9.2.1
  
 5)NOTE: OK.
  
 6)NOTE:NO, PLEASE SEE RESPONSE
 MENTTIONS THIS TO BE DONE LATER, HOWEVER
 THIS IS REQUIRED AT THIS TIME AS NOTED
 PREVIOUSLY. THIS WOULD MOST LIKELY NOT
 BE DONE BY THE ELECTRICAL ENGINEER.
  
 ** PREVIOUS NOTE **
 PLEASE PROVIDE DETAIL FOR ROOF TOP LT
 POLES AND FIXTURES. PLEASE PROVIDE WIND
 LOAD CALCULATIONS FOR REVIEW. THIS IS
 REQUIRED AT THIS TIME FOR FIXTURES AND
 POLES.
 CALCULATIONS WILL BE REVIEWED BY THE
 BLDG REVIEWER FOR CODE COMPLIANCE OF FBC
 140 MPH WIND LOADS.
  
 7)NOTE: NO, PLEASE SEE SOME SHEETS
 INDICATE THE CORRECT FIXTURE
 IDENTIFICATION AND CORRELATES WITH THE
 FIXTURE SCHEDULE, HOWEVER SOME OF THE
 COMMON AREA/GARAGE AREA PLANS/SHEETS
 SHOW FIXTURES WHICH ARE NOT BATTERY BACK
 UP AND /OR ARE NOT ON FIXTURE SCHEDULE
 AND SYMBOL SEEMS TO LEND TO THE FIXTURE
 BEING A BATTERY BACK UP FIXTURE OF SOME
 SORT. "B" , B2".
  
 ** PREVIOUS NOTE **
 PLEASE SUBMIT A COMPLETED LIGHTING
 FIXTURE SCHEDULE TO CORRELATE WITH
 FIXTURES AS SHOWN ON PLANS. PLEASE ALSO
 SEE COMMON AREAS WHERE FIXTURES DO NOT
 INDICATE WHAT TYPE ETC.
 RECREATION AREA, ROOF TOP ETC.
  
 8)NOTE: OK
  
 9)NOTE: OK.
  
  
 10)NOTE: OK.
  
 11)NOTE: OK.
  
 12)NOTE: OK.
  
 13)NOTE: OK.
  
 14)NOTE:OK, HOWEVER PLEASE CORRELATE
 CIRCUITING AS, UNITS SHOWN DINING ARE
 WITH 15A CIRCUIT(S). PLEASE SEE
 210.52B1, 210.11C1 AND 220.16A FOR TWO
 OR MORE CIRCUITS. PLEASE ADJUST
 CIRCUITING ANDLOAD CALCUALTIONS.
  
 ** PRWEVIOUS NOTE **
 PLEASE PROVIDE "DINING RM/AREA"
 DESIGNATIONS ON UNITS "A" AND "E".
 210.52B.
  
 15)NOTE: NO, PLEASE SEE SOME OF THESE
 RMS, ELEV EQUIPMENT ETC DO NOT SHOW ROOM
 DESIGNATIONS OR NOTE WHERE TO FIND. SEE
 GARAGE PLANS ALSO. POOL RM LABLED.OK
  
 ** PREVIOUS NOTE **
 PLEASE PROVIDE ROOM/ AREA DESIGNATIONS
 ON COMMON AREAS PLANS.
 PLEASE SEE ROOMS ETC NOT LABLED.
 PLEASE SEE ELECTRICAL PLANS DO NOT
 INDICATE "POOL EQUIPMENT " ROOM ETC.
  
 16)NOTE:NO, SAME NOTE:RESPONSE
 MENTIONS TO SEE REVISED SHEETS, HOWEVER
 THE SAME #'S ARE SHOWNA S ON PREVIOUS
 PLANS.??
  
 ** PREVIOUS NOTE **
 PLEASE SEE 424.3B WHICH REQUIRES ALL
 OVERCURRENT PROTECTION FOR AHU'S HEAT TO
 BE A MIN OF 125%.
 PLEASE SEE THESE AS REDLINED ON PLANS.
 PLEASE ALSO REVISE MIN AWG PER 310.16
 ONCE OCP HAS BEEN ADJUSTED.
 PLEASE KNOW, MOST OCP IS 150% MAX,
 HOWEVER WHEN A AMPERAGE DOES NOT
 CORRESPONED TO A COMMON OCP DEVICE AS
 LISTED IN 240.6, GOING UP TO THE NEXT
 HIGHER OCP IS PERMITTED.
  
 17)NOTE:NO, SAME NOTE,RESPONSE
 MENTIONS TO SEE REVISED, HOWEVER THE
 PANEL SCHEDULES WERE NOT CHANGED??
  
 ** PREVIOUS NOTE **
 PLEASE SEE MANY OF THE UNITS AS LISTED
 ON HOUSE PANELS ALSO NEED TO BE
 ADJUSTED.
 PLEASE SEE L2B AHU#10, SHOWS 11KW ON A
 2P-30A WITH #10 AWG.
 AHU #11 LISTED TWICE, SHOWS 11KW ON
 2P-45A WITH #8.
 AHU#11 LISTED AGAIN, 4.8KW WITHAND 30A
 OCP THIS ONE IS OK.
 PLEASE SEE AHU#10 IS LISTED TWICE ALSO.
 PLEASE SEE AHU #6 ON LRB.
 PLEASE SEE AHU #7 ON LRB.
 BOTH WITH THE SAME COMMENTS AS LISTED
 ABOVE.
 PLEASE ADJUST.424.3B,310.16
  
 18)NOTE: NO,?? RESPONSE LTR MENTIONS TO
 SEE REVISED,HOWVER THE SAME #'S ARE
 SHOWN?
 ** PREVIOUS NOTES**
 PLEASE SEE MIN OCPFOR WATER HEATER
 UNITS, SHALL BE A MIN OF 125% AND A MAX
 OF 150%.
 PLEASE SEE 6KW SHOWN ON A 2P35.
 422.13,422.11E3
  
 19)NOTE: OK, HOWEVER PLEASE SEE THE
 CONTINUOUS LOADS NOTE WAS ADDED TO ALL
 PLANS INCLUDING UNITS??
  
 ** PREVIOUS NOTE **
 PLEASE SHOW ALL CONTINUOUS LOADS
 AT 125%. PLEASE SEE THIS IS FOR LOADS
 DEDICATED TO HOUSE PANELS, POOL PUMPS,
 ANY POOL HEAT PUMPS, LIGHTING , LARGEST
 MOTOR STEC.
 215.3,230.42 ETC.
  
 20)NOTE: OK.
  
 21)NOTE: OK/NO, PLEASE SEE SPECS WERE
 SUBMITTED AND VERIFIED, HOWEVER PLEASE
 SEE PLANS DO NOT REFLECT OR NOTE
 ANYTHING FOR LOCKED ROTOR FOR THE FIRE
 PUMP AND PLANS AND SPECS FOR THE FIRE
 PUMP DO NOT CORRELATE FOR SIZING. PLEASE
 SPECIFY THE LOCAKED ROTOR SETTING PER
 MANUFACTURES SPECS AND PLEASE CORRELATE
 THE HP RATINGS. (SPECS SHOW 100HP AND
 RISER SHOWS 125HP).REVIEW FOR CONDUCTORS
 OCP ETC CANNOT BE DONE AT THIS TIME.
  
 ** PREVIOUS NOTE **
 PLEASE SUBMIT ALL MANUFACTURE SPECS/CUT
 SHEETS FOR FIRE PUMP AND FIRE PUMP
 CONTROLLER.
 PLEASE BE SURE NOTES FOR LOCKED ROTOR
 AND MANUAL MEANS OF DISCONNECT IS
 LOCATED ON PLANS.
 PLEASE SEE 695.4B1,
 NFPA-20 10.4.2.1.1,10.4.2.2 ETC.
 PLEASE SEE THIS INFORMATION IS REQUIRED
 AT THIS TIME EVEN IF FIRE PUMP/
 CONTROLLER IS PERMITTED UNDER FIRE
 SPRINKLER PERMIT.
  
 22)NOTE:OK.
  
 23)NOTE: OK.
  
 24)NOTE: OK.
  
 25)NOTE: OK.
  
 26)NOTE: OK.
  
 27)NOTE: OK.
  
 28)NOTE: OK.
  
 29)NOTE: OK.
  
 30)NOTE:OK, HOWEVER PLEASE SEE COMMON
 AREA PLANS AND GARAGE LIGHTING PLANS
 WHICH INDICATE THE LIGHTING IN THESE RMS
 CIRCUITED TO THE GARAGE LTS.
 PLEASE ADJUST.
  
 ** PREVIOUS NOTE **
 PLEASE SEE 620.23,620.24 WHICH REQUIRES
 DEDICATED CIRCUITS FOR ELEVATOR PIT LTS
 AND RECEPTS. THIS CIRCUIT MAY NOT FEED
 ANY OTHER LTS AND RECEPTS.
 THESE SHALL ALSO BE DEDICATE TO EACH
 ELEVATOR/PIT.
 PLEASE SEE CIRCUITS FOR ELEVATOR
 EQUIPMENT ROOMS SHALL ALSO BE DEDICATED
 AND MAY NOT FEED ANY OTHER ROOMS OR
 ELECTRICAL LIGHTING OR RECEPTS.
 PLEASE ALSO SEE PREVIOUS NOTE WHICH IS
 REQUIRING A BATTERY BACK-UP FIXTURE IN
 THESE ROOMS.
 PLEASE ALSO SEE 700.16D
  
 31)NOTE: OK.
  
 32)NOTE: OK.
  
 33)NOTE: OK.
  
  
 ****** NEW NOTE ****
  
 34) NOTE: PLEASE SEE ALL UNITS LOCATED
 ON THE FIRST FLR WITH GRADE LEVEL
 ACCESS/EGRESS FROM UNIT/ FROM PATIO
 SHALL CONTAIN A LT FIXTURE OF SOME SORT
 FOR EGRESS LT. THIS MAY BE ADDRESSED AS
 A CLOUDED NOTE FOR ALL FIRST FLR UNITS.
 210.70, LS 101-7.8
  
 35) NOTE: PLEASE SEE COPY OF FS
 553.80(2)(B) ATTACHED WITH RESPECT TO
 REPEAT COMMENTS. THIS IS ONLY A NOTICE
 AT THIS TIME.
  
 ** PLEASE KNOW, MANY OF THE ABOVE ITEMS
 HAVE BEENREDLINED ON PLANS FOR AREAS
 OF COMMENTS.
  
 **PLEASE SEE ALL COMMENTS FROM ALL OTHER
 TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
 PLEASE SEE FIRE REVIEW COMMENTS.
  
 ** PLEASE REMOVE ALL OLD/VOIDED SHEETS
 FROM SETS AND ONLY INSERT NEW REVISED
 SHEETS INTO COMPLETE SETS FOR REVIEW AND
 STAMPING. ONE SET OF ALL OL/VOIDED
 SHEETS SHOULD BE SUBMITTED FOR
 REFERENCE.
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DONOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2006-04-13 00:00:00ONE ROLL IN ELECTRIC FOR REVIEW