2006-04-17 00:00:00 | **** UNSAT 2ND REVIEW **** |
| |
| ** PLEASE SEE SOME COMMENTS FROM |
| PREVIOUS REVIEW WHICH STILL NEED TO BE |
| ADDRESSED AND SOME NEW COMMENTS DUE TO |
| INFORMATION/OR CHANGES TO PLANS. |
| |
| |
| ** PLEASE SEE NOTES BELOW ARE TAKEN |
| DIRECTLY FROM PREVIOUS REVIEW ABD NOTED. |
| PLEASE SEE NEW NOTES WERE ADDED TO THE |
| BOTTOM OF NOTES AND ARE NOTED AS NEW. |
| |
| MARVILLA |
| |
| 4-STORY CONDO BLDGS W/ PARKING GARAGES. |
| |
| |
| 1)NOTE: OK. |
| |
| 2)NOTE: NO/YES, PLEASE SEE A DETAIL WAS |
| SUBMITTED, HOWEVER PLEASE KNOW THE |
| CURBING SHALL GO COMPLETELY AROUND BUS |
| PENTRATING THE FLR. CAN NOT BE THREE |
| SIDED UP ON WALL. |
| |
| ** PREVIOUS NOTE ** |
| PLEASE PROVIDE A DETAIL FOR CURBING |
| REQUIRED AROUND BUS-DUCT ON FLOOR |
| PENETRATIONS WHERE A VERTICAL RISER |
| PENETRATES TWO OR MORE DRY FLOORS, |
| A MINIMUM 100 MM (4 IN.) HIGH CURB SHALL |
| BE INSTALLED AROUND ALL FLOOR OPENINGS |
| FOR RISER BUSWAYS TO PREVENT LIQUIDS |
| FROM ENTERING THE OPENING. PER 368.6 |
| |
| 3)NOTE: OK, HOWEVER SEE NOTE #7 FOR |
| OTHER AREAS WHICH REQUIRE A BATTERY FIX. |
| |
| |
| 4)NOTE:NO, PLEASE SEE STAIR AREA WERE |
| NOT SHOWN AND PHOTO METRICS WERE DONE |
| FOR MOST FLRS AND AREAS BUT NOT ALL. |
| PLEASE SEE IF FIRST FLR IS "TYPICAL" |
| THEN PLEASE NOTE AS: |
| PLEASE SEE WHAT APPEARS TO BE FT CANDLES |
| SHOWN ON OTHER SHEETS WHICH ARE NOT |
| VISABLE. |
| |
| ** PREVIOUS NOTE** |
| PLEASE PROVIDE PHOTOMETRICS FOR |
| STAIR/CORRIDOR AREAS FOR EGRESS TO THE |
| PUBLIC RIGHT OF WAY. PLEASE SEE 2003 |
| 101, 7.8 AND 7.9, WHICH REQUIRES 10FT |
| CANDLES FOR STAIR AREAS AND 1FT FOR |
| CORRIDOR. |
| 7.8.1.3,7.9.2.1 |
| |
| 5)NOTE: OK. |
| |
| 6)NOTE:NO, PLEASE SEE RESPONSE |
| MENTTIONS THIS TO BE DONE LATER, HOWEVER |
| THIS IS REQUIRED AT THIS TIME AS NOTED |
| PREVIOUSLY. THIS WOULD MOST LIKELY NOT |
| BE DONE BY THE ELECTRICAL ENGINEER. |
| |
| ** PREVIOUS NOTE ** |
| PLEASE PROVIDE DETAIL FOR ROOF TOP LT |
| POLES AND FIXTURES. PLEASE PROVIDE WIND |
| LOAD CALCULATIONS FOR REVIEW. THIS IS |
| REQUIRED AT THIS TIME FOR FIXTURES AND |
| POLES. |
| CALCULATIONS WILL BE REVIEWED BY THE |
| BLDG REVIEWER FOR CODE COMPLIANCE OF FBC |
| 140 MPH WIND LOADS. |
| |
| 7)NOTE: NO, PLEASE SEE SOME SHEETS |
| INDICATE THE CORRECT FIXTURE |
| IDENTIFICATION AND CORRELATES WITH THE |
| FIXTURE SCHEDULE, HOWEVER SOME OF THE |
| COMMON AREA/GARAGE AREA PLANS/SHEETS |
| SHOW FIXTURES WHICH ARE NOT BATTERY BACK |
| UP AND /OR ARE NOT ON FIXTURE SCHEDULE |
| AND SYMBOL SEEMS TO LEND TO THE FIXTURE |
| BEING A BATTERY BACK UP FIXTURE OF SOME |
| SORT. "B" , B2". |
| |
| ** PREVIOUS NOTE ** |
| PLEASE SUBMIT A COMPLETED LIGHTING |
| FIXTURE SCHEDULE TO CORRELATE WITH |
| FIXTURES AS SHOWN ON PLANS. PLEASE ALSO |
| SEE COMMON AREAS WHERE FIXTURES DO NOT |
| INDICATE WHAT TYPE ETC. |
| RECREATION AREA, ROOF TOP ETC. |
| |
| 8)NOTE: OK |
| |
| 9)NOTE: OK. |
| |
| |
| 10)NOTE: OK. |
| |
| 11)NOTE: OK. |
| |
| 12)NOTE: OK. |
| |
| 13)NOTE: OK. |
| |
| 14)NOTE:OK, HOWEVER PLEASE CORRELATE |
| CIRCUITING AS, UNITS SHOWN DINING ARE |
| WITH 15A CIRCUIT(S). PLEASE SEE |
| 210.52B1, 210.11C1 AND 220.16A FOR TWO |
| OR MORE CIRCUITS. PLEASE ADJUST |
| CIRCUITING ANDLOAD CALCUALTIONS. |
| |
| ** PRWEVIOUS NOTE ** |
| PLEASE PROVIDE "DINING RM/AREA" |
| DESIGNATIONS ON UNITS "A" AND "E". |
| 210.52B. |
| |
| 15)NOTE: NO, PLEASE SEE SOME OF THESE |
| RMS, ELEV EQUIPMENT ETC DO NOT SHOW ROOM |
| DESIGNATIONS OR NOTE WHERE TO FIND. SEE |
| GARAGE PLANS ALSO. POOL RM LABLED.OK |
| |
| ** PREVIOUS NOTE ** |
| PLEASE PROVIDE ROOM/ AREA DESIGNATIONS |
| ON COMMON AREAS PLANS. |
| PLEASE SEE ROOMS ETC NOT LABLED. |
| PLEASE SEE ELECTRICAL PLANS DO NOT |
| INDICATE "POOL EQUIPMENT " ROOM ETC. |
| |
| 16)NOTE:NO, SAME NOTE:RESPONSE |
| MENTIONS TO SEE REVISED SHEETS, HOWEVER |
| THE SAME #'S ARE SHOWNA S ON PREVIOUS |
| PLANS.?? |
| |
| ** PREVIOUS NOTE ** |
| PLEASE SEE 424.3B WHICH REQUIRES ALL |
| OVERCURRENT PROTECTION FOR AHU'S HEAT TO |
| BE A MIN OF 125%. |
| PLEASE SEE THESE AS REDLINED ON PLANS. |
| PLEASE ALSO REVISE MIN AWG PER 310.16 |
| ONCE OCP HAS BEEN ADJUSTED. |
| PLEASE KNOW, MOST OCP IS 150% MAX, |
| HOWEVER WHEN A AMPERAGE DOES NOT |
| CORRESPONED TO A COMMON OCP DEVICE AS |
| LISTED IN 240.6, GOING UP TO THE NEXT |
| HIGHER OCP IS PERMITTED. |
| |
| 17)NOTE:NO, SAME NOTE,RESPONSE |
| MENTIONS TO SEE REVISED, HOWEVER THE |
| PANEL SCHEDULES WERE NOT CHANGED?? |
| |
| ** PREVIOUS NOTE ** |
| PLEASE SEE MANY OF THE UNITS AS LISTED |
| ON HOUSE PANELS ALSO NEED TO BE |
| ADJUSTED. |
| PLEASE SEE L2B AHU#10, SHOWS 11KW ON A |
| 2P-30A WITH #10 AWG. |
| AHU #11 LISTED TWICE, SHOWS 11KW ON |
| 2P-45A WITH #8. |
| AHU#11 LISTED AGAIN, 4.8KW WITHAND 30A |
| OCP THIS ONE IS OK. |
| PLEASE SEE AHU#10 IS LISTED TWICE ALSO. |
| PLEASE SEE AHU #6 ON LRB. |
| PLEASE SEE AHU #7 ON LRB. |
| BOTH WITH THE SAME COMMENTS AS LISTED |
| ABOVE. |
| PLEASE ADJUST.424.3B,310.16 |
| |
| 18)NOTE: NO,?? RESPONSE LTR MENTIONS TO |
| SEE REVISED,HOWVER THE SAME #'S ARE |
| SHOWN? |
| ** PREVIOUS NOTES** |
| PLEASE SEE MIN OCPFOR WATER HEATER |
| UNITS, SHALL BE A MIN OF 125% AND A MAX |
| OF 150%. |
| PLEASE SEE 6KW SHOWN ON A 2P35. |
| 422.13,422.11E3 |
| |
| 19)NOTE: OK, HOWEVER PLEASE SEE THE |
| CONTINUOUS LOADS NOTE WAS ADDED TO ALL |
| PLANS INCLUDING UNITS?? |
| |
| ** PREVIOUS NOTE ** |
| PLEASE SHOW ALL CONTINUOUS LOADS |
| AT 125%. PLEASE SEE THIS IS FOR LOADS |
| DEDICATED TO HOUSE PANELS, POOL PUMPS, |
| ANY POOL HEAT PUMPS, LIGHTING , LARGEST |
| MOTOR STEC. |
| 215.3,230.42 ETC. |
| |
| 20)NOTE: OK. |
| |
| 21)NOTE: OK/NO, PLEASE SEE SPECS WERE |
| SUBMITTED AND VERIFIED, HOWEVER PLEASE |
| SEE PLANS DO NOT REFLECT OR NOTE |
| ANYTHING FOR LOCKED ROTOR FOR THE FIRE |
| PUMP AND PLANS AND SPECS FOR THE FIRE |
| PUMP DO NOT CORRELATE FOR SIZING. PLEASE |
| SPECIFY THE LOCAKED ROTOR SETTING PER |
| MANUFACTURES SPECS AND PLEASE CORRELATE |
| THE HP RATINGS. (SPECS SHOW 100HP AND |
| RISER SHOWS 125HP).REVIEW FOR CONDUCTORS |
| OCP ETC CANNOT BE DONE AT THIS TIME. |
| |
| ** PREVIOUS NOTE ** |
| PLEASE SUBMIT ALL MANUFACTURE SPECS/CUT |
| SHEETS FOR FIRE PUMP AND FIRE PUMP |
| CONTROLLER. |
| PLEASE BE SURE NOTES FOR LOCKED ROTOR |
| AND MANUAL MEANS OF DISCONNECT IS |
| LOCATED ON PLANS. |
| PLEASE SEE 695.4B1, |
| NFPA-20 10.4.2.1.1,10.4.2.2 ETC. |
| PLEASE SEE THIS INFORMATION IS REQUIRED |
| AT THIS TIME EVEN IF FIRE PUMP/ |
| CONTROLLER IS PERMITTED UNDER FIRE |
| SPRINKLER PERMIT. |
| |
| 22)NOTE:OK. |
| |
| 23)NOTE: OK. |
| |
| 24)NOTE: OK. |
| |
| 25)NOTE: OK. |
| |
| 26)NOTE: OK. |
| |
| 27)NOTE: OK. |
| |
| 28)NOTE: OK. |
| |
| 29)NOTE: OK. |
| |
| 30)NOTE:OK, HOWEVER PLEASE SEE COMMON |
| AREA PLANS AND GARAGE LIGHTING PLANS |
| WHICH INDICATE THE LIGHTING IN THESE RMS |
| CIRCUITED TO THE GARAGE LTS. |
| PLEASE ADJUST. |
| |
| ** PREVIOUS NOTE ** |
| PLEASE SEE 620.23,620.24 WHICH REQUIRES |
| DEDICATED CIRCUITS FOR ELEVATOR PIT LTS |
| AND RECEPTS. THIS CIRCUIT MAY NOT FEED |
| ANY OTHER LTS AND RECEPTS. |
| THESE SHALL ALSO BE DEDICATE TO EACH |
| ELEVATOR/PIT. |
| PLEASE SEE CIRCUITS FOR ELEVATOR |
| EQUIPMENT ROOMS SHALL ALSO BE DEDICATED |
| AND MAY NOT FEED ANY OTHER ROOMS OR |
| ELECTRICAL LIGHTING OR RECEPTS. |
| PLEASE ALSO SEE PREVIOUS NOTE WHICH IS |
| REQUIRING A BATTERY BACK-UP FIXTURE IN |
| THESE ROOMS. |
| PLEASE ALSO SEE 700.16D |
| |
| 31)NOTE: OK. |
| |
| 32)NOTE: OK. |
| |
| 33)NOTE: OK. |
| |
| |
| ****** NEW NOTE **** |
| |
| 34) NOTE: PLEASE SEE ALL UNITS LOCATED |
| ON THE FIRST FLR WITH GRADE LEVEL |
| ACCESS/EGRESS FROM UNIT/ FROM PATIO |
| SHALL CONTAIN A LT FIXTURE OF SOME SORT |
| FOR EGRESS LT. THIS MAY BE ADDRESSED AS |
| A CLOUDED NOTE FOR ALL FIRST FLR UNITS. |
| 210.70, LS 101-7.8 |
| |
| 35) NOTE: PLEASE SEE COPY OF FS |
| 553.80(2)(B) ATTACHED WITH RESPECT TO |
| REPEAT COMMENTS. THIS IS ONLY A NOTICE |
| AT THIS TIME. |
| |
| ** PLEASE KNOW, MANY OF THE ABOVE ITEMS |
| HAVE BEENREDLINED ON PLANS FOR AREAS |
| OF COMMENTS. |
| |
| **PLEASE SEE ALL COMMENTS FROM ALL OTHER |
| TRADES WHICH MAY AFFECT ELECTRICAL |
| PLANS. |
| PLEASE SEE FIRE REVIEW COMMENTS. |
| |
| ** PLEASE REMOVE ALL OLD/VOIDED SHEETS |
| FROM SETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO COMPLETE SETS FOR REVIEW AND |
| STAMPING. ONE SET OF ALL OL/VOIDED |
| SHEETS SHOULD BE SUBMITTED FOR |
| REFERENCE. |
| |
| ** PLEASE SUBMIT THE ABOVE INFORMATION |
| FOR REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DONOT HESITATE IN CONTACTING |
| THIS OFFICE. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-805-6717 |
| [email protected] |