2006-05-22 00:00:00 | PERMIT NUMBER: 05090156 |
| ADDRESS: 3701 N MILITARY TRAIL |
| CONTRACTOR: TOWN AND COUNTRY HOMES |
| FOUR STORY R2 WITH PARKING GARAGE |
| TYPE II SPRINKLERED (13R SYSTEM) |
| CODE EDITION: 2001 FBC |
| SECOND REVIEW |
| --------------------------------------- |
| DENIED |
| |
| |
| 1)WPB AMENDMENT 105.13.6. W.P.B. |
| CONSTRUCTION SERVICES DEPARTMENT |
| REQUEST FOR THRESHOLD BUILDINGS A |
| SPECIAL INSPECTOR AS REQUIRED BY S. |
| 553.79(5) FLORIDA STATUTES TO THE MIN- |
| IMUM INSPECTIONS REQUIRED BY THIS CODE. |
| CONTACT HAROLD PISKURA MANAGER OF THE |
| SPECIAL INSPECTOR PROGRAM AT (561) |
| 805-6711 FOR FURTHER INFORMATION BEFORE |
| THE PERMIT MAY BE ISSUED. |
| |
| 2) CONDOMINIUM V APARTMENTS.IF THE |
| DWELLING UNITS ARE TO BE SOLD AS |
| CONDOMINIUMS, A 'DECLARATION OF |
| CONDOMINIUM' SHALL BE SUBMITTED TO THE |
| STATE FOR APPROVAL, AND THEN RECORDED |
| WITH THE CLERK OF THE COUNTY COURT.A |
| RECORDED COPY SHALL BE SUBMITTED TO THE |
| CITY FOR RECORDS, ADDRESSING PURPOSES, |
| AND TO PALM BEACH COUNTY PROPERTY |
| APPRAISER'S OFFICE PRIOR TO C.O. |
| RECORDED COPY OF CONDOMINIUM DOCUMENTS |
| RECEIVED. |
| |
| 3) ALL THREE (3) COPIES OF THE |
| SUBSURFACE SOIL REPORTS, OTHER REPORTS, |
| CALCULATIONS AND DRAWINGS PREPARED BY A |
| FLORIDA REGISTERED ARCHITECT OR ENGINEER |
| ARE REQUIRED TO BE SIGNED AND SEALED. |
| |
| 4) SUBMIT (3) SETS OF ENGINEERED LAYOUTS |
| AND TRUSS DRAWINGS FOR THE METAL TRUSSES |
| THAT HAVE BEEN REVIEWED AND APPROVED BY |
| THE DESIGNER OF RECORD FOR THE |
| STRUCTURE. |
| |
| 5) REVISED DETAILS #9 THRU #13 ON SHEET |
| A-8.3.1 AND #2, #4 ON A-8.3.2 SPECIFY |
| WOOD TRUSSES AND DO NOT SPECIFY FIRE |
| TREATED PLYWOOD. THIS STRUCTURE IS |
| SPECIFIED AS TYPE II CONSTRUCTION AND |
| DOES NOT ALLOW COMBUSTIBLE MATERIALS AT |
| THIS LOCATION. PLEASE CORRECT. |
| |
| 6) SPECIFY THE ATTACHMENT SPACING AND |
| FASTENERS FOR THE FIRETREATED PLYWOOD |
| SHEATHING TO THE METAL TRUSSES. |
| |
| 7) SUBMIT (3) SETS OF ENGINEERED SHOP |
| DRAWINGS AND LAYOUTS FOR THE PRECAST |
| SYSTEM FOR THE PARKING GARAGE.(PRIOR TO |
| CONSTRUCTION) |
| |
| 8) THE CORRIDOR BETWEEN THE FITNESS |
| CENTER AND THE BATH ROOMS IS A DEAD END |
| HALLWAY THAT EXCEEDS TWENTY FEET IN |
| LENGTH WHICH IS PROHIBITED BY FBC |
| 1005.2. |
| |
| 9) 2001 FBC 903.7.6 REQUIRES GROUP R2 |
| OCCUPANCIES THREE OR MORE STORIES IN |
| HEIGHT TO BE PROVIDED THROUGHOUT WITH AN |
| APPROVED AUTOMATIC SPRINKLER SYSTEM. |
| EXCEPTION (2) ALLOWS AN AUTOMATIC |
| SPRINKLER SYSTEM COMPLYING WITH NFPA 13R |
| FOR BUILDINGS NOT EXCEEDING FOUR STORIES |
| IN HEIGHT PROVIDED THE AUTOMATIC |
| SPRINKLER SYSTEM SHALL NOT BE CONSIDERED |
| AS AN ALTERNATE TO OTHER REQUIREMENTS OF |
| THE CODE. (SEE 903.2) FBC 903.2 STATES |
| THAT AUTOMATIC SPRINKLER SYSTEMS |
| INSTALLED IN LIEU OF OR AS AN ALTERNATE |
| TO OTHER REQUIREMENTS, AS PERMITTED BY |
| THIS CODE, SHALL BE CONSIDERED REQUIRED |
| SYSTEMS AND SHALL COMPLY WITH NFPA 13. |
| THIS MEANS THAT IN ORDER TO APPLY THE |
| REDUCTION IN CORRIDOR FIRE RATING |
| ALLOWED BY TABLE 704.2.4 TO 1/2 HOUR FOR |
| FULLY SPRINKLERED BUILDINGS OR THE |
| INCREASED TRAVEL DISTANCE OF 325' IN |
| TABLE 1004 FOR SPRINKLERED BUILDINGS AN |
| NFPA 13 SPRINKLER SYSTEM IS REQUIRED. |
| |
| 10) THE BILLARD ROOM IS AN ASSEMBLY |
| OCCUPANCY WHICH REQUIRES A TWO HOUR |
| TENANT FIRE SEPARATION. SEE FBC 704.1.1 |
| HOWEVER, FBC 704.1.2.3 ALLOWS A ONE HOUR |
| OCCUPANCY SEPARATION. |
| |
| 11) ALL FIRE RATED DOORS ARE REQUIRED TO |
| HAVE APPROVED CLOSERS OR BE SELF |
| CLOSING. SPECIFY CLOSERS FOR ALL RATED |
| DOORS PER FBC 705.1.3.2.3. SPECIFY IN |
| THE DOOR SCHEDULE ON A4.0.8 THAT DOOR #4 |
| IS REQUIRED TO HAVE APPROVED CLOSERS. |
| |
| 12) A VERTICAL SECTION THROUGH THE TRASH |
| CHUTE IS INDICATED AS 5 ON A4.0.10 THIS |
| IS INCORRECT AS IT IS LOCATED ON DETAIL |
| 5 ON A4.0.10. PLEASE CORRECT. |
| |
| 13) THE TRASH CHUTE SECTION SHOWN ON |
| SHEET A8.1.4 IS INCORRECTLY LABELED AS 4 |
| ON A4.0.7. PLEASE CORRECT. |
| |
| 14) PLEASE REVISE NEW NOTES ON A8.2.1 |
| AND A8.2.2 WHICH REFER TO THE HIGH |
| VELOCITY HURRICANE ZONES AS REQUIRING |
| IMPACT PROTECTION. THE CITY OF WEST PALM |
| BEACH IS NOT IN THE HIGH VELOCITY |
| HURRICANE ZONE, HOWEVER, WE ARE LOCATED |
| IN THE WIND BOURNE DEBRIS REGION AND |
| BECAUSE OF THIS MISSILE IMPACT |
| PROTECTION OF EXTERIOR GLAZING IS |
| REQUIRED. SEE 2001 FBC 1606.1.4. |
| |
| 15) SUBMIT THE MANUFACTURER'S |
| SPECS.(LISTING) AND PRODUCT APPROVALS |
| FOR THE FIRE RATED GLASS BLOCK. |
| |
| 16) THE INTERNAL PRESSURE COEFFICENT ON |
| SHEET S7 IS POSITIVE AND NEGATIVE + OR |
| -0.18. PLEASE CORRECT. |
| |
| 17) MANY OF THE FULL LOUVERED DOORS ARE |
| LOCATED IN FIRE RATED WALLS AND OPEN |
| ONTO THE EGRESS CORRIDORS. THESE DOORS |
| ARE REQUIRED TO BE FIRE RATED. I DO NOT |
| BELIEVE THAT THERE ARE ANY FIRE RATED |
| FULL LOUVERED DOORS AVAILABLE. SUBMIT |
| MANUFACTURER'S SPECS. AND LISTING FOR |
| THE DOORS YOU WILL BE USING. |
| |
| 18) THE PRODCUCT APPROVALS SUBMITTED FOR |
| THE FULL LOUVERED DOORS REQUIRES A |
| HURRICANE PROTECTION SYSTEM FOR THEM. |
| SUBMIT A STATE PRODUCT APPROVAL, A KEY |
| PLAN, AN INSTALLATION SCHEDULE AND A |
| PRESTORM PREPARATION PLAN FOR BUILDING |
| OFFICAL APPROVAL FOR THE STORM PANELS |
| FOR THESE DOORS. |
| |
| 19) SPECIFY THE LOCATIONS WHERE THE |
| THERMA-TRU/ BENCHMARK DOORS WILL BE |
| INSTALLED. THESE DOORS DO NOT HAVE A |
| FIRE RATING. |
| |
| 20) SUBMIT STATE PRODUCT APPROVALS FOR |
| THE ROOFING MATERIAL THAT WILL BE USED |
| ON THE FLAT ROOF AREAS OF THE BUILDING. |
| INDICATE THE SYSTEM LISTED IN THE |
| PRODUCT APPROVAL THAT WILL BE USED. MAKE |
| SURE THAT THE DESIGN PRESSURES FOR THE |
| SELECTED PRODUCT ARE ADEQUATE. |
| |
| 21) THE WINDOWS (E) LOCATED IN THE ONE |
| HOUR FIRE RATED PARTIONS ON SHEET A4.0.8 |
| ARE REQUIRED TO BE 45 MIN. FIRE |
| PROTECTION RATED PER FBC 705.1.3.6.2. |
| THE SCHEDULE LISTS 20 MIN. RATED. PLEASE |
| CORRECT. |
| |
| 22)A SEPARATE PERMIT WILL BE REQUIRED |
| FOR SITE AMENITIES. A SITE PLAN SHOWING |
| ACCESSIBLE ROUTES TO ALL BUILDINGS, |
| AMENITIES, PARKING AND TO THE PUBLIC WAY |
| AS REQUIRED BY FBC 11-4.1.2, THE FAIR |
| HOUSING ACCESSIBILITY GUIDELINES AND |
| ANSI 4.3. SHOW CURB RAMPS, SIDE WALK |
| WIDTHS, SIGNAGE, DETECTABLE WARNINGS, |
| CROSSWALKS,ETC. DETAILS OF THE COMMON |
| TRASH PICK-UP AREA, GAZEBOS AND TOT LOT |
| MUST SHOW COMPLIANCE WITH ADA |
| REQUIREMENTS. |
| |
| 23) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 24) ADDITIONAL COMMENTS MAY RESULT FROM |
| RESPONSES TO THESE ISSUES. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)805-6714 |
| |
| |
| |
| |
| |
| |
| |