2006-05-22 00:00:00PERMIT NUMBER: 05090156
 ADDRESS: 3701 N MILITARY TRAIL
 CONTRACTOR: TOWN AND COUNTRY HOMES
 FOUR STORY R2 WITH PARKING GARAGE
 TYPE II SPRINKLERED (13R SYSTEM)
 CODE EDITION: 2001 FBC
 SECOND REVIEW
 ---------------------------------------
 DENIED
  
  
 1)WPB AMENDMENT 105.13.6. W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A
 SPECIAL INSPECTOR AS REQUIRED BY S.
 553.79(5) FLORIDA STATUTES TO THE MIN-
 IMUM INSPECTIONS REQUIRED BY THIS CODE.
 CONTACT HAROLD PISKURA MANAGER OF THE
 SPECIAL INSPECTOR PROGRAM AT (561)
 805-6711 FOR FURTHER INFORMATION BEFORE
 THE PERMIT MAY BE ISSUED.
  
 2) CONDOMINIUM V APARTMENTS.IF THE
 DWELLING UNITS ARE TO BE SOLD AS
 CONDOMINIUMS, A 'DECLARATION OF
 CONDOMINIUM' SHALL BE SUBMITTED TO THE
 STATE FOR APPROVAL, AND THEN RECORDED
 WITH THE CLERK OF THE COUNTY COURT.A
 RECORDED COPY SHALL BE SUBMITTED TO THE
 CITY FOR RECORDS, ADDRESSING PURPOSES,
 AND TO PALM BEACH COUNTY PROPERTY
 APPRAISER'S OFFICE PRIOR TO C.O.
 RECORDED COPY OF CONDOMINIUM DOCUMENTS
 RECEIVED.
  
 3) ALL THREE (3) COPIES OF THE
 SUBSURFACE SOIL REPORTS, OTHER REPORTS,
 CALCULATIONS AND DRAWINGS PREPARED BY A
 FLORIDA REGISTERED ARCHITECT OR ENGINEER
 ARE REQUIRED TO BE SIGNED AND SEALED.
  
 4) SUBMIT (3) SETS OF ENGINEERED LAYOUTS
 AND TRUSS DRAWINGS FOR THE METAL TRUSSES
 THAT HAVE BEEN REVIEWED AND APPROVED BY
 THE DESIGNER OF RECORD FOR THE
 STRUCTURE.
  
 5) REVISED DETAILS #9 THRU #13 ON SHEET
 A-8.3.1 AND #2, #4 ON A-8.3.2 SPECIFY
 WOOD TRUSSES AND DO NOT SPECIFY FIRE
 TREATED PLYWOOD. THIS STRUCTURE IS
 SPECIFIED AS TYPE II CONSTRUCTION AND
 DOES NOT ALLOW COMBUSTIBLE MATERIALS AT
 THIS LOCATION. PLEASE CORRECT.
  
 6) SPECIFY THE ATTACHMENT SPACING AND
 FASTENERS FOR THE FIRETREATED PLYWOOD
 SHEATHING TO THE METAL TRUSSES.
  
 7) SUBMIT (3) SETS OF ENGINEERED SHOP
 DRAWINGS AND LAYOUTS FOR THE PRECAST
 SYSTEM FOR THE PARKING GARAGE.(PRIOR TO
 CONSTRUCTION)
  
 8) THE CORRIDOR BETWEEN THE FITNESS
 CENTER AND THE BATH ROOMS IS A DEAD END
 HALLWAY THAT EXCEEDS TWENTY FEET IN
 LENGTH WHICH IS PROHIBITED BY FBC
 1005.2.
  
 9) 2001 FBC 903.7.6 REQUIRES GROUP R2
 OCCUPANCIES THREE OR MORE STORIES IN
 HEIGHT TO BE PROVIDED THROUGHOUT WITH AN
 APPROVED AUTOMATIC SPRINKLER SYSTEM.
 EXCEPTION (2) ALLOWS AN AUTOMATIC
 SPRINKLER SYSTEM COMPLYING WITH NFPA 13R
 FOR BUILDINGS NOT EXCEEDING FOUR STORIES
 IN HEIGHT PROVIDED THE AUTOMATIC
 SPRINKLER SYSTEM SHALL NOT BE CONSIDERED
 AS AN ALTERNATE TO OTHER REQUIREMENTS OF
 THE CODE. (SEE 903.2) FBC 903.2 STATES
 THAT AUTOMATIC SPRINKLER SYSTEMS
 INSTALLED IN LIEU OF OR AS AN ALTERNATE
 TO OTHER REQUIREMENTS, AS PERMITTED BY
 THIS CODE, SHALL BE CONSIDERED REQUIRED
 SYSTEMS AND SHALL COMPLY WITH NFPA 13.
 THIS MEANS THAT IN ORDER TO APPLY THE
 REDUCTION IN CORRIDOR FIRE RATING
 ALLOWED BY TABLE 704.2.4 TO 1/2 HOUR FOR
 FULLY SPRINKLERED BUILDINGS OR THE
 INCREASED TRAVEL DISTANCE OF 325' IN
 TABLE 1004 FOR SPRINKLERED BUILDINGS AN
 NFPA 13 SPRINKLER SYSTEM IS REQUIRED.
  
 10) THE BILLARD ROOM IS AN ASSEMBLY
 OCCUPANCY WHICH REQUIRES A TWO HOUR
 TENANT FIRE SEPARATION. SEE FBC 704.1.1
 HOWEVER, FBC 704.1.2.3 ALLOWS A ONE HOUR
 OCCUPANCY SEPARATION.
  
 11) ALL FIRE RATED DOORS ARE REQUIRED TO
 HAVE APPROVED CLOSERS OR BE SELF
 CLOSING. SPECIFY CLOSERS FOR ALL RATED
 DOORS PER FBC 705.1.3.2.3. SPECIFY IN
 THE DOOR SCHEDULE ON A4.0.8 THAT DOOR #4
 IS REQUIRED TO HAVE APPROVED CLOSERS.
  
 12) A VERTICAL SECTION THROUGH THE TRASH
 CHUTE IS INDICATED AS 5 ON A4.0.10 THIS
 IS INCORRECT AS IT IS LOCATED ON DETAIL
 5 ON A4.0.10. PLEASE CORRECT.
  
 13) THE TRASH CHUTE SECTION SHOWN ON
 SHEET A8.1.4 IS INCORRECTLY LABELED AS 4
 ON A4.0.7. PLEASE CORRECT.
  
 14) PLEASE REVISE NEW NOTES ON A8.2.1
 AND A8.2.2 WHICH REFER TO THE HIGH
 VELOCITY HURRICANE ZONES AS REQUIRING
 IMPACT PROTECTION. THE CITY OF WEST PALM
 BEACH IS NOT IN THE HIGH VELOCITY
 HURRICANE ZONE, HOWEVER, WE ARE LOCATED
 IN THE WIND BOURNE DEBRIS REGION AND
 BECAUSE OF THIS MISSILE IMPACT
 PROTECTION OF EXTERIOR GLAZING IS
 REQUIRED. SEE 2001 FBC 1606.1.4.
  
 15) SUBMIT THE MANUFACTURER'S
 SPECS.(LISTING) AND PRODUCT APPROVALS
 FOR THE FIRE RATED GLASS BLOCK.
  
 16) THE INTERNAL PRESSURE COEFFICENT ON
 SHEET S7 IS POSITIVE AND NEGATIVE + OR
 -0.18. PLEASE CORRECT.
  
 17) MANY OF THE FULL LOUVERED DOORS ARE
 LOCATED IN FIRE RATED WALLS AND OPEN
 ONTO THE EGRESS CORRIDORS. THESE DOORS
 ARE REQUIRED TO BE FIRE RATED. I DO NOT
 BELIEVE THAT THERE ARE ANY FIRE RATED
 FULL LOUVERED DOORS AVAILABLE. SUBMIT
 MANUFACTURER'S SPECS. AND LISTING FOR
 THE DOORS YOU WILL BE USING.
  
 18) THE PRODCUCT APPROVALS SUBMITTED FOR
 THE FULL LOUVERED DOORS REQUIRES A
 HURRICANE PROTECTION SYSTEM FOR THEM.
 SUBMIT A STATE PRODUCT APPROVAL, A KEY
 PLAN, AN INSTALLATION SCHEDULE AND A
 PRESTORM PREPARATION PLAN FOR BUILDING
 OFFICAL APPROVAL FOR THE STORM PANELS
 FOR THESE DOORS.
  
 19) SPECIFY THE LOCATIONS WHERE THE
 THERMA-TRU/ BENCHMARK DOORS WILL BE
 INSTALLED. THESE DOORS DO NOT HAVE A
 FIRE RATING.
  
 20) SUBMIT STATE PRODUCT APPROVALS FOR
 THE ROOFING MATERIAL THAT WILL BE USED
 ON THE FLAT ROOF AREAS OF THE BUILDING.
 INDICATE THE SYSTEM LISTED IN THE
 PRODUCT APPROVAL THAT WILL BE USED. MAKE
 SURE THAT THE DESIGN PRESSURES FOR THE
 SELECTED PRODUCT ARE ADEQUATE.
  
 21) THE WINDOWS (E) LOCATED IN THE ONE
 HOUR FIRE RATED PARTIONS ON SHEET A4.0.8
 ARE REQUIRED TO BE 45 MIN. FIRE
 PROTECTION RATED PER FBC 705.1.3.6.2.
 THE SCHEDULE LISTS 20 MIN. RATED. PLEASE
 CORRECT.
  
 22)A SEPARATE PERMIT WILL BE REQUIRED
 FOR SITE AMENITIES. A SITE PLAN SHOWING
 ACCESSIBLE ROUTES TO ALL BUILDINGS,
 AMENITIES, PARKING AND TO THE PUBLIC WAY
 AS REQUIRED BY FBC 11-4.1.2, THE FAIR
 HOUSING ACCESSIBILITY GUIDELINES AND
 ANSI 4.3. SHOW CURB RAMPS, SIDE WALK
 WIDTHS, SIGNAGE, DETECTABLE WARNINGS,
 CROSSWALKS,ETC. DETAILS OF THE COMMON
 TRASH PICK-UP AREA, GAZEBOS AND TOT LOT
 MUST SHOW COMPLIANCE WITH ADA
 REQUIREMENTS.
  
 23) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 24) ADDITIONAL COMMENTS MAY RESULT FROM
 RESPONSES TO THESE ISSUES.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  
  
  
  
  