2005-11-12 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 BUILDING
 FBC-2001 CHAPTER 11
 FHA-98 DESIGN MANUAL
  
 1. SHT A2.0.5 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS. SHOW
 SQUARE FEET FOR EACH AREA, PLUS 1/2 AREA
 OF ALL VERTICAL WALLS, INCLUDING
 PARAPETS, AS WELL AS THE AREA OF ALL
 ROOFS THAT DRAIN ONTO EACH AREA FROM
 ABOVE ADDED IN CALCULATIONS. SECTIONS
 1106 & 1107 AND ALL SUBSECTIONS.
 2. A2.1.13 SUBMIT CALCULATIONS FOR THE
 PRIMARY AND SECONDARY ROOF DRAINS FOR
 THE GARAGE. (SEE COMMENT #1 FOR ALL
 INFORMATION REQUIRED IN CALCULATIONS).
 SECTIONS 1106 & 1107.
 3. SHTS A4.0.2, A4.0.2A, A4.0.3,
 A4.0.3A, A4.0.4, & A4.0.4A, NO SHOWER
 BATH ELEVATIONS FOR W/C SHOWN. W/C TO BE
 18" OFF WALL TO CENTER OF FIXTURE. LAV
 TO BE 34" TO FLOOD RIM LEVEL. PAGES 7.43
 AND 7.52 FHA DESIGN MANUAL. SHTS A4.0.7,
 & A4.0.7A W/C TO BE 18" OFF WALL TO
 CENTER OF FIXTURE. (DETAIL E).
 4. SHT A4.0.8 SUBMIT CALCULATIONS FOR
 MINIMUM FACILITIES PER TABLES 1003.1
 BLDG. AND 403.1 PLMG. SHOW SF OF EACH
 COMMON AREA & INDICATE THE OCCUPANCY AND
 OCCUPANCY LOAD OF EACH AREA. ALSO
 INDICATE ROOM DESIGNATION ON PLANS.
 SECTION 104.2.1.
 5. SHT A4.0.8 KITCHEN SINK SHALL COMPLY
 WITH SECTION 11-4.24 AND ALL
 SUBSECTIONS. SUBMIT A DETAIL. FORWARD
 APPROACH CLEAR FLOOR SPACE REQUIRED.
 6. SHT A4.0.10 DETAIL #5, BACKFLOW
 PROTECTION IS REQUIRED FOR THE TRASH
 CHUTE WASHDOWN. SECTION 608. INDICATE
 METHOD OF PROTECTION.
 7. SHT A8.3.1 DETAIL #2 OVERFLOW SCUPPER
 DETAIL, INDICATE HEIGHT & WIDTH OF
 SCUPPER OPENING AND INDICATE THE
 MEASUREMENT ABOVE THE ROOF TO THE FLOW
 LINE AS REQUIRED IN SECTION 1503.4.2.
 8. SHT A8.3.2 DETAIL #5 PRIMARY ROOF
 SCUPPER THRU MANSARD ROOF. SHOW THIS
 SCUPPER AS AN OVERFLOW SCUPPER AND SHOW
 AS REQUIRED PER SECTION 1503.4.2.
 SCUPPER SHALL BE 2" TO 4" ABOVE ROOF TO
 FLOW LINE. PLEASE CLARIFY.
 9. SHT A8.3.2 DETAIL #4 SHT A2.0.5 DOES
 NOT INDICATE WHERE THIS OVERFLOW SCUPPER
 WILL BE LOCATED/USED. PLEASE CLARIFY
 SECTION 104.2.1.
 10. SHT P0.1 WATER HEATER SCHED/DETAIL,
 THERMAL EXPANSION CONTROL REQUIRED PER
 SECTION 607.3.2. PLEASE INDICATE METHOD.
 11. SHT P2.1.1 4" RWL (800SF) UNIT "A" &
 4" RWL (900SF) UNIT "C" ARE NOT
 CONNECTED TO THE BLDG STORM DRAIN.
 SECTION 104.2.1.
 12. SHT P2.1.1 CLEANOUTS ARE REQUIRED IN
 THE BUILDING SANITARY DRAIN MAX. 100'
 AND IN ALL CHANGE OF DIRECTION GREATER
 THAN 45 DEGREES. SECTIONS 708.3.1 AND
 708.3.3.
 13. SHT P2.1.2 4" RWL (815SF) UNIT C NOT
 CONNECTED TO BLDG STORM DRAIN. SANT.
 RISERS S/C4 & S/C2 NOT CONNECTED TO BLDG
 SANT. DRAIN. PLEASE CLARIFY. SECTION
 104.2.1.
 14. SHT P2.1.4 3/4" COLD WATER SUPPLY TO
 FOUNTAIN SHALL HAVE BACKFLOW PROTECTION.
 SECTION 608. PLEASE INDICATE METHOD.
 15. SHT P2.4.1 ROOF DRAIN, 4 ROOF DRAINS
 SHOW NO DRAIN SIZE OF SF. 2 ROOF DRAINS
 ARE SHOWN IN WRONG LOCATIONS. PLEASE
 CLARIFY. SECTION 104.2.1.
 16. SHT P2.4.2 ROOF DRAINS, 1 ROOF DRAIN
 SHOWS NO DRAIN SIZE OF SF. 1 ROOF DRAIN
 SHOWN IN THE WRONG LOCATION. PLEASE
 CLARIFY. SECTION 104.2.1.
 17. SHT PR.3.3 INSTA HOT WATER HEATER.
 SUBMIT MANUF. SPECIFICATION FOR
 APPROVAL. SHALL BE LISTED. SECTION 303.4
 18. SHT P5.2 RISER S/E4 MAX. 4FU ON 2"
 WET VENT. TABLE 909.3.
 19. SHTS P5.3 & P5.4 SANT. ISOMETRIC
 SHOW DFU'S AS THEY ACCUMULATE IN THE
 SYSTEM. SECTION 104.2.1 & TABLE 710.1(1)
 20. SHT P6.1 DOMESTIC WATER ISOMETRIC
 RISER DIAGRAM, WATER HAMMER ARRESTORS
 SHALL BE LOCATED NEAR THE FIXTURE IN AN
 "EFFECTIVE RANGE", NOT IN THE CEILING AS
 SHOWN. PDI-WH 201 AND MANUF.
 INSTALLATION INSTRUCTIONS.
 21. SHT P6.2 COMMON AREA DOMESTIC WATER
 ISOMETRIC RISER DIAGRAM, SEE PREVIOUS
 COMMENT.
 22. SUBMIT A STORM RISER DIAGRAM
 ISOMETRIC FOR THE BLDG. STORM DRAIN
 SYSTEM. SHOW ALL PIPE SIZES, RISER
 CONNECTION LOCATION, AND SF AS THEY
 ACCUMULATE IN THE SYSTEM. SECTIONS
 104.2.1 AND 104.3.1.1.
 23. SUBMIT STORM RISER DIAGRAMS FOR EACH
 RWL. SHOW ALL PIPE SIZES AND SF FOR EACH
 RISER. SECTIONS 104.2.1 & 104.3.1.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  