Date |
Text |
2005-10-18 00:00:00 | DENIED: *********2001 FBC********* |
| 2 FOUR STORY CONDO'S W/ATTACHED GARAGE |
| |
| 1.PLAN SHEET M4.1, PLAN INDICATES |
| RETURN AIR PLENUM.PER 2001 |
| FBC(M)601.3, EXHAUST DUCTS & VENTING |
| SYSTEMS SHALL NOT EXTEND INTO OR PASS |
| THROUGH PLENUMS. |
| |
| 2.PLAN SHEET M2.1.2, PLEASE CLARIFY |
| WHAT THE SQUARES WITH THE ARROWS THAT |
| ARE NOT IDENTIFIED ON THE LEGEND LOCATED |
| ON M2.1.1. |
| |
| 3.PLAN SHEET M2.3.2 REFERENCES M4.4 |
| FOR VENTILATION DETAILS.IT APPEARS THE |
| EXHAUST IS TERMINATING ONTO THE WALKWAY. |
| PER 2001 FBC(M)401.5.2, EXHAUST OPENINGS |
| SHALL NOT BE DIRECTED ONTO WALKWAYS. |
| |
| 4.PLAN SHEET M3.1 SHOWS DEF-7 |
| TERMINATING IN FRONT OF A DOOR TO THE |
| STAIRWELL.TERMINATION SHALL BE IN A |
| LOCATION WHERE IT WILL NOT CREATE A |
| NUISANCE & PRODUCTS OF COMBUSTION WILL |
| NOT INFILTRATE INTO THE STAIRWELL.2001 |
| FBC(M)401.5.2 & 401.5.1. |
| |
| 5.DRYER SHAFTS SHALL HAVE SPRINKLERS |
| IN ACCORDANCE WITH NFPA 13 SECTION |
| 8.14.2.2.1 & 8.14.2.2.2. |
| |
| 6.PLAN SHEET M4.4 & M4.5 INDICATE AIR |
| MAKE-UP WITHIN 10 FT OF THE EXHAUST. |
| PLEASE PROVIDE VERTICAL SEPARATION FROM |
| THE TOP OF THE AIR MAKE-UP TO THE BOTTOM |
| OF THE EXHAUST.PLEASE NOTE, EXHAUST |
| SHALL TERMINATE AS NOT TO BE DRAWN IN BY |
| THE VENTILATION SYSTEM 2001 FBC 501.3. |
| |