2005-10-04 00:00:00MARVILLA
  
 4-STORY CONDO BLDGS W/ PARKING GARAGES.
  
 *********** UNSAT **********
  
  
 1)NOTE: PLEASE SEE PLANS ARE TO
 REFERENCE THE 2002 NEC AS ADOPTED BY THE
 STATE OF FLORIDA.(JULY 1ST, 2003)
 PLEASE ALSO SEE NOTES FOR PLANS WHICH
 INDICATE LOCAL AMENDMENTS PER CITY OF
 BOYNTON BEACH. PLEASE SEE NOTE WOULD
 REFERENCE LOCAL AMENDMENTS PER CITY OF
 WEST PALM BEACH.
  
 2)NOTE: PLEASE PROVIDE A DETAIL FOR
 CURBING REQUIRED AROUND BUS-DUCT ON
 FLOOR PENETRATIONS WHERE A VERTICAL
 RISER PENETRATES TWO OR MORE DRY FLOORS,
 A MINIMUM 100 MM (4 IN.) HIGH CURB SHALL
 BE INSTALLED AROUND ALL FLOOR OPENINGS
 FOR RISER BUSWAYS TO PREVENT LIQUIDS
 FROM ENTERING THE OPENING. PER 368.6
  
 3)NOTE: PLEASE PROVIDE BATTERY BACK UP
 LIGHT FIXTURES IN ALL ELECTRICAL ROOMS,
 ELEVATOR EQUIPMENT ROOMS AND FIRE PUMP
 RM.
 THIS IS REQUIRED PER FIRE MARSHALS
 OFFICE AND AHJ FOR LIGHTING WHICH BE
 REQUIRED UNDER NFPA-101 7.8,7.9.
  
 4)NOTE: PLEASE PROVIDE PHOTOMETRICS FOR
 STAIR/CORRIDOR AREAS FOR EGRESS TO THE
 PUBLIC RIGHT OF WAY. PLEASE SEE 2003
 101, 7.8 AND 7.9, WHICH REQUIRES 10FT
 CANDLES FOR STAIR AREAS AND 1FT FOR
 CORRIDOR.
 7.8.1.3,7.9.2.1
  
 5)NOTE: PLEASE SEE MISSING CIRCUITING
 FOR FRIG IN UNIT "A".
  
 6)NOTE: PLEASE PROVIDE DETAIL FOR ROOF
 TOP LT POLES AND FIXTURES. PLEASE
 PROVIDE WIND LOAD CALCULATIONS FOR
 REVIEW. THIS IS REQUIRED AT THIS TIME
 FOR FIXTURES AND POLES.
 CALCULATIONS WILL BE REVIEWED BY THE
 BLDG REVIEWER FOR CODE COMPLIANCE OF FBC
 140 MPH WIND LOADS.
  
 7)NOTE: PLEASE SUBMIT A COMPLETED
 LIGHTING FIXTURE SCHEDULE TO CORRELATE
 WITH FIXTURES AS SHOWN ON PLANS.
 PLEASE ALSO SEE COMMON AREAS WHERE
 FIXTURES DO NOT INDICATE WHAT TYPE ETC.
 RECREATION AREA, ROOF TOP ETC.
  
 8)NOTE: PLEASE MAKE REFERENCE/ NOTES
 PERTAINING TO ALL THE ELECTRICAL
 REQUIREMENTS FOR ELECTRICAL DEVICES
 UNDER FAIR HOUSING ACT REGULATIONS, CFR
 24 100.205.
  
 9)NOTE: PLEASE SEE 2002 NFPA-72 11.8.3.5
 FOR SMOKE DETECTOR PLACEMENT. PLEASE
 KNOW ALL SD'S ARE REQUIRED TO BE WITH-IN
 12" OF A CEILINGIN FALT CEILING
 INSTALLATIONS. PLEASE SEE SD'S WHICH
 SEEM TO BE LOCATED AT AREAS OF SOFFIT
 ETC SHALL BE MOVED TO AREAS WHERE
 CEILINGS WITH HIGHEST POINT.
 IF SD'S ARE WALL MOUNTED, THEY ARE STILL
 REQUIRED TO BE WITH IN 12" OF CEILING
 BUT NO CLOSER THAN 4".
 PLEASE ALSO PLACE NOTE ON PLANS FOR SD
 PALCEMENT PER ABOVE WITH RESPECT TO SD'S
 BEING LOCATE NO CLOSER THAN 3' OF BATH
 AND KIRTCHEN DOORS AND NO CLOSER THAN
 20' OF COOKING APPLIANCES, (UNLESS
 MEETING EXCEPTIONS AS SET FORTH) AS
 LISTED IN NFPA-72
  
 10)NOTE: PLEASE SEE SOME MISSING RECEPTS
 ALONG KITCHEN COUNTERSPACES AND
 PENINSULARS.
 210.52C1,210.52C3
 PLEASE SEE REDLINED PLANS FOR LOCATIONS.
 UNIT, B
  
 11)NOTE: PLEASE SEE SOME RECEPTS MISSING
 PER 210.52, 2' OF WALL SPACE.
 ONCE AGAIN, SEE REDLINED PLANS FOR AREAS
 AS NOTED. UNIT , E, A
  
 12)NOTE: PLEASE LIST ALL ARC FAULT
 PROTECTED CIRCUITS AS REQUIRED UNDER THE
 2002 NEC 210.12. THIS REQUIRES ALL
 "OUTLETS" TO BE AF PROTECTED. THIS
 INCLUDES SD'S, LTS, RECEPTS , FANS ETC.
  
 13)NOTE: PLEASE SEE UNIT "A" WHICH SHOWS
 INDIVIDUALS WASHER AND DRYER, HOWEVER
 PANEL SCHEDULE SHOWS THIS AS A STACKABLE
 UNIT??
 PLEASE SEE "L1A WHICH SHOWS CIRCUIT #24
 AS A SPARE, YET ON PLANS THIS IS SHOWN
 FOR ABOVE.
 PLEASE CORRELATE.
  
 14)NOTE: PLEASE PROVIDE "DINING RM/AREA"
  
 DESIGNATIONS ON UNITS "A" AND "E".
 210.52B.
  
 15)NOTE: PLEASE PROVIDE ROOM/ AREA
 DESIGNATIONS ON COMMON AREAS PLANS.
 PLEASE SEE ROOMS ETC NOT LABLED.
 PLEASE SEE ELECTRICAL PLANS DO NOT
 INDICATE "POOL EQUIPMENT " ROOM ETC.
  
 16)NOTE: PLEASE SEE 424.3B WHICH
 REQUIRES ALL OVERCURRENT PROTECTION FOR
 AHU'S HEAT TO BE A MIN OF 125%.
 PLEASE SEE THESE AS REDLINED ON PLANS.
 PLEASE ALSO REVISE MIN AWG PER 310.16
 ONCE OCP HAS BEEN ADJUSTED.
 PLEASE KNOW, MOST OCP IS 150% MAX,
 HOWEVER WHEN A AMPERAGE DOES NOT
 CORRESPONED TO A COMMON OCP DEVICE AS
 LISTED IN 240.6, GOING UP TO THE NEXT
 HIGHER OCP IS PERMITTED.
  
 17)NOTE: PLEASE SEE MANY OF THE UNITS AS
 LISTED ON HOUSE PANELS ALSO NEED TO BE
 ADJUSTED.
 PLEASE SEE L2B
 AHU#10, SHOWS 11KW ON A 2P-30A WITH #10
 AWG.
 AHU #11 LISTED TWICE, SHOWS 11KW ON
 2P-45A WITH #8.
 AHU#11 LISTED AGAIN, 4.8KW WITHAND 30A
 OCP THIS ONE IS OK.
 PLEASE SEE AHU#10 IS LISTED TWICE ALSO.
 PLEASE SEE AHU #6 ON LRB.
 PLEASE SEE AHU #7 ON LRB.
 BOTH WITH THE SAME COMMENTS AS LISTED
 ABOVE.
 PLEASE ADJUST.424.3B,310.16
  
 18)NOTE: PLEASE SEE MIN OCPFOR WATER
 HEATER UNITS, SHALL BE A MIN OF 125% AND
 A MAX OF 150%.
 PLEASE SEE 6KW SHOWN ON A 2P35.
 422.13,422.11E3
  
 19)NOTE:PLEASE SHOW ALL CONTINUOUS LOADS
 AT 125%. PLEASE SEE THIS IS FOR LOADS
 DEDICATED TO HOUSE PANELS, POOL PUMPS,
 ANY POOL HEAT PUMPS, LIGHTING , LARGEST
 MOTOR STEC.
 215.3,230.42 ETC.
  
 20)NOTE: PLEASE BE SURE MAINS 1A,2A,1B,
 2B, INDICATE THAT THE MCB CONTAINS A
 MANUAL MEANS OF DISCONNECT LOCATED ON
 THE OOUTSIDE OF THE EQUIPMENT AND RATED
 FOR THE LOAD SERVED. 230.76 AND 230.79
 PLEASE SEE PLANS ONLY INDUCATE THESE AS
 BEING SHUNT TRIP TYPE?
 PLEASE ALSO MAKE NOTES FOR MAINS DPA AND
 DPB.
  
 21)NOTE: PLEASE SUBMIT ALL MANUFACTURE
 SPECS/CUT SHEETS FOR FIRE PUMP AND FIRE
 PUMP CONTROLLER.
 PLEASE BE SURE NOTES FOR LOCKED ROTOR
 AND MANUAL MEANS OF DISCONNECT IS
 LOCATED ON PLANS.
 PLEASE SEE 695.4B1,
 NFPA-20 10.4.2.1.1,10.4.2.2 ETC.
 PLEASE SEE THIS INFORMATION IS REQUIRED
 AT THIS TIME EVEN IF FIRE PUMP/
 CONTROLLER IS PERMITTED UNDER FIRE
 SPRINKLER PERMIT.
  
 22)NOTE: PLEASE INDICATE THE EQUIPMENT
 GROUNDING CONDUCTORS ON RISER FEEDERS TO
 "TAP-BOXES".
 250.110,250.122
  
 23)NOTE: PLEASE SEE FEEDERS FROM MAINS
 1A,2A,1B,AND 2B TO "TAP BOXES
 COULD NOT BE LOCATED??
 PLEASE SEE, 215.5,310.16
  
 24)NOTE: PLEASE CORRELATE BUS RISER
 DETAILS AND NOTES. PLEASE SEE REDLINED
 PLANS, AS THERE ARE 2- "BUSWAY #2 SHOWN,
 AND NOTES FOR FEED TO MAIN 2B IS LISTED
 TWICE AND ONE IS CROSSED THROUGH??
 PLEASE SEE REDLINED PLANS AND CORRELATE.
 215.5
  
 25)NOTE: PLEASE SEE FEEDERS FROM "DPA"
 TO PANEL "L4A" ARE SHOWN AS 3/0'S,
 HOWEVER OCP ON DPA IS 400A'S. PLEASE
 CORRELATE AND ADJUST. 240.4,310.16
  
 26)NOTE: PLEASE SPECIFY OF PANEL "L4A"
 HAS "FEED-THRU " LUGS OR DOES THIS PANEL
 CONTAIN OCP FEEDING THRU TO PANEL
 "L4AA".?
 215.5
  
 27)NOTE: PLEASE SEE ELEVATOR CIRCUITS AS
 LISTED ON DPA #5 AND #6 SHOWS 4-POLES?
 FOR A 3-POLE BRKR?
 PLEASE ALSO SEE DPB #5 AND #6 AS THIS
 SHOWS THE SAME THING.
 215.5
  
 28)NOTE: PLEASE SEE "L1BA" WHICH IS
 SHOWN AS A 100A PANEL YET IS BEING FED
 WITH A 225A BRKR FROM DPB.
  
 29)NOTE: PLEASE SEE PANEL "LPB" WHICH IS
 SHOWN AS 200A PANEL, HOWEVER PANEL IS
 BEING FED WITH A 225A BRKR FROM "DPB".
 PLEASE CORRLEATE.
  
 30)NOTE: PLEASE SEE 620.23,620.24 WHICH
 REQUIRES DEDICATED CIRCUITS FOR ELEVATOR
 PIT LTS AND RECEPTS. THIS CIRCUIT MAY
 NOT FEED ANY OTHER LTS AND RECEPTS.
 THESE SHALL ALSO BE DEDICATE TO EACH
 ELEVATOR/PIT.
 PLEASE SEE CIRCUITS FOR ELEVATOR
 EQUIPMENT ROOMS SHALL ALSO BE DEDICATED
 AND MAY NOT FEED ANY OTHER ROOMS OR
 ELECTRICAL LIGHTING OR RECEPTS.
 PLEASE ALSO SEE PREVIOUS NOTE WHICH IS
 REQUIRING A BATTERY BACK-UP FIXTURE IN
 THESE ROOMS.
 PLEASE ALSO SEE 700.16D
  
 31)NOTE: PLEASE PROVIDE A NOTE ON SHEETS
 FOR ELECTRICAL/ ELEVATOR ROOMSWHICH
 SHOULD STATE ALL REQUIRED CLEARENCES PER
 110.26 SHALL BE MET FOR ALL ELECTRICAL
 EQUIPMENT. (OR WORDS TO THAT AFFECT).
 110.26
 THIS HAS BEEN AN ISSUE IN THIS
 JURISDICTION FOR MAINS/METER CENTERS FOR
 HEIGHT AND WIDTH OF EQUIPMENT.
  
 32)NOTE: PLEASE PLACE NOTE ON "ROOF-TOP"
 PLANS WHICH WILL STATE >
 "ANY LIGHTNING PROTECTION SYSTEMS WILL
 BE REQUIRED TO BE SUBMITTED UNDER A
 SEPARATE PERMIT AND PLANS."
 "ALL SYSTEMS SHALL MEET NFPA-780."
  
 33)NOTE: PLEASE SEE RISER DIAGRAM SEEMS
 TO SHOW ELEVATOR EQUIPMENT/ DISCONNECTS,
 ETC ON 2ND FLR, HOWEVER PLANS FOR ROOMS
 ON E7.1, APPEAR TO SHOW THIS EQUIPMENT
 LOCATED ON 1ST FLR??
  
 ** PLEASE KNOW, MANY OF THE ABOVE ITEMS
 HAVE BEENREDLINED ON PLANS FOR AREAS
 OF COMMENTS.
  
 **PLEASE SEE ALL COMMENTS FROM ALL OTHER
 TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
 PLEASE SEE FIRE REVIEW COMMENTS.
  
 ** PLEASE REMOVE ALL OLD/VOIDED SHEETS
 FROM SETS AND ONLY INSERT NEW REVISED
 SHEETS INTO COMPLETE SETS FOR REVIEW AND
 STAMPING. ONE SET OF ALL OL/VOIDED
 SHEETS SHOULD BE SUBMITTED FOR
 REFERENCE.
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DONOT HESITATE IN CONTACTING
 THIS OFFICE.
  