2005-10-04 00:00:00 | MARVILLA |
| |
| 4-STORY CONDO BLDGS W/ PARKING GARAGES. |
| |
| *********** UNSAT ********** |
| |
| |
| 1)NOTE: PLEASE SEE PLANS ARE TO |
| REFERENCE THE 2002 NEC AS ADOPTED BY THE |
| STATE OF FLORIDA.(JULY 1ST, 2003) |
| PLEASE ALSO SEE NOTES FOR PLANS WHICH |
| INDICATE LOCAL AMENDMENTS PER CITY OF |
| BOYNTON BEACH. PLEASE SEE NOTE WOULD |
| REFERENCE LOCAL AMENDMENTS PER CITY OF |
| WEST PALM BEACH. |
| |
| 2)NOTE: PLEASE PROVIDE A DETAIL FOR |
| CURBING REQUIRED AROUND BUS-DUCT ON |
| FLOOR PENETRATIONS WHERE A VERTICAL |
| RISER PENETRATES TWO OR MORE DRY FLOORS, |
| A MINIMUM 100 MM (4 IN.) HIGH CURB SHALL |
| BE INSTALLED AROUND ALL FLOOR OPENINGS |
| FOR RISER BUSWAYS TO PREVENT LIQUIDS |
| FROM ENTERING THE OPENING. PER 368.6 |
| |
| 3)NOTE: PLEASE PROVIDE BATTERY BACK UP |
| LIGHT FIXTURES IN ALL ELECTRICAL ROOMS, |
| ELEVATOR EQUIPMENT ROOMS AND FIRE PUMP |
| RM. |
| THIS IS REQUIRED PER FIRE MARSHALS |
| OFFICE AND AHJ FOR LIGHTING WHICH BE |
| REQUIRED UNDER NFPA-101 7.8,7.9. |
| |
| 4)NOTE: PLEASE PROVIDE PHOTOMETRICS FOR |
| STAIR/CORRIDOR AREAS FOR EGRESS TO THE |
| PUBLIC RIGHT OF WAY. PLEASE SEE 2003 |
| 101, 7.8 AND 7.9, WHICH REQUIRES 10FT |
| CANDLES FOR STAIR AREAS AND 1FT FOR |
| CORRIDOR. |
| 7.8.1.3,7.9.2.1 |
| |
| 5)NOTE: PLEASE SEE MISSING CIRCUITING |
| FOR FRIG IN UNIT "A". |
| |
| 6)NOTE: PLEASE PROVIDE DETAIL FOR ROOF |
| TOP LT POLES AND FIXTURES. PLEASE |
| PROVIDE WIND LOAD CALCULATIONS FOR |
| REVIEW. THIS IS REQUIRED AT THIS TIME |
| FOR FIXTURES AND POLES. |
| CALCULATIONS WILL BE REVIEWED BY THE |
| BLDG REVIEWER FOR CODE COMPLIANCE OF FBC |
| 140 MPH WIND LOADS. |
| |
| 7)NOTE: PLEASE SUBMIT A COMPLETED |
| LIGHTING FIXTURE SCHEDULE TO CORRELATE |
| WITH FIXTURES AS SHOWN ON PLANS. |
| PLEASE ALSO SEE COMMON AREAS WHERE |
| FIXTURES DO NOT INDICATE WHAT TYPE ETC. |
| RECREATION AREA, ROOF TOP ETC. |
| |
| 8)NOTE: PLEASE MAKE REFERENCE/ NOTES |
| PERTAINING TO ALL THE ELECTRICAL |
| REQUIREMENTS FOR ELECTRICAL DEVICES |
| UNDER FAIR HOUSING ACT REGULATIONS, CFR |
| 24 100.205. |
| |
| 9)NOTE: PLEASE SEE 2002 NFPA-72 11.8.3.5 |
| FOR SMOKE DETECTOR PLACEMENT. PLEASE |
| KNOW ALL SD'S ARE REQUIRED TO BE WITH-IN |
| 12" OF A CEILINGIN FALT CEILING |
| INSTALLATIONS. PLEASE SEE SD'S WHICH |
| SEEM TO BE LOCATED AT AREAS OF SOFFIT |
| ETC SHALL BE MOVED TO AREAS WHERE |
| CEILINGS WITH HIGHEST POINT. |
| IF SD'S ARE WALL MOUNTED, THEY ARE STILL |
| REQUIRED TO BE WITH IN 12" OF CEILING |
| BUT NO CLOSER THAN 4". |
| PLEASE ALSO PLACE NOTE ON PLANS FOR SD |
| PALCEMENT PER ABOVE WITH RESPECT TO SD'S |
| BEING LOCATE NO CLOSER THAN 3' OF BATH |
| AND KIRTCHEN DOORS AND NO CLOSER THAN |
| 20' OF COOKING APPLIANCES, (UNLESS |
| MEETING EXCEPTIONS AS SET FORTH) AS |
| LISTED IN NFPA-72 |
| |
| 10)NOTE: PLEASE SEE SOME MISSING RECEPTS |
| ALONG KITCHEN COUNTERSPACES AND |
| PENINSULARS. |
| 210.52C1,210.52C3 |
| PLEASE SEE REDLINED PLANS FOR LOCATIONS. |
| UNIT, B |
| |
| 11)NOTE: PLEASE SEE SOME RECEPTS MISSING |
| PER 210.52, 2' OF WALL SPACE. |
| ONCE AGAIN, SEE REDLINED PLANS FOR AREAS |
| AS NOTED. UNIT , E, A |
| |
| 12)NOTE: PLEASE LIST ALL ARC FAULT |
| PROTECTED CIRCUITS AS REQUIRED UNDER THE |
| 2002 NEC 210.12. THIS REQUIRES ALL |
| "OUTLETS" TO BE AF PROTECTED. THIS |
| INCLUDES SD'S, LTS, RECEPTS , FANS ETC. |
| |
| 13)NOTE: PLEASE SEE UNIT "A" WHICH SHOWS |
| INDIVIDUALS WASHER AND DRYER, HOWEVER |
| PANEL SCHEDULE SHOWS THIS AS A STACKABLE |
| UNIT?? |
| PLEASE SEE "L1A WHICH SHOWS CIRCUIT #24 |
| AS A SPARE, YET ON PLANS THIS IS SHOWN |
| FOR ABOVE. |
| PLEASE CORRELATE. |
| |
| 14)NOTE: PLEASE PROVIDE "DINING RM/AREA" |
| |
| DESIGNATIONS ON UNITS "A" AND "E". |
| 210.52B. |
| |
| 15)NOTE: PLEASE PROVIDE ROOM/ AREA |
| DESIGNATIONS ON COMMON AREAS PLANS. |
| PLEASE SEE ROOMS ETC NOT LABLED. |
| PLEASE SEE ELECTRICAL PLANS DO NOT |
| INDICATE "POOL EQUIPMENT " ROOM ETC. |
| |
| 16)NOTE: PLEASE SEE 424.3B WHICH |
| REQUIRES ALL OVERCURRENT PROTECTION FOR |
| AHU'S HEAT TO BE A MIN OF 125%. |
| PLEASE SEE THESE AS REDLINED ON PLANS. |
| PLEASE ALSO REVISE MIN AWG PER 310.16 |
| ONCE OCP HAS BEEN ADJUSTED. |
| PLEASE KNOW, MOST OCP IS 150% MAX, |
| HOWEVER WHEN A AMPERAGE DOES NOT |
| CORRESPONED TO A COMMON OCP DEVICE AS |
| LISTED IN 240.6, GOING UP TO THE NEXT |
| HIGHER OCP IS PERMITTED. |
| |
| 17)NOTE: PLEASE SEE MANY OF THE UNITS AS |
| LISTED ON HOUSE PANELS ALSO NEED TO BE |
| ADJUSTED. |
| PLEASE SEE L2B |
| AHU#10, SHOWS 11KW ON A 2P-30A WITH #10 |
| AWG. |
| AHU #11 LISTED TWICE, SHOWS 11KW ON |
| 2P-45A WITH #8. |
| AHU#11 LISTED AGAIN, 4.8KW WITHAND 30A |
| OCP THIS ONE IS OK. |
| PLEASE SEE AHU#10 IS LISTED TWICE ALSO. |
| PLEASE SEE AHU #6 ON LRB. |
| PLEASE SEE AHU #7 ON LRB. |
| BOTH WITH THE SAME COMMENTS AS LISTED |
| ABOVE. |
| PLEASE ADJUST.424.3B,310.16 |
| |
| 18)NOTE: PLEASE SEE MIN OCPFOR WATER |
| HEATER UNITS, SHALL BE A MIN OF 125% AND |
| A MAX OF 150%. |
| PLEASE SEE 6KW SHOWN ON A 2P35. |
| 422.13,422.11E3 |
| |
| 19)NOTE:PLEASE SHOW ALL CONTINUOUS LOADS |
| AT 125%. PLEASE SEE THIS IS FOR LOADS |
| DEDICATED TO HOUSE PANELS, POOL PUMPS, |
| ANY POOL HEAT PUMPS, LIGHTING , LARGEST |
| MOTOR STEC. |
| 215.3,230.42 ETC. |
| |
| 20)NOTE: PLEASE BE SURE MAINS 1A,2A,1B, |
| 2B, INDICATE THAT THE MCB CONTAINS A |
| MANUAL MEANS OF DISCONNECT LOCATED ON |
| THE OOUTSIDE OF THE EQUIPMENT AND RATED |
| FOR THE LOAD SERVED. 230.76 AND 230.79 |
| PLEASE SEE PLANS ONLY INDUCATE THESE AS |
| BEING SHUNT TRIP TYPE? |
| PLEASE ALSO MAKE NOTES FOR MAINS DPA AND |
| DPB. |
| |
| 21)NOTE: PLEASE SUBMIT ALL MANUFACTURE |
| SPECS/CUT SHEETS FOR FIRE PUMP AND FIRE |
| PUMP CONTROLLER. |
| PLEASE BE SURE NOTES FOR LOCKED ROTOR |
| AND MANUAL MEANS OF DISCONNECT IS |
| LOCATED ON PLANS. |
| PLEASE SEE 695.4B1, |
| NFPA-20 10.4.2.1.1,10.4.2.2 ETC. |
| PLEASE SEE THIS INFORMATION IS REQUIRED |
| AT THIS TIME EVEN IF FIRE PUMP/ |
| CONTROLLER IS PERMITTED UNDER FIRE |
| SPRINKLER PERMIT. |
| |
| 22)NOTE: PLEASE INDICATE THE EQUIPMENT |
| GROUNDING CONDUCTORS ON RISER FEEDERS TO |
| "TAP-BOXES". |
| 250.110,250.122 |
| |
| 23)NOTE: PLEASE SEE FEEDERS FROM MAINS |
| 1A,2A,1B,AND 2B TO "TAP BOXES |
| COULD NOT BE LOCATED?? |
| PLEASE SEE, 215.5,310.16 |
| |
| 24)NOTE: PLEASE CORRELATE BUS RISER |
| DETAILS AND NOTES. PLEASE SEE REDLINED |
| PLANS, AS THERE ARE 2- "BUSWAY #2 SHOWN, |
| AND NOTES FOR FEED TO MAIN 2B IS LISTED |
| TWICE AND ONE IS CROSSED THROUGH?? |
| PLEASE SEE REDLINED PLANS AND CORRELATE. |
| 215.5 |
| |
| 25)NOTE: PLEASE SEE FEEDERS FROM "DPA" |
| TO PANEL "L4A" ARE SHOWN AS 3/0'S, |
| HOWEVER OCP ON DPA IS 400A'S. PLEASE |
| CORRELATE AND ADJUST. 240.4,310.16 |
| |
| 26)NOTE: PLEASE SPECIFY OF PANEL "L4A" |
| HAS "FEED-THRU " LUGS OR DOES THIS PANEL |
| CONTAIN OCP FEEDING THRU TO PANEL |
| "L4AA".? |
| 215.5 |
| |
| 27)NOTE: PLEASE SEE ELEVATOR CIRCUITS AS |
| LISTED ON DPA #5 AND #6 SHOWS 4-POLES? |
| FOR A 3-POLE BRKR? |
| PLEASE ALSO SEE DPB #5 AND #6 AS THIS |
| SHOWS THE SAME THING. |
| 215.5 |
| |
| 28)NOTE: PLEASE SEE "L1BA" WHICH IS |
| SHOWN AS A 100A PANEL YET IS BEING FED |
| WITH A 225A BRKR FROM DPB. |
| |
| 29)NOTE: PLEASE SEE PANEL "LPB" WHICH IS |
| SHOWN AS 200A PANEL, HOWEVER PANEL IS |
| BEING FED WITH A 225A BRKR FROM "DPB". |
| PLEASE CORRLEATE. |
| |
| 30)NOTE: PLEASE SEE 620.23,620.24 WHICH |
| REQUIRES DEDICATED CIRCUITS FOR ELEVATOR |
| PIT LTS AND RECEPTS. THIS CIRCUIT MAY |
| NOT FEED ANY OTHER LTS AND RECEPTS. |
| THESE SHALL ALSO BE DEDICATE TO EACH |
| ELEVATOR/PIT. |
| PLEASE SEE CIRCUITS FOR ELEVATOR |
| EQUIPMENT ROOMS SHALL ALSO BE DEDICATED |
| AND MAY NOT FEED ANY OTHER ROOMS OR |
| ELECTRICAL LIGHTING OR RECEPTS. |
| PLEASE ALSO SEE PREVIOUS NOTE WHICH IS |
| REQUIRING A BATTERY BACK-UP FIXTURE IN |
| THESE ROOMS. |
| PLEASE ALSO SEE 700.16D |
| |
| 31)NOTE: PLEASE PROVIDE A NOTE ON SHEETS |
| FOR ELECTRICAL/ ELEVATOR ROOMSWHICH |
| SHOULD STATE ALL REQUIRED CLEARENCES PER |
| 110.26 SHALL BE MET FOR ALL ELECTRICAL |
| EQUIPMENT. (OR WORDS TO THAT AFFECT). |
| 110.26 |
| THIS HAS BEEN AN ISSUE IN THIS |
| JURISDICTION FOR MAINS/METER CENTERS FOR |
| HEIGHT AND WIDTH OF EQUIPMENT. |
| |
| 32)NOTE: PLEASE PLACE NOTE ON "ROOF-TOP" |
| PLANS WHICH WILL STATE > |
| "ANY LIGHTNING PROTECTION SYSTEMS WILL |
| BE REQUIRED TO BE SUBMITTED UNDER A |
| SEPARATE PERMIT AND PLANS." |
| "ALL SYSTEMS SHALL MEET NFPA-780." |
| |
| 33)NOTE: PLEASE SEE RISER DIAGRAM SEEMS |
| TO SHOW ELEVATOR EQUIPMENT/ DISCONNECTS, |
| ETC ON 2ND FLR, HOWEVER PLANS FOR ROOMS |
| ON E7.1, APPEAR TO SHOW THIS EQUIPMENT |
| LOCATED ON 1ST FLR?? |
| |
| ** PLEASE KNOW, MANY OF THE ABOVE ITEMS |
| HAVE BEENREDLINED ON PLANS FOR AREAS |
| OF COMMENTS. |
| |
| **PLEASE SEE ALL COMMENTS FROM ALL OTHER |
| TRADES WHICH MAY AFFECT ELECTRICAL |
| PLANS. |
| PLEASE SEE FIRE REVIEW COMMENTS. |
| |
| ** PLEASE REMOVE ALL OLD/VOIDED SHEETS |
| FROM SETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO COMPLETE SETS FOR REVIEW AND |
| STAMPING. ONE SET OF ALL OL/VOIDED |
| SHEETS SHOULD BE SUBMITTED FOR |
| REFERENCE. |
| |
| ** PLEASE SUBMIT THE ABOVE INFORMATION |
| FOR REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DONOT HESITATE IN CONTACTING |
| THIS OFFICE. |
| |