Plan Review Notes
Plan Review Notes For Permit 05090114
Permit Number 05090114
Review Stop B
Sequence Number 2
Notes
Date Text
2005-11-15 00:00:001) A NOTORIZE LETTER SIGNED BY THE OWNER
 AGREEING TO STATEMENT IN THE 2004 FBC
 SEC.3105.5. WHICH STATES THAT THE AWNING
 SHALL BE REMOVED OR REPOSITIONED DURING
 PERIODS OF HIGH WINDS OF 90MPH, 3-SECOND
 WIND GUST.
  
 2)SHOW HOW AWNING WILL BE DESIGNED TO
 THE 140MPH BASIC WIND SPEED.FBC.
 1606.1.6 AND 1606.1.7 ALSO SEE 2004 FBC.
 SEC.3105.4
  
 3) AWNINGS, CANOPIES, MARQUEES AND SIGNS
 WITH LESS THAN 15 FEET CLEARANCE ABOVE
 THE SIDEWALK SHALL NOT EXTEND INTO OR
 OCCUPY MORE THAN TWO-THIRDS THE WIDTH OF
 THE SIDEWALK MEASURE FROM THE BUILDING.
 2004 FBC. 3202.3.1. SHOW THE HEIGHT OF
 THE AWNING FROM THE LOWEST POINT TO THE
 SIDE-WALK IMMEDIATELY BELOW.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL: (561)805-6726
 FAX: (561)659-8026
 [email protected]