Date |
Text |
2005-09-10 00:00:00 | ************UNSST ************* |
| |
| 1)NOTE: PLEASE SEE PLANS MENTIONS, |
| "WAREHOUSE" , HOWEVER 2ND FLR AREA SEEMS |
| TO BE CHNAGED TO A RESIDENTIAL |
| DWELLING/APT. |
| PLEASE SEE FULL KITCHEN/ BATH ETC BEING |
| PROVIDED. |
| PLEASE SEE POSSIBLE COMMENTS FROM OTHER |
| TRADES WHICH MAY AFFECT THE PLANS. |
| EGRESS INTO WAREHOUSE ETC |
| |
| 2)NOTE: PLEASE SEE FIRE REVIEWCOMMENTS |
| FOR MISSING EGRESS LT REQUIRED. PLEASE |
| SEE NFPA 101 7.8 AND 7.9 . |
| PLEASE ALSO SEE AREAS WHERE A "J"-BOX IS |
| BEING SHOWN AND NO LIGHTING IS PROVIDED. |
| PLEASE SEE BATHS ETC. |
| |
| 3)NOTE: PLEASE SHOW ALL CIRCUTING ON |
| PLANS AND CORRELATE WITH PANEL SCHEDULES |
| TO BE SUBMITTED. |
| 215.5, PLEASE ALSO SEE 700.12E WHICH |
| REQUIRES THE BRANCH CIRCUIT FEEDING THE |
| UNIT EQUIPMENT (EM/EXT LTS) SHALL BE THE |
| SAME BRANCH CIRCUIT AS THAT SERVING THE |
| NORMAL LIGHTING IN THE AREA AND |
| CONNECTED AHEAD OF ANY LOCAL SWITCHES. |
| |
| 4)NOTE: PLEASE SUBMIT A RISER DIAGRMA |
| SHOWING ANY NEW OR EXSITING ELECTRICAL |
| EQUIPMENT TO BE INSTALLED ETC. IF THIS |
| BLDG WAS DAMGED TO THE POINT AS STATED |
| ON PLANS, ALL EXISTING ELECTRICAL PANELS |
| MAY ALREADY BE REQUIRED TO BE REPLACED |
| DUE TO CONTAMINATION OF BUS/BRKRS ETC. |
| 110.11 |
| |
| 5)NOTE: PLEASE ALSO SUBMIT ELECTRICAL |
| LOAD CALCULATIONS FOR NEW ELECTRICAL . |
| 220.3,220.10,220.11,220.13 ETC. |
| PLEASE BE SURE ALL CONTINUOUS LOADS ARE |
| SHOWN AT 125%, 215.3,230.42 ETC. |
| |
| 6)NOTE: PLEASE SEE IF ZONING, BLDG ETC |
| APPROVES DWELLING UNIT ON 2ND FLR, |
| PLEASE SEE 210.8A6 FOR ALL RECEPTS |
| SERVING KITCHEN COUNTERSPACE. |
| IF USE IS GOING TO BE COMMERCIAL, THEN |
| PLEASE SEE 210.8B3 FOR KITCHENS IN OTHER |
| THAN DWELLING UNITS. |
| |
| 7)NOTE: PLEASE 600.5 FOR REQUIRED SIGN |
| CIRCUIT. |
| |
| 8)NOTE: PLEASE SEE MISSING LICENSE |
| INFORMATION REQUIRED ON TITLE BLOCK PER |
| FAC 61G1-16.004, FS 481.219 |
| PLEASE SEE MISSING CERTIFICATE OF |
| AUTHORIZATION NUMBER. |
| |
| 9)NOTE: PLEASE VERIFY HOW NEW DIPOSAL IN |
| KITCHEN WILL BE CONTROLLED. |
| |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW, IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW. |
| 561-805-6717 |
| [email protected] |