Plan Review Notes
Plan Review Notes For Permit 05090073
Permit Number 05090073
Review Stop E
Sequence Number 3
Notes
Date Text
2006-04-13 00:00:00**********UNSAT 3RD REVIEW *********
  
 1) NOTE: PLEASE SEE VALUATION FOR
 COMPLETE SCOPE OF WORK IS STILL NOT
 BEING ADJUSTED BY THE CONTRACTOR WHEN
 RESUBMITTING PLANS AND A VALUE CAN NOT
 BE VERIFIED AT THIS TIME.
 PLEASE PROVIDE ALL SIGNED CONTRACTS FOR
 EQUIPMENT BEING INSTALLED AND LABOR.
 THIS WAS REQUESTED ON TWO PREVIOUS
 REVIEWS TO ADJUST VALUE FOR SCOPE AS
 VALUE WAS WAY TOO LOW AND DID NOT
 REFLECT WORK BEING DONE.
 PLEASE SEE FBC ADMISTRATIVE SECITON
 104.6.5,2001) 108.3 2004.
 SHALL INCLUDE ALL LABOR AND MATERIALS,
 EVEN IF EQUIPMENT IS OWNER SUPPLIED.
 PLEASE SEE THIS WOULD INCLUDE, GEN,
 TANK, ATS, ELECTRICAL SERVICE, AND ALL
 EQUIPMENT BRING INSTALLED INSIDE ROOM
 ALONG WITH ANY VALUE FOR OTHER TRADES.
 PLEASE SEE ORIGINAL VALUE WAS APPLIED
 FOR AT $17K AND THENA VALUE WAS PLACED
 ON APPLICATION FOR $67K.
 PLEASE SEE APPLICATION NOW CONTAINS
 "WHITE-OUT " WHERE BACK UP DIESEL
 GENERATOR WAS? IS THIS NO LONGER IN
 SCOPE? PLANS HOWEVER STILL INDICATE A
 GENERATOR. PLEASE DESCRIBE PROJECT IN
 DETAIL ON APPLICATION AS REQUESTED ON
 APPLICATION AND CORRELATE WITH THE
 PLANS.
 IT IS NOW UNCLEAR FI GEN IS STILL PART
 OF THIS PROJECT??
  
 2) NOTE: PLEASE SEE SPECS FOR ATS IS THE
 SAME SPECS THAT WERE SUBMITTEDON THE
 PREVIOUS REVIEW.
 PLEASE SEE NO DISCONNECTING MEANS RATED
 FOR THE LOAD SERVED, GROUPED, LOCATED ON
 THE OUTSIDE OF THE EQUIPMENT COULD BE
 LOCATED.?
 230.76.230.79,230.72,225.31-225.39
  
 3) NOTE: PLEASE SUBMIT TWO COMPLETE SETS
 OF PLANS.
 PLEASE SEE ONE SET HAS MULTIPLE E-SHEETS
 WHICH ARE REPEATED AND CONTAIN TWO
 DIFFERENT DATES SIGNED, DATED AND SEALED
 BY THE ENGINEER?
 PLEASE SEE ONE SET STARTS WITH E-4 AND
 E-5 DATED 2/27/06 AND THEN STARTS OVER
 AGAIN WITHE NEWER DATED SHEETS DATED
 3/3/06??
  
  
 4) NOTE: PLEASE SEE COVER SHEET MENTIONS
 2005 NEC, WE ARE CURRENTLY UNDER THE
 2002 NEC, THIS CAN BE REDLINED.
  
 ** PLEASE SEE COMMENTS FROM MECHANICAL
 REVIEWER WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. ONCE AGAIN, IF THERE ARE ANY
 QUESTIONS, PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2006-04-12 00:00:00IN ELEC FOR REVIEW