2006-04-13 00:00:00 | **********UNSAT 3RD REVIEW ********* |
| |
| 1) NOTE: PLEASE SEE VALUATION FOR |
| COMPLETE SCOPE OF WORK IS STILL NOT |
| BEING ADJUSTED BY THE CONTRACTOR WHEN |
| RESUBMITTING PLANS AND A VALUE CAN NOT |
| BE VERIFIED AT THIS TIME. |
| PLEASE PROVIDE ALL SIGNED CONTRACTS FOR |
| EQUIPMENT BEING INSTALLED AND LABOR. |
| THIS WAS REQUESTED ON TWO PREVIOUS |
| REVIEWS TO ADJUST VALUE FOR SCOPE AS |
| VALUE WAS WAY TOO LOW AND DID NOT |
| REFLECT WORK BEING DONE. |
| PLEASE SEE FBC ADMISTRATIVE SECITON |
| 104.6.5,2001) 108.3 2004. |
| SHALL INCLUDE ALL LABOR AND MATERIALS, |
| EVEN IF EQUIPMENT IS OWNER SUPPLIED. |
| PLEASE SEE THIS WOULD INCLUDE, GEN, |
| TANK, ATS, ELECTRICAL SERVICE, AND ALL |
| EQUIPMENT BRING INSTALLED INSIDE ROOM |
| ALONG WITH ANY VALUE FOR OTHER TRADES. |
| PLEASE SEE ORIGINAL VALUE WAS APPLIED |
| FOR AT $17K AND THENA VALUE WAS PLACED |
| ON APPLICATION FOR $67K. |
| PLEASE SEE APPLICATION NOW CONTAINS |
| "WHITE-OUT " WHERE BACK UP DIESEL |
| GENERATOR WAS? IS THIS NO LONGER IN |
| SCOPE? PLANS HOWEVER STILL INDICATE A |
| GENERATOR. PLEASE DESCRIBE PROJECT IN |
| DETAIL ON APPLICATION AS REQUESTED ON |
| APPLICATION AND CORRELATE WITH THE |
| PLANS. |
| IT IS NOW UNCLEAR FI GEN IS STILL PART |
| OF THIS PROJECT?? |
| |
| 2) NOTE: PLEASE SEE SPECS FOR ATS IS THE |
| SAME SPECS THAT WERE SUBMITTEDON THE |
| PREVIOUS REVIEW. |
| PLEASE SEE NO DISCONNECTING MEANS RATED |
| FOR THE LOAD SERVED, GROUPED, LOCATED ON |
| THE OUTSIDE OF THE EQUIPMENT COULD BE |
| LOCATED.? |
| 230.76.230.79,230.72,225.31-225.39 |
| |
| 3) NOTE: PLEASE SUBMIT TWO COMPLETE SETS |
| OF PLANS. |
| PLEASE SEE ONE SET HAS MULTIPLE E-SHEETS |
| WHICH ARE REPEATED AND CONTAIN TWO |
| DIFFERENT DATES SIGNED, DATED AND SEALED |
| BY THE ENGINEER? |
| PLEASE SEE ONE SET STARTS WITH E-4 AND |
| E-5 DATED 2/27/06 AND THEN STARTS OVER |
| AGAIN WITHE NEWER DATED SHEETS DATED |
| 3/3/06?? |
| |
| |
| 4) NOTE: PLEASE SEE COVER SHEET MENTIONS |
| 2005 NEC, WE ARE CURRENTLY UNDER THE |
| 2002 NEC, THIS CAN BE REDLINED. |
| |
| ** PLEASE SEE COMMENTS FROM MECHANICAL |
| REVIEWER WHICH MAY AFFECT ELECTRICAL |
| PLANS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. ONCE AGAIN, IF THERE ARE ANY |
| QUESTIONS, PLEASE DO NOT HESITATE IN |
| CONTACTING THIS OFFICE. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-805-6717 |
| [email protected] |
2006-04-12 00:00:00 | IN ELEC FOR REVIEW |