Plan Review Notes
Plan Review Notes For Permit 05090073
Permit Number 05090073
Review Stop P
Sequence Number 2
Notes
Date Text
2006-02-11 00:00:00PLUMBING PLAN REVIEW EXAMINER
 PAUL SCHMITZ 561-805-6692
 FBC PLUMBING 2004
 FBC FUEL GAS 2004
 FBC BUILDING 2004, CH 11
 DENIED
 NEW COMMENTS
  
 1) SHT.P-1 WATER RISER.
 604.9 WATER HAMMER.
 THE FLOW VELOCITY OF THE WATER
 DISTRIBUTION SYSTEM SHALL BE CONTROLLED
 TO REDUCE THE POSSIBILITY OF WATER
 HAMMER. A WATER-HAMMER ARRESTOR SHALL BE
 INSTALLED WHERE QUICK-CLOSING VALVES ARE
 UTILIZED. WATER-HAMMER ARRESTORS SHALL
 BE INSTALLED IN ACCORDANCE WITH THE
 MANUFACTURER?S SPECIFICATIONS.
 WATER-HAMMER ARRESTORS SHALL CONFORM TO
 ASSE 1010.
  
 2)SHT.P-1 WATER RISER.
 606.1 LOCATION OF FULL-OPEN VALVES.
 FULL-OPEN VALVES SHALL BE INSTALLED IN
 THE FOLLOWING LOCATIONS:
 4.ON THE TOP OF EVERY WATER DOWN-FEED
 PIPE IN OCCUPANCIES OTHER THAN ONE- AND
 TWO-FAMILY RESIDENTIAL OCCUPANCIES.
  
 3)SHT.P-1 WATER RISER, DEHUM 1,2
 608.3 DEVICES, APPURTENANCES, APPLIANCES
 AND APPARATUS.
 ALL DEVICES, APPURTENANCES, APPLIANCES
 AND APPARATUS INTENDED TO SERVE SOME
 SPECIAL FUNCTION, SUCH AS STERILIZATION,
 DISTILLATION, PROCESSING, COOLING, OR
 STORAGE OF ICE OR FOODS, AND THAT
 CONNECT TO THE WATER SUPPLY SYSTEM,
 SHALL BE PROVIDED WITH PROTECTION
 AGAINST BACKFLOW AND CONTAMINATION OF
 THE WATER SUPPLY SYSTEM. WATER PUMPS,
 FILTERS, SOFTENERS, TANKS, COMMERCIAL
 DRINKING WATER DISPENSERS AND ALL OTHER
 APPLIANCES AND DEVICES THAT HANDLE OR
 TREAT POTABLE WATER SHALL BE PROTECTED
 AGAINST CONTAMINATION.
  
 4)SHT A-3 MINIMUM NUMBER OF REQUIRED
 PLUMBING FIXTURES. TAB.403.1
 4 FACTORY AND INDUSTRIAL STRUCTURES IN
 WHICH OCCUPANTS ARE ENGAGED IN WORK
 FABRICATING, ASSEMBLY OR PROCESSING OF
 PRODUCTS OR MATERIALS.
 1 SERVICE SINK REQUIRED.
  
 END OF COMMENTS, QUESTIONS 561-805-6692