Plan Review Notes
Plan Review Notes For Permit 05090073
Permit Number 05090073
Review Stop E
Sequence Number 2
Notes
Date Text
2006-01-11 00:00:00**** UNSAT 2ND REVIEW ******
  
 PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW STTILL NEED TO BE ADDRESSED.
 PLEASE ALSO SEE NEW NOTES DUE TO SOME
 CHANGES IN PLANS.
  
  
 1)NOTE: NOTE #1 NO.
 THE PERMIT APPLICATION NOW MENTIONS A
 VALUE OF $67,000, HOWEVER THIS VALUE IS
 NOT APPROPRIATE FOR SCOPE OF WORK, ALL
 LABOR AND MATERIALS.
 PLEASE KNOW, EVEN IF EQUIPMENT IS OWNER
 SUPPLIED, THE VALUE SHALL BE INLCUDED.
 WHEN RESUBMITTED , PLEASE HAVE VALUE
 INCREASED AT THAT TIME. IF VALUE IS NOT
 ADJUSTED FOR THE FOLLOWING REVIEW, ONE
 WILL BE ASSESSED. 104.6.5
  
 2)NOTE: NOTE #2 OK.
  
 3)NOTE: NOTE #3 NO, PLEASE SEE PANEL DP1
 IS NOW BEING SHOWN AS A MCB, HOWEVER
 PLEASE SEE FEEDERS FROM ATS (FIRST MEANS
 OF DISCONNECT) TO THIS DP1. AS PER SPECS
 FOR ATS SUBMITTED, THE ATS DOES NOT
 CONTAIN A MANUAL MEANS OF DISCONNECT
 LOCATED ON THE OUTSIDE OF THE EQUIPMENT
 RATED FOR THE LOAD SERVED AS REQUIRED
 PER 230.76, 230.79.
 PLEASE SEE THE SPECS DO INDICATE A
 MANUAL SWITCH, HOWEVER NOTES AS BEING
 FOR NEMA 1 LOCATION ONLY. PLEASE SEE
 THIS ATS IS LOCATED OUTSIDE.
 THIS ATS ALSO NOT INDICATE BEING RATED
 AS SERVICE ENTRANCE AS REQUIRED.
 PLEASE SEE A DISCONNECTING MEANS MAY BE
 INSTALLED FROM METER/CT TO THE ATS AND
 ANOTHER DISCONNECT FROM GEN TO ATS,
 GROUPED AS REQUIRED BY 230.72,225.34 AND
 THE MCB WOULD NOT BE REQUIRED IN PANEL
 DP1.
 THIS IS ONLY ONE POSSIBLE METHOD.
  
 4)NOTE: NOTE #4 OK.
  
 5)NOTE: NOTE #5 OK.
  
 6)NOTE: NOTE #6 OK.
  
 7)NOTE: NOTE # 7 OK.
  
 8)NOTE: NOTE #8 OK, HOWEVER PLEASE SEE
 NOTES FOR REVIEW OF SPECS.
  
 9)NOTE: NOTE # 9 OK.
  
 NEW NOTE;
  
 1)NOTE: PLEASE SEE PLANS WERE ORIGINALLY
 SINED , DATED AND SEALED BY AN ENGINEER
 OF RECORD AS REQUIRED, HOWEVER NOW PLANS
 ARE COMING BACK SIGNED AND SEALED BY AN
 ARCH??
 PLEASE SEE SCOPE OF WORK REQUIRES THE
 EELCTRICAL PLANS TO BE DONE BY AN
 ENGINEER AND ANOTHER DESIGNER MAY NOT
 SIGN AND SEAL ANOTHER DESIGNERS WORK.
 FS 481, 471.
  
 PLEASE SEE OTHER POSSIBLE COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]