Plan Review Notes
Plan Review Notes For Permit 05090073
Permit Number 05090073
Review Stop P
Sequence Number 1
Notes
Date Text
2005-11-12 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
  
 1. ALL SHEETS, ADDRESS IS OKEECHOBEE RD,
 NO "OLD" IN ADDRESS. PLEASE CORRECT
 TITLE BLOCK INFORMATION. FAC
 61G1-16.004(3).
 2. SHT A-3 SPECIAL NOTE: REFERENCE
 11-4.1.2 IS FOR NEW CONSTRUCTION.
 REFERENCE TO USE FOR ALTERNATIONS IS
 11-4.1.6(K)(III). PLEASE CHANGE
 REFERENCE.
 3. SHT P-0 CODES AND STANDARDS, CODES
 AD0PTED ARE FBC-2004 NOT THE STANDARD
 CODES. PLEASE CHANGE CODE REFERENCE.
 - PLUMBING & DRAINAGE PIPING. REFERENCE
 TO STANDARD CODE TO BE CHANGED TO
 FBC-2004.
 - SOLDER SHALL CONFORM TO ASTM B 32.
 4. SHT P-1 MINIMUM 1 VENT THRU ROOF PER
 BUILDING PER SECTION 903.1. INDICATE THE
 LOCATION OF THE VTR FOR THIS BUILDING.
 5. SHT P-1 SANT. RISER (DETAIL D) DOES
 NOT REFLECT THE FLOOR LAYOUT (DETAIL B).
 THE FLOOR DRAIN IS SHOWN CONNECTING AT
 THE LAV ARM ON THE FLOOR PLAN. PLEASE
 CORRELATE RISER AND FLOOR PLAN. SECTION
 106.1.1.
 6. SHT P-1 DETAIL E AIR CHAMBERS ARE NOT
 APPROVED. DELETE FROM RISER DIAGRAM.
 SECTION 604.9
 7. SUBMIT MANUF. SPECIFICATION SHEETS
 FOR THE INSTA HOT WATER HEATER. MUST BE
 LISTED. SECTION303.4 & TABLE 303.4.
 8. SHT P-2 DETAIL DOES NOT REFLECT THE
 WATER RISER DIAGRAM. PLEASE CORRELEATE.
 SECTION 106.1.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]