2005-11-09 00:00:00******DENIED******
  
 1) PLEASE PROVIDE MANUFACTURER SPEC
 SHEETS FOR FIRE SUPPRESSION AND ALARM
 SYSTEMS.
  
 2) 2A-10B,C RATED FIRE EXTINGUISHERS ARE
 STILL REQUIRED TO BE MOUNTED SO THAT
 TRAVEL DISTANCE DOESN'T EXCEED 75'.
  
 3) PLEASE PROVIDE (2) COPIES OF
 MANUFACTURER SPEC SHEETS FOR GENERATOR.
  
 4) DOES THE STORE ROOM MEET THE
 REQUIREMENT FOR A SINGLE EXIT IN
 ACCORDANCE WITH NFPA 101, 2003 EDITION?
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722