Plan Review Notes
Plan Review Notes For Permit 05090073
Permit Number 05090073
Review Stop E
Sequence Number 1
Notes
Date Text
2005-09-30 00:00:00************** UNSAT ************
  
 1)NOTE: PLEASE SEE VALUATION SHALL BE
 BASED ON ALL LABOR AND MATERIALS EVEN IF
 MATERIALS ARE OWNER SUPPLIED.
 THIS WOULD ALSO INCLUDE ALL OTHER
 PERMANANTLY INSTALLED EQUIPMENT IE: DC
 SYSTEM, ETC
 PLEASE KNOW A VALUE WILL BE ACCESSED BY
 THIS OFFICE IF NOT ADJUSTED BY
 CONTRACTOR.
 THIS WOULD INCLUDE ALL ELECTRICAL
 EQUIPMENT , GENERATOR ETC.
 FBC 104.6.5, ADMINISTRATIVE AMENDMENTS.
  
 2)NOTE: PLEASE CORRELATE PLANS, ONE
 SHEET INDICATES GENERATOR TO BE A MOBILE
 UNIT WITH SOME SORT OF TAP BOX?
 PLANS AND SUBMITTALS ALSO DO NOT REFLECT
 THIS AND SHOWS A PERMANANTLY INSTALLED
 GEN ETC.??
 215.5
  
 3)NOTE: PLEASE INSTALLED A DISCONNECT
 FOR FEEDERS COMING FROM GENERATOR AT
 BLDG.
 THIS MEANS OF DISC SHALL BE GROUPED WITH
 OTHER MAINS AND RATED FOR THE LOAD
 SERVED.
 PLEASE SEE 225.31-225.39,110.27 ETC.
 A MCB MAY BE INSTALLED IN DP1 WHICH NOW
 INDICATES BEING A MLO.
 SIGNAGE WILL BE REQUIRED, 230.2E, 702.8
 ETC
  
 4)NOTE: PLEASE CLARIFY DOOR/ WINDOW
 WHICH IS SHOWN ON PLANS?
 IF A MEANS OF EXIT, SEE FIRE REVIEW
 COMMENTS FOR ANY EXT LT WHICH MAY BE
 REQUIRED.
  
 5)NOTE: PLEASE SEE "TAP BOX" AS SHOWN
 WILL NOT MEET THE DISCONNECTING MEANS
 REQUIRED.
  
 6)NOTE: PLEASE SHOW LOCATION OF ALL ASSC
 GEN EQUIPMENT.
 PLEASE SHOW LOCATION OF GEN STATUS
 PANEL.
 215.5
  
 7)NOTE: PLEASE INCLUDED COLD WATER PIPE
 IN GROUNDING DETAIL FOR SERVICE.
 250.50
  
 8)NOTE: PLEASE SUBMIT TWO COPIES OF ALL
 MANUFACTURES SPEC/CUT SHEETS FOR GEN
 ETC.
 PLEASE SEE ONLY ONE SET WAS SUBMITTED.
 PLEASE ALSO INLCUDE SPECS/CUT SHEETS FOR
 ATS.
 PLEASE ALSO SUBMIT ALL SPECS/INFORMATION
 ON DC SYSTEM PROPOSED.
 THIS EQUIPMENT
  
 9)NOTE: PLEASE SEE PERMIT APPLICATION
 MENTIONS ADDRESS AS "OLD OKEECHOBEE"
 PLEASE KNOW AND SEE BLDG REVIEW
 COMMENTS, THIS SHOULD READ "OKEECHOBEE
 RD".
 PLEASE ALSO ADJUST ON PLANS/TITL BLOCK.
  
  
 PLEASE COMPLETELY REMOVE ANY OLD/VOIDED
 SHEETS FROM SETS AND ONLY INSERT NEW
 REVISED SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING.
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
2005-09-29 00:00:00NOTES TO FOLLOW.
 PLANS WILL BE IN "F" STATUS.