2005-09-30 00:00:00 | ************** UNSAT ************ |
| |
| 1)NOTE: PLEASE SEE VALUATION SHALL BE |
| BASED ON ALL LABOR AND MATERIALS EVEN IF |
| MATERIALS ARE OWNER SUPPLIED. |
| THIS WOULD ALSO INCLUDE ALL OTHER |
| PERMANANTLY INSTALLED EQUIPMENT IE: DC |
| SYSTEM, ETC |
| PLEASE KNOW A VALUE WILL BE ACCESSED BY |
| THIS OFFICE IF NOT ADJUSTED BY |
| CONTRACTOR. |
| THIS WOULD INCLUDE ALL ELECTRICAL |
| EQUIPMENT , GENERATOR ETC. |
| FBC 104.6.5, ADMINISTRATIVE AMENDMENTS. |
| |
| 2)NOTE: PLEASE CORRELATE PLANS, ONE |
| SHEET INDICATES GENERATOR TO BE A MOBILE |
| UNIT WITH SOME SORT OF TAP BOX? |
| PLANS AND SUBMITTALS ALSO DO NOT REFLECT |
| THIS AND SHOWS A PERMANANTLY INSTALLED |
| GEN ETC.?? |
| 215.5 |
| |
| 3)NOTE: PLEASE INSTALLED A DISCONNECT |
| FOR FEEDERS COMING FROM GENERATOR AT |
| BLDG. |
| THIS MEANS OF DISC SHALL BE GROUPED WITH |
| OTHER MAINS AND RATED FOR THE LOAD |
| SERVED. |
| PLEASE SEE 225.31-225.39,110.27 ETC. |
| A MCB MAY BE INSTALLED IN DP1 WHICH NOW |
| INDICATES BEING A MLO. |
| SIGNAGE WILL BE REQUIRED, 230.2E, 702.8 |
| ETC |
| |
| 4)NOTE: PLEASE CLARIFY DOOR/ WINDOW |
| WHICH IS SHOWN ON PLANS? |
| IF A MEANS OF EXIT, SEE FIRE REVIEW |
| COMMENTS FOR ANY EXT LT WHICH MAY BE |
| REQUIRED. |
| |
| 5)NOTE: PLEASE SEE "TAP BOX" AS SHOWN |
| WILL NOT MEET THE DISCONNECTING MEANS |
| REQUIRED. |
| |
| 6)NOTE: PLEASE SHOW LOCATION OF ALL ASSC |
| GEN EQUIPMENT. |
| PLEASE SHOW LOCATION OF GEN STATUS |
| PANEL. |
| 215.5 |
| |
| 7)NOTE: PLEASE INCLUDED COLD WATER PIPE |
| IN GROUNDING DETAIL FOR SERVICE. |
| 250.50 |
| |
| 8)NOTE: PLEASE SUBMIT TWO COPIES OF ALL |
| MANUFACTURES SPEC/CUT SHEETS FOR GEN |
| ETC. |
| PLEASE SEE ONLY ONE SET WAS SUBMITTED. |
| PLEASE ALSO INLCUDE SPECS/CUT SHEETS FOR |
| ATS. |
| PLEASE ALSO SUBMIT ALL SPECS/INFORMATION |
| ON DC SYSTEM PROPOSED. |
| THIS EQUIPMENT |
| |
| 9)NOTE: PLEASE SEE PERMIT APPLICATION |
| MENTIONS ADDRESS AS "OLD OKEECHOBEE" |
| PLEASE KNOW AND SEE BLDG REVIEW |
| COMMENTS, THIS SHOULD READ "OKEECHOBEE |
| RD". |
| PLEASE ALSO ADJUST ON PLANS/TITL BLOCK. |
| |
| |
| PLEASE COMPLETELY REMOVE ANY OLD/VOIDED |
| SHEETS FROM SETS AND ONLY INSERT NEW |
| REVISED SHEETS INTO COMPLETE SETS FOR |
| REVIEW AND STAMPING. |
| |
| PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| OTHER TRADES WHICH MAY AFFECT ELECTRICAL |
| PLANS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE IN CONTACTING |
| THIS OFFICE. |
| |