2005-11-07 00:00:00 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBC FLORIDA BUILDING CODE 2004 |
| FBC* CITY OF WEST PALM BEACH AMENDMENTS |
| TO THE FBC2004 |
| |
| 1.)A NOTICE OF COMMENCEMENT MUST BE |
| FILED WITH THE CLERK OF COURTS BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2.)DECLARE THE OCCUPANCY FOR THIS |
| IMPROVEMENT THE OCCUPANCY FOR THE |
| ADJACENT TENANT. |
| |
| 3.)THE BUILDING IS REQUIRED TO BE |
| ACCESSIBLE.THERE ARE EXCEPTIONS IN THE |
| CODE RELATED TO VERTICAL ACCESSIBILITY |
| OR IN CASES WHERE IT IS STRUCTURALLY |
| IMPRACTICABLE, BUT THESE EXCEPTIONS DO |
| NOT APPLY.SEE FBC11-4.1.1(3), AREAS |
| USED ONLY BY EMPLOYEES AS WORK AREAS. |
| |
| 4.)SHOW ACCESSIBLE ROUTE, |
| FBC11-4.1.2(1). |
| |
| 5.)THE BATHROOM IS TO BE ACCESSIBLE. |
| PROVIDE ALL DETAILS INCLUDING ALL |
| DIMENSIONS.FBC11. |
| |
| 6.)FBC11-4.1.3(9), ACCESSIBLE MEANS OF |
| EGRESS SHALL BE PROVIDED IN THE SAME |
| NUMBER AS REQUIRED FOR EXITS BY LOCAL |
| BUILDING/LIFE SAFETY REGULATIONS.IT |
| APPEARS THAT ONLY THE FRONT DOOR IS AN |
| ACCESSIBLE EXIT.THE OTHER TWO APPEAR |
| TO HAVE A LANDING OUTSIDE THE DOOR. |
| |
| 7.)FOR THE EXISTING 2 HOUR WALL, |
| PROVIDE AN APPROVED ASSEMBLY OR |
| CALCULATED FIRE RESISTANCE, FBC7. |
| |
| 8.)FOR THE INFILL FOR THE 2 HOUR WALL, |
| PROVIDE AN APPROVED ASSEMBLY OR |
| CALCULATED FIRE RESISTANCE, FBC7. |